Troubleshooting Reference
90
Freedom X 1200 Owner's Guide
Problem
Possible Cause
Solution
No output voltage is shown in the LCD
screen but the green status LED for
Battery mode is illuminated.
GFCI (when installed) has tripped
or supplementary breaker has
tripped.
Check load and reset the GFCI or supplementary
breaker.
Circuit breaker on the AC load
panel or AC output disconnect has
tripped.
Reset the circuit breaker or check the AC output
disconnect circuits.
Battery voltage is too low
(depending on setting, see
Maintaining the Freedom X 1200
Unit on page 82
) to start inverting.
LCD screen may show DC voltage
as
000
.
Check DC connections and cable.
Recharge battery.
No output voltage is shown in the LCD
screen and neither of the green status
LEDs (for Grid mode and Battery mode)
is illuminated.
AC shore power is not available or
out of operating range and the
inverter is OFF.
Check AC shore power.
Turn the inverter ON.
AC shore power is not available
and the inverter is OFF due to a
shutdown for more than 30 s.
Check AC shore power and battery voltage.
Turn the inverter ON and look at the LCD screen for any
error code.