background image

6

2.0  INSTALLATION

©2000 Xantrex Technology Inc.

Pre-installation

NOTE: Before installing the inverter/charger, read all instructions and cautionary markings located in

this manual.

NOTE: The inverter/charger can weigh up to 45 lb. (20.4 kg) depending upon configuration.  Always

use proper lifting techniques during installation to prevent personal injury.

Location

•

Inverters contain sophisticated electronic components and should be located in a well

protected, dry environment away from sources of fluctuating or extreme temperatures and

moisture. Exposure to saltwater is particularly destructive and potentially hazardous.

NOTE: If the inverter is installed in a location where it is exposed to a corrosive or condensing

environment, and fails due to corrosion, it will not be covered under warranty.

•

Locate the inverter as close to the batteries as possible in order to keep the battery cable

length short. However, do not locate the inverter above the batteries or in the same

compartment as vented batteries. Batteries generate hydrogen sulfide gas which is corrosive

to electronic equipment. They also generate hydrogen and oxygen. If accumulated, an arc

caused by connecting the battery cables or switching a relay could ignite this mixture.

Mounting the inverter in a ventilated enclosure with sealed batteries is acceptable.

NOTE: Inverters can generate RFI (Radio Frequency Interference). Locate any sensitive electronic

equipment susceptible to RFI as far away from the inverter as possible. This includes radios and

TVs.

Mounting

•

UL Standard 1741 requires the inverter be mounted on a vertical surface (or wall). The

keyhole slots must not be used as the only method of mounting. The purpose of the wall

mounting requirement is to orient the inverter so that its bottom cover, which has no holes,

will not allow burning material to be ejected in the event of an internal fire. Use 0.25 inch

diameter bolts for mounting. The mounting surface must be capable of supporting twice the

weight of the inverter to comply with UL 1741.

Ventilation

•

Install the inverter in a well ventilated area/enclosure for proper operation. The inverter’s

thermal shutdown point will be reached sooner than normal in a poorly ventilated

environment, resulting in reduced peak power output and surge capability, as well as shorter

inverter life.

•

The inverter contains an internal fan. Ensure the air vents and intakes are not obstructed in

any way. Provide a minimum clearance of 1-1/2 inches around the top and sides of the

inverter for ventilation.

Summary of Contents for DR - REV A

Page 1: ...Installation Operator s Manual DR Series Inverter Charger...

Page 2: ......

Page 3: ...5 Pre installation 6 Location 6 Mounting 6 Ventilation 6 Tools Required 7 Hardware Materials Required 7 Wiring 7 AC Connections 7 DC Connections 7 Grounding 7 AC Grounding 7 DC Grounding 7 Batteries 8...

Page 4: ...C Generator Hookup non utility applications only 31 Basic 120 VAC Utility Generator Hookup 32 Generator Connections to manual bypass switch 32 Utility Connections to manual bypass switch 32 Inverter C...

Page 5: ...55 Flooded Lead Acid FLA 55 RV and Marine 55 Golf Cart 55 Industrial electric forklift 55 Sealed Batteries 55 Gel Cell 55 Absorbed Glass Mat 55 NiCad and NiFe Batteries 56 Battery Bank Sizing 57 Estim...

Page 6: ...methods of installation operation use and maintenance of the unit are beyond the control of Xantrex Technology Inc the company does not assume responsibility and expressly disclaims liability for loss...

Page 7: ...portant Follow instructions closely NOTE Cette d claration est importante Suivre les instructions de pr s All electrical work must be done in accordance with local national and or international electr...

Page 8: ...dup of explosive gasses If the batteries are installed inside an enclosure vent its highest point to the outdoors When installing batteries allow at least 1 inch of air space between batteries to prom...

Page 9: ...rator power while charging the batteries When utility power fails the battery backup system keeps your appliances powered until utility power is restored Internal protection circuits prevent over disc...

Page 10: ...the unit should require warranty service Save the original shipping carton and packing materials If the inverter ever needs to be returned for service it should be shipped in the original carton This...

Page 11: ...he model number describes the type of inverter the output specifications the required battery voltage and the output voltage and frequency DR indicates the type of inverter charger DR Series 15 the fi...

Page 12: ...erter charger has been tested to nationally recognized safety standards UL for the US and CSA for Canada and have been found to be free from reasonably foreseeable risk of fire electric shock and rela...

Page 13: ...le time The built in fully automatic AC transfer relay automatically transfers power from the utility to the inverter and handles a full 60 amps of current at 120 VAC 30 amps for pass through plus 30...

Page 14: ...y connecting the battery cables or switching a relay could ignite this mixture Mounting the inverter in a ventilated enclosure with sealed batteries is acceptable NOTE Inverters can generate RFI Radio...

Page 15: ...oth AC and DC cables in conduit Refer to the Figure 25 page 29 for an example of AC wiring to the sub panel for 120 VAC circuits AC Connections Use 6 AWG THHN wire for all AC wiring DC Connections Bat...

Page 16: ...re Install an intake vent at the bottom of the enclosure to promote air circulation These vents exhaust explosive hydrogen gases and must not be overlooked when designing an enclosure The enclosure sh...

Page 17: ...TERY ENCLOSURE if used 975 0012 001 DC DISCONNECT VENT outlet VENT inlet MAIN PANEL SUB PANEL INVERTER CHARGER AC CONDUIT AC CONDUIT TO SUB PANEL DC CONDUIT if used CONDUIT BOX if used BATTERIES BATTE...

Page 18: ...n accidental short Size the breaker in accordance with the battery cables Switch this breaker OFF whenever servicing the batteries Wire Routing Determine all wire routes both to and from the inverter...

Page 19: ...ON HAND TO ASSIST IN LIFTING THE INVERTER INTO POSITION WHILE IT IS BEING SECURED Procedure Locate the studs and mark their location on the wall Measure the desired height from the floor for the inve...

Page 20: ...mounted directly to the plywood using 1 4 inch diameter lag bolts and washers The plywood must span three studs for adequate support 20 175 inches 51 244 cm 1 90 inches 4 83 cm 7 00 inches 17 8 cm 7...

Page 21: ...at the inverter s peak power rating exceeding one hour larger cables and disconnects MUST be used see Tables 1 and 2 NOTE If the system includes a large battery bank or large DC source such as a micr...

Page 22: ...for long cable runs Also the plastic red and black covers on the DC inverter inputs are not designed to accommodate dual cables If dual cables are used the optional conduit box DRCB must be used Some...

Page 23: ...he battery cables to the DR Series inverter charger terminals 2 0 Copper Compression Lug 2 0 Aluminum Mechanical Lug Do not place anything between battery cable lug and terminal surface Assemble exact...

Page 24: ...le starting battery and deep discharge applications Only the deep discharge types are recommended for inverter applications Choose the batteries best suited for the inverter installation and cost Use...

Page 25: ...g Batteries in Series Wiring the batteries in a series configuration increases the voltage of the battery string 6 volt batteries can be combined to form 12 V 24 V or 48 V battery banks In the same wa...

Page 26: ...Batteries in Series Parallel Wiring the batteries in a series parallel configuration increases the current and voltage of the battery bank Series parallel wiring is more complicated and care should b...

Page 27: ...fused device Connect the NEGATIVE terminal of the second battery string to the inverter s NEGATIVE DC terminal NOTE Connecting the positive and negative wires to the inverter from different strings e...

Page 28: ...re these dashed lines 6 V 6 V 3597 F00 D32 6 V 6 V 6 V 6 V 6 V 6 V 6 V 6 V 6 V 6 V 6 V 6 V 6 V 6 V Cross tie cable not required Cross tie cable not required Cross tie cable not required Cross tie cabl...

Page 29: ...Cross tie cable not required Cross tie cable not required Cross tie cable not required Fuse Block Disconnect 12 V 12 V 3597 F00 D34 12 V 12 V Cross tie cable not required Cross tie cable not required...

Page 30: ...recommendations Ensure the correct polarity of the cables with a DC voltmeter DVM Observing battery polarity connect the positive battery cable from the over current device to the inverter s positive...

Page 31: ...ng to NEC 250 95 see table below for a portion of the NEC code Size of Over current Device Protecting the Conductor Minimum Size of Copper Ground Wire 30 or 60 amp 10 AWG 100 amp 8 AWG 200 amp 6 AWG 3...

Page 32: ...ng overcharging in warm temperatures and undercharging in cold temperatures Installing the sensor Run the battery temperature sensor wire in the DC conduit if used and route the RJ11 connector end to...

Page 33: ...stacked configuration install two 60 amp circuit breakers for 240 VAC service one in each leg of the circuit for L1 and L2 Input to the Inverter CAUTION THE INVERTER S AC OUTPUT MUST NEVER BE WIRED TO...

Page 34: ...8 or 6 AWG 10 AWG 12 AWG 16 AWG DR2412 6 AWG 10 AWG 10 AWG 14 AWG DR1524 8 or 6 AWG 10 AWG 12 AWG 16 AWG DR2424 8 AWG 10 AWG 10 AWG 14 AWG DR3624 6 AWG Not Available 8 AWG Not Available 975 0012 007...

Page 35: ...stall a 60 amp circuit breaker in the utility service panel This will serve as both an AC disconnect and over current protection Feed the HOT NEUTRAL and GROUND wires via conduit from the inverter to...

Page 36: ...to the inverter s AC GROUND chassis terminal Connect the other end of this wire to the GROUND bus in the sub panel Connect the NEUTRAL white wire to the inverter s NEUTRAL OUTPUT terminal Connect the...

Page 37: ...POWER TO LOAD 120 VAC 120 VAC 240 VAC GROUND CAUTION NEUTRAL BONDED TO GROUND IN MAIN PANEL ONLY NEUTRAL 3597 W00 C06 Figure 25 Single Inverter 120 VAC Wiring Diagram AC Wiring continued AC Input Wir...

Page 38: ...energy to the charger The charger s rated output is based on a utility voltage of 120 VACrms which has a peak voltage of 169 VACp 230 VACrms has a peak voltage of 325 VACp Low power generators may no...

Page 39: ...he output of the generator only if used in non utility installations or in the MAIN SERVICE PANEL not both Drive a ground rod 6 8 feet into the ground and connect the generator s ground to the ground...

Page 40: ...AIN UTILITY PANEL and the GROUND terminal in the manual bypass switch Connect a white wire between the NEUTRAL bus in the MAIN UTILITY PANEL and the NEUTRAL bus in the manual bypass switch Connect a b...

Page 41: ...HOT NEUTRAL Isolated Neutral Bus Isolated Neutral Bus Isolated Neutral Bus Bonded Neutral Ground Bus House Ground HOT NEUTRAL HOT NEUTRAL GROUND UTILITY HOT CONTACT GENERATOR HOT CONTACT 975 0012 008...

Page 42: ...C operation Both units can charge the batteries or provide battery backup power during a utility outage The following illustrations provide a general overview of AC and DC wiring configurations and ou...

Page 43: ...ct 120 VAC 60 Hz models only Figure 30 Stacking Port and Battery Wiring with Two Disconnects 120 VAC 60 Hz models only DC Disconnect Negative Tie Series Stacking Cable DRI 975 0012 009 Positive Tie In...

Page 44: ...rs are designed to operate with either an RC4 or RC8 remote control units Both remotes incorporate a membrane switch with a single red LED display combination to start and stop the inverter as well as...

Page 45: ...e batteries receive a full charge and lowers it during warm temperatures reducing battery gassing and providing overcharge protection Refer to the Installation section for the BTS location on the batt...

Page 46: ...recommendation for Float and Bulk settings 3 Not Specified Provides an additional set of Bulk and Float voltages Switch Position Description 12 Volt Models 24 Volt Models Equalize Float Voltage Bulk E...

Page 47: ...GEL Cell 2 Recommended for gel cell batteries that specify high float voltages Check with the battery s manufacturer 5 GEL Cell 1 Typical gel cell setting 6 PbCa Lead Calcium Use this setting for sea...

Page 48: ...erter is in the SEARCH MODE Slowly turn the potentiometer CCW toward MIN when the proper setting is found the lamp and INVERTER MODE LED will light steady Turn the lamp OFF for a moment the inverter s...

Page 49: ...batteries Divide the amp hour capacity by 5 250 5 50 Set the potentiometer to approximately 71 50 amps Use the table below to find the approximate setting of the Battery Charge Rate potentiometer The...

Page 50: ...battery cutoff to protect the batteries from over discharge damage The inverter circuitry calculates the lowest safe DC voltage leaving approximately 20 battery capacity based on the position the Bat...

Page 51: ...ect the operation of the AC Transfer Voltage ODP is either ON or OFF depending upon the position of the potentiometer NOTE There are 6 settings available for the AC Transfer Voltage for both ODP OFF a...

Page 52: ...between these values will allow the incoming source voltage to drop to this level and still operate the connected appliances load If the appliances do not operate properly at the lower AC utility pass...

Page 53: ...ble to the actual capacity of the battery bank for optimum charging If the system s battery bank is larger than 1000 amp hours set the potentiometer for 1K NOTE Most battery manufacturers list the amp...

Page 54: ...Overload LED Red Green error condition The Over Temp Overload LED is a dual color dual function indicator When the inverter s temperature is too high for safe operation the LED lights red to indicate...

Page 55: ...re detected LOW HIGH BATTERY OVER TEMPERATURE or a quick duration SHORTED OUTPUT or OVER CURRENT The inverter shuts OFF and requires a MANUAL restart if the following conditions are detected a prolong...

Page 56: ...cuit breaker protects the charger circuit The breakers are rated for the maximum charge rate and pass through current allowed according to the rating of the internal relay Table 11 Battery Charger Cir...

Page 57: ...eck the output voltage of the inverter This voltage can be checked at either the AC terminal block or in the sub panel between the HOT and NEUTRAL lines The voltage should be 120 VAC 230 VAC for E mod...

Page 58: ...y decreases When the current equals the programmed return amps value battery bank capacity 40 set with the BATTERY BANK CAPACITY potentiometer the charger switches to the third stage float NOTE If the...

Page 59: ...Charge Remove all DC loads connected to the batteries Remove all battery vent caps Check the battery water level it should be just over the top of the plates do not overfill Use only distilled water f...

Page 60: ...6 30 0 3 Not Specified 13 6 14 3 27 2 28 6 4 Gel Cell 2 13 7 14 4 27 4 28 8 5 Gel Cell 1 13 5 14 1 27 0 28 2 6 PbCa Lead Acid 13 2 14 3 26 4 28 6 7 Deep Cycle Lead Acid 1 Default Setting 13 4 14 6 26...

Page 61: ...C DVM and measure the input voltatge Remove excessive loads Let inverter cool down before restarting Check inverter s cooling fan Check for obstructions in air vents Clean if necessary OVERLOAD LED gr...

Page 62: ...side of the unit Check AC PASS THRU circuit breaker on the side of the inverter Check for open AC output breakers or fuses and AC wiring connections Charger is inoperative or supplying a low charge ra...

Page 63: ...r in small systems Often referred to as Group 24 or Group 27 batteries Designed for limited cycling Do not last as long as the other true deep cycle batteries Typically rated at 12 volts 80 to 100 amp...

Page 64: ...d for a 12 24 and 48 volt system i e 10 cells for a 12 volt system 20 cells for a 24 volt system and 40 cells for a 48 volt system Alkaline batteries require a higher charge voltage to fully recharge...

Page 65: ...size the batteries at twice this amount to ensure the batteries are not regularly over discharged To compute the amp hour requirements the amp hour ratings of each appliance powered by the inverter mu...

Page 66: ...Divide the number entered into each row of the Step 4 column by 7 to obtain the AVERAGE DAILY WATT HOURS REQUIRED figure Enter these figures in the Step 5 column Step 6 Add all the figures entered int...

Page 67: ...Step 10 Divide the SAFE BATTERY SIZE WATT HOURS Step 9 figure by the DC system voltage i e 12 24 or 48 volts Enter this number in the SAFE BATTERY SIZE AMP HOURS Step 10 column Use this figure to dete...

Page 68: ...ance Watts Fluorescent type light 10 Blender 400 Computer 200 300 Toaster 1000 Microwave compact 600 800 Hot Plate 1800 Microwave full size 1500 Washer Dryer 375 1000 Stereo or VCR 50 3 8 Drill 500 Co...

Page 69: ...them in a ready state Temperature Compensation For optimal battery charging the Bulk and Float charge rate should be adjusted according to the temperature of the battery This can be accomplished auto...

Page 70: ...manual Clean Battery Cables and Posts WARNING BEFORE ATTEMPTING TO CLEAN THE BATTERY POSTS TURN OFF THE DC CIRCUIT BREAKER USE ONLY INSULATED TOOLS AND REMOVE ALL JEWELRY Battery posts must be clean t...

Page 71: ...ess than a 0 2 volt difference between each battery To determine the individual cell voltage divide the voltage by the number of cells in the battery i e 12 6 V divided by 6 cells 2 1 volts per cell I...

Page 72: ...nexpensive tape recorders are likely to experience noise as well When using sensitive electronic devices avoid starting large loads Clocks The inverter s crystal controlled oscillator keeps the freque...

Page 73: ...f power is added Microwave Ovens Microwave ovens are sensitive to peak output voltages The higher the voltage the faster they cook Since the inverter s peak output voltage is dependent upon battery vo...

Page 74: ...using the one neutral wire to now carry the in phase currents for both circuits Since the current is in phase the two circuits add instead of subtract potentially doubling the current flow in the neut...

Page 75: ...RFORMED BY QUALIFIED PERSONS OR ELECTRICIANS Multiwire branch circuits can be identified by removing the cover on the load center and inspecting the wiring Conventional 120 VAC circuits are identified...

Page 76: ...protection and can power 240 VAC loads Add a T240 Autotransformer to the output of the inverter to restore the split phase configuration This is the least expensive and easiest method to correct for m...

Page 77: ...products must be returned to Xantrex or its Authorized Service Center in the original packaging or equivalent The cost of transportation and insurance on items returned for service is the responsibili...

Page 78: ...nowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to The Company that a the risks of injury or damage have been minimized b the customer ass...

Page 79: ...Include a telephone number where you can be reached during business hours and a complete return shipping address P O Box numbers are not acceptable Name _______________________________________________...

Page 80: ...18 kg 45 lb 21 kg N A Common Specifications Voltage Regulation Max 5 Voltage Regulation Typ 2 5 Waveform modified sine wave Power Factor allowed 0 to 1 Frequency Regulation 60 Hz 0 04 E models 50 Hz 0...

Page 81: ......

Page 82: ......

Page 83: ......

Page 84: ...Xantrex Technology Inc 5916 195th Northeast Arlington WA 98223 U S A t 360 435 8826 f 360 435 3945 www xantrex com Printed in U S A 2000 Xantrex Technology Inc P N 975 0012 01 01 Rev A 12 00...

Reviews: