Prosine 2.5/3.0 Installation & Operation Guide
9
Section 2: Controls and Indicators
Fault LED
This LED flashes on-and-off during an error condition from which the unit will
automatically recover and restart when the condition is remedied. The
FAULT
LED will be lighted
steadily when any error occurs from which the inverter/charger cannot automatically recover. It is
usually necessary to disconnect the AC or DC supply to recover from this type of error. An error
condition is accompanied by an audible alarm if the alarm is enabled.
Temp LED
This LED flashes on-and-off to indicate that the internal temperature of the Prosine
inverter/charger is too high and the unit has shutdown. When the internal temperature of the unit cools
sufficiently, the inverter/charger will automatically restart. The audible alarm that accompanies this
condition (if enabled) will also be silenced upon auto-restart.
Reset Button
The
RESET
button on the Faults panel has two functions: pressed and released, it
will silence the audible alarm which, if enabled, will sound an insistent intermittent tone anytime an
error condition occurs, which can be looked up in a table to determine the nature of the error. Press
and hold the
RESET
button to display error codes. Error codes are listed in an Appendix to this
manual.
Inverter Status Indicators and On/Off Button
Invert LED
When the green LED labeled
INVERT
is flashing,
shorepower is not present, Load Sense is enabled, and no AC
loads exceed the Load Sense threshold. The inverter is not
producing AC power from the batteries. When the
INVERT
LED is lighted steadily, shorepower is not present and the
inverter is producing AC power from the batteries. The
INVERT
LED is not lighted when shorepower
is present.
Standby LED
When the amber LED labeled
STANDBY
is lighted steadily, shorepower is present
and the inverter will pass AC power through to any AC loads that may be present.
If shorepower should fail or be removed while the inverter is in Standby mode, the inverter will
automatically begin to produce AC power from the batteries, and the
INVERT
LED will be lighted.
On/Off Button.
A button labeled
ON/OFF
is provided adjacent to the
INVERT
and
STANDBY
LEDs. When pressed, this button switches the inverter from On to Standby mode. Use in conjunction
with the charger’s
ON/OFF
button to set the startup inverter/charger mode. See
for instructions on how to set the startup inverter/charger mode.
Summary of Contents for Prosine PS2.5 and
Page 1: ...Xantrex ProsineTM 2 5 and 3 0 Inverter Chargers Installation and Operation Guide PS2 5 PS3 0...
Page 2: ...ProsineTM PS2 5 Inverter Charger PS3 0 Inverter Charger Installation and Operation Guide...
Page 9: ...vi Prosine 2 5 3 0 Installation Operation Guide Figure 1 Inverter Charger Components...
Page 13: ...Return Procedure x Prosine 2 5 3 0 Installation Operation Guide...
Page 21: ...Inverter Features 4 Prosine 2 5 3 0 Installation Operation Guide...
Page 41: ...Battery Temperature Sensor 24 Prosine 2 5 3 0 Installation Operation Guide...
Page 75: ...Operating Limits for Inverter Operation 58 Prosine 2 5 3 0 Installation Operation Guide...
Page 83: ...Operating Limits for Charger Operation 66 Prosine 2 5 3 0 Installation Operation Guide...
Page 95: ...Cabling Hook up Configurations 78 Prosine 2 5 3 0 Installation Operation Guide...
Page 101: ...84 Prosine 2 5 3 0 Installation Operation Guide...