Adjusting Settings in Configuration Mode
52
Freedom XC Owner's Guide
Settings
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Inverter Ignition Control
01
OFF
OFF
LOT
ATO
See
Description of Ignition Control Features on page 37
LBCO Voltage
02
10
.
5
10
.
0
to
12
.
8
The voltage setting value can be adjusted by 0.1 increments. The
inverter is able to recover automatically at LBCO v
0.2 volts.
LBCO Shutdown Delay
Timer
03
300
1
to
300
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-second increments. When the range is from 20 to
300, the timer setting value can be adjusted by 10-second
increments.
LBCO Recovery Voltage
04
13
.
1
12
.
0
to
16
.
0
and
OFF
The range is from LBCO v 0.2 to 16, adjusted by 0.1
increments. Selecting
OFF
or a higher value than the battery’s
actual fully-charged voltage level will disable the auto-recovery
feature. You may manually reset the inverter/charger when the low
battery cut off event occurs.