Adjusting Settings in Configuration Mode
54
Freedom XC Owner's Guide
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Inverter Output Power
Limit Timer
10
300
1
to
300
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-second increments. When the range is from 20 to
300, the timer setting value can be adjusted by 10-second
increments.
Use with Inverter Output Power especially when pairing with a
lithium ion battery. The timer is automatically disabled if the
maximum Inverter Output Power limit is selected.
Transfer Mode
11
APL
APL
(appliance)
UPS
(UPS)
Selecting
APL
- appliance sets the transfer time from line to battery
to 20 ms. Selecting
UPS
(uninterruptible power supply) sets the
transfer time from line to battery to 10 ms.
NOTE
: Do not connect
motor loads when in UPS transfer mode. See
Utility AC Under Voltage
Level
12
90
85
to
110
Inverter Shutdown
Recovery
13
MAT
At0
(auto-
restart)
MAT
(manual
restart)
The inverter shuts down when there is an over temperature,
overload, and short circuit condition. Selecting
ATO
(auto-restart)
will allow the inverter/charger to recover automatically from a
shutdown up to three times maximum. Selecting
MAT
(manual
restart) allows the user to restart the inverter/charger by performing
a manual reset, that is, by acknowledging the restart via the
display panel.
Summary of Contents for Freedom XC 1000
Page 1: ...Freedom XC Inverter Charger Owner s Guide Freedom XC 1000 817 1050 Freedom XC 2000 817 2080 ...
Page 6: ...This page is intentionally left blank 2 ...
Page 22: ...This page is intentionally left blank 2 ...
Page 28: ...This page is intentionally left blank 2 ...
Page 56: ...This page is intentionally left blank 2 ...
Page 98: ...This page is intentionally left blank 2 ...