Part 3: Configuration Options
445-0089-01-01
4–9
Low AC Transfer
(V)
This is the voltage below which the unit will no longer recognize AC as “good”,
will open the relay, and will attempt to transfer to Invert mode if Invert is
Enabled
. The range of values is
85–110Vac
.
Low AC Transfer
(Hz)
This the frequency at which the unit will no longer recognize AC as “good” and
will attempt to transfer to Invert mode. The range is
40–59Hz
.
High AC Transfer
(V)
This is the voltage above which the unit will no longer recognize AC as “good”
and will attempt to transfer to Invert. The range is
120–135Vac
.
High AC Transfer
(Hz)
This the frequency at which the unit will no longer recognize AC as “good” and
will attempt to transfer to Invert. The range is
61–70Hz
.
AC Series Mode
Select
Standalone
if you are operating a single PROsine to produce 120V single
phase.
If you are installing two PROsines as a 240 split-phase system, set one PROsine
as
Master
and the other as
Slave
.
Inverter Low V
Shutdown
At or below this battery voltage, the inverter will shut down. The values range
from
10–16Vdc
.
Inverter Low V
Warning
This is an offset voltage ranging from
0 to 3.0V
. When the battery voltage drops
below the sum of
Low V Shutdown
and
Low V Warning
, the PROsine will
sound a warning.
Inverter Low V
Restart Hysteresis
This is an offset voltage ranging from
0.5 to 2.5V
. When the unit has shut down
due to low battery voltage it will not automatically restart until the battery voltage
recovers to the sum of
Inverter Low V Shutdown
and
Inverter Low V Restart
Hysteresis
. When the PROsine shuts down the battery voltage will rise and may
cause the PROsine to restart, which drops the voltage again so the PROsine shuts
down, etc. This hysteresis setting reduces this problem. The default value is
2.5V
and should not be changed unless there is a special reason for doing so or this
problem will return.
Run Without Panel
Select
Yes
if you want the PROsine to continue running if the display panel is
disconnected or the communication cable is damaged.
Inverter Enabled on
Reset Without Panel
Select
Yes
if you want the inverter to be enabled on startup if no panel is detected
after 10 seconds.
Charger Enabled on
Reset Without Panel
Select
Yes
if you want the charger to be enabled on startup if no panel is detected
after 10 seconds.
Summary of Contents for PROsine 2.0
Page 1: ...PROsine 2 0 Inverter Charger User s Manual...
Page 2: ......
Page 3: ...PROsine 2 0 Inverter Charger User s Manual...
Page 8: ...vi...
Page 12: ...x...
Page 18: ...xvi...
Page 20: ...xviii...
Page 68: ...Installation 3 26 445 0089 01 01...
Page 120: ...Series Operation 7 12 445 0089 01 01...
Page 128: ...A 8...
Page 132: ...B 4...
Page 147: ......