Make sure power supply is protected up to standard depending on application. The power of the 
motor has to be within the control panel's limits of use. 

Eliminate whatever metal and/or plastic impurity which could happen to fall inside the box (screws, 
washers, dust…).

Install the control panel in an environment appropriate to its IP65 degree of protection. To fix the 
enclosure, use the brackets for the boxes 03-04 and the special predispositions for the remaining 
boxes. In order to fix the box, use the appropriate holes which are present or suggested on the 
bottom. Pay particular attention to not touching or damaging any components while fixing the box.

When connecting electric cables, follow the wiring diagrams.

If necessary substitute the various components only with those having the same characteristics and 
components as the originals.

It  is  the  installer'  s  duty  to  verify  the  device  after

 

the  installation  although  it  has  already 

undergone regular testing by the manufacturer.

When fixing the cables in the terminal board use tools of correct size to avoid damaging the metal 
feed clamps and their sockets.

The manufacturer is released from all responsibilities for accidents to things or people, which 
derive from misuse of the devices by unauthorized personnel or from lack of maintenance 
and repair.

Before  acting  upon  anything  inside,  disconnect  power  supply.  Regulation  procedures  must  be 
carried out by qualified personnel. In case protections intervene verify the cause of the problem 
before resetting.

1.

 GENERAL INSTRUCTIONS FOR INSTALLING

2. 

WARNINGS

Risk of electric shocks if not complied with the requirements.

ELECTRIC SHOCKS

DANGER

Risk of personal injury and property if not complied with the requirements.

 

WARNING

Before installing and using the product read this book in all its parts. Installation and maintenance must be 
performed by qualified personnel in accordance with current regulations.
The manufacturer will not be held responsible for any damage caused by improper or prohibited use of this 
control panel and is not responsible for any damages caused by an incorrect installation or maintenance of the 
plant. The use of non-original spare parts, tempering or improper use, make the product warranty null.

WARNING

Be sure that the power of the motor is within the control panel range.Install the control panel in an environment 
appropriate to its IP

 65 degree of protection.

To operate inside the control panel use tools of correct size to avoid damaging the sockets.

 

 

 

 

In order to fix the box use the appropriate holes present on the bottom, don't damage internal components and 
eliminate any working debris inside the box.

Before any intervention ensure that the control panel is disconnected from the electricity supply.
Do not attempt operations when the control panel is open.The control panel must be connected to an efficient 
earthing system.

In the case of protections eliminate the cause of the malfunction before the restoration.

DANGER

 

ENGLISH

Summary of Contents for 648.612

Page 1: ...onatore blocca porta Direct starting electronic control panel 1 motor for clean water and sewage with general disconnecting switch with door lock MADE IN ITALY rev 3 20 03 2020 ITA ENG MANUALE DI ISTRUZIONE E INSTALLAZIONE INSTRUCTION AND INSTALLATION MANUAL MULTI 1 648 612 649 615 ...

Page 2: ...2 INDICE ...

Page 3: ...sinistri a cose o persone dovuti a manomissioni delle apparecchiature da parte di personale non autorizzato o da carenze nella manutenzione e riparazione 2 AVVERTENZE SCOSSE ELETTRICHE Rischio di scosse elettriche se non si osserva quanto prescritto Rischio di lesioni personali e materiali se non si osserva quanto prescritto PERICOLO AVVERTENZA Prima di installare e utilizzare questo prodotto legg...

Page 4: ...10 25 50 100 35 65 80 1 2 G MIN COM MIN COM MAX G MAX1 G MAX2 G ALAR PR STA PR EME KLIX1 COM N C N O COM ALARM MOTORE M 1 U V AVV MOTORE CAPACITOR SIREN 12V FLASHING LAMP 12V 3 4 5 6 7 8 9 10 12 13 14 PROBE DELAY 1 40 120 240 80 160 200 7 8 GALLEGGIANTE ALLARME 12 13 14 USCITA ALLARME CONTATTO PURO MAX 5A 1 2 SONDE DI LIVELLO O GALLEGGIANTE MINIMO LEGENDA 9 10 KLIXON MOTORE 1 3 4 SONDE DI LIVELLO ...

Page 5: ...LARM SIREN 12V FLASHING LAMP 12V 3 4 5 6 7 8 9 10 12 13 14 R MOT1 S R S T SUPPLY L1 L2 L3 U V W M 3 MOTORE LINEA DI ALIMENTAZIONE 400 Vac 50 60 Hz CURRENT MOTOR 1 2 5 11 18 8 14 16 PROBE SENSITIVITY 10 25 50 100 35 65 80 PROBE DELAY 1 40 120 240 80 160 200 3 4 SONDE DI LIVELLO O GALLEGGIANTE MAX1 LEGENDA 5 6 GALLEGGIANTE MAX2 O PRESSOSTATO START 12 13 14 USCITA ALLARME CONTATTO PURO MAX 5A 1 2 SON...

Page 6: ...ULITE SONDE 5 4 ESEMPI APPLICATIVI Di seguito vengono illustrati alcuni esempi pratici delle applicazioni che è possibile realizzare con il quadro MULTI 1 LEGENDA COMPONENTI 6 ACQUE PULITE RILANCIO ACQUE PULITE SVUOTAMENTO ...

Page 7: ...er CURRENT MOTOR 1 è possibile regolare la corrente massima di sovraccarico del motore Per effettuare una buona calibrazione è raccomandabile ruotare il trimmer fino al valore di fondo scala e successivamente quando si avvia il motore ruotarlo in senso antiorario fino ad individuare la corrente di assorbimento del motore il led rosso PROTECTION si accende e poi aumentare la regolazione di un 20 VE...

Page 8: ...ATA FUNZIONAMENTO STOP IN QUESTA CONDIZIONE IL QUADRO NON AVVIA IL MOTORE SERVE A TACITARE L USCITA SIRENE IN PRESENZA DI QUALSIASI ALLARME N B TUTTI GLI ALLARMI VENGONO RIPRISTINATI AUTOMATICAMENTE AD ECCEZIONE DELLA SOVRACCORRENTE MOTORE CHE SI RESETTA PREMENDO PER 2s IL PULSANTE INDICA CHE IL MOTORE È IN FUNZIONE INDICA CHE IL MOTORE È SPENTO INDICA UN ALLARME DI SOVRACCARICO DEL MOTORE CHE NE ...

Page 9: ...IL MOTORE ATTESA RIEMPIMENTO ABILITA IL MOTORE GALLEGGIANTE ALLARME ON VIENE ABILITATO IL MOTORE E LE USCITE ALLARME LAMPEGGIANTE SIRENA E CONTATTO PULITO GALLEGGIANTE ALLARME ON VENGONO ABILITATE LE USCITE ALLARME LAMPEGGIANTE SIRENA E CONTATTO PULITO N B IL MOTORE SI AVVIA SOLO SE SI TROVA NEL FUNZIONAMENTO AUTOMATICO E SI ARRESTA SOLO QUANDO IL GALLEGGIANTE MAX 2 È OFF OPPURE IL GALLEGGIANTE MI...

Page 10: ...erale su 0 Cavetto flat all interno del quadro scollegato Motore bloccato o danneggiato Modo ACQUE PULITE Led FUNCTION spento con vasca piena Modo ACQUE REFLUE Led FUNCTION spento con livello acqua alto Verificare la funzionalità dei galleggianti e del cavo e se necessario sostituirli Possibile guasto dei galleggianti o cavo di collegamento interrotto Verificare la funzionalità dei galleggianti e ...

Page 11: ... ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ _______...

Page 12: ...12 INDEX ...

Page 13: ...ures must be carried out by qualified personnel In case protections intervene verify the cause of the problem before resetting 1 GENERAL INSTRUCTIONS FOR INSTALLING 2 WARNINGS Risk of electric shocks if not complied with the requirements ELECTRIC SHOCKS DANGER Risk of personal injury and property if not complied with the requirements WARNING Before installing and using the product read this book i...

Page 14: ... MAX1 G MAX2 G ALAR PR STA PR EME KLIX1 COM N C N O COM ALARM MOTOR M 1 U V AVV MOTORE SIREN 12V FLASHING LAMP 12V 3 4 5 6 7 8 9 10 12 13 14 PROBE DELAY 1 40 120 240 80 160 200 LEGENDA 5 6 MAX2 FLOAT SWITCH OR START PRESSURE SWITCH 1 2 LEVEL PROBES OR MINIMUM FLOAT SWITCH 12 13 14 PURE CONTACT ALARM OUTPUT MAX 5A 9 10 MOTOR 1 KLIXON 3 4 LEVEL PROBES OR MAX1 FLOAT SWITCH 7 8 ALARM FLOAT SWITCH COMM...

Page 15: ...2 13 14 R MOT1 S R S T SUPPLY L1 L2 L3 U V W M 3 MOTOR POWER SUPPLY 400 Vac 50 60 Hz CURRENT MOTOR 1 2 5 11 18 8 14 16 PROBE SENSITIVITY 10 25 50 100 35 65 80 PROBE DELAY 1 40 120 240 80 160 200 1 2 LEVEL PROBES OR MINIMUM FLOAT SWITCH 7 8 ALARM FLOAT SWITCH 12 13 14 PURE CONTACT ALARM OUTPUT MAX 5A LEGENDA 3 4 LEVEL PROBES OR MAX1 FLOAT SWITCH 5 6 MAX2 FLOAT SWITCH OR START PRESSURE SWITCH 9 10 M...

Page 16: ... EXAMPLES Below are some practical examples of applications that can be implemented with the MULTI 1 control panel COMPONENTS KEY Float switch for clean water Float switch for sewage Level probe CLEAN WATER PROBES CLEAN WATER LIFTING SEWAGE ...

Page 17: ...PHASE VERSION 2 5 11 18 8 14 16 CURRENT MOTOR 1 Through this trimmer it is possible to set the sensitivity of the conductivity between the 3 level probes The adjustment range is from 0 to 100 Kohm This trimmer is only adjusted when it is required to operate with 2 time probes COMMON and MINIMUM excluding the maximum probe to activate it just set the SWITCH F3 on the board to ON The adjustable time...

Page 18: ... PANEL WILL WORK ACCORDING TO THE SET APPLICATION STOP OPERATION IN THIS CONDITION THE CONTROL PANEL DOES NOT START THE MOTORS IT SERVES TO SILENCE THE SIREN OUTPUT IN PRESENCE OF ANY ALARM N B ALL ALARMS ARE AUTOMATICALLY RESET WITH THE EXCEPTION OF THE MOTOR OVERCURRENT WHICH RESETS BY PRESSING THE BUTTON FOR 2s INDICATES THAT THE MOTOR IS RUNNING INDICATES THAT THE MOTOR IS OFF IT INDICATES A M...

Page 19: ...SIREN AND PURE CONTACT NO WATER UNCOVERED MINIMUM LEVEL THE MOTOR IS DISABLED NO WATER UNCOVERED MINIMUM LEVEL THE MOTOR IS ENABLED WAITING FILLING THE MOTOR IS DISABLED WAITING FILLING THE MOTOR IS ENABLED FLOAT SWITCH ALARM ON THE MOTOR AND THE ALARM OUTPUTS ARE ENABLED FLASHING LAMP SIREN AND PURE CONTACT ALARM FLOAT SWITCH ON ALARM OUTPUTS ARE ENABLED FLASHING LAMP SIREN AND PURE CONTACT N B T...

Page 20: ... Maximum current alarm Motor blocked or damaged SEWAGE WATER mode Led FUNCTION OFF high level of the water Possible failure of the float switches or connection cable interrupted Ceck the functionality of the float switches and of the cable and replace if necessary CLEAN WATER mode FUNCTION led off with full tank Possible failure of the float switches or connection cable interrupted Ceck the functi...

Page 21: ...adeguato smaltimento di questo prodotto Il riciclaggio dei materiali aiuterà a conservare le risorse naturali Per informazioni più dettagliate riguardo il riciclaggio di questo prodotto contattate per cortesia il Vs ufficio locale il Vs servizio di smaltimento rifiuti domestici o il negozio dove avete acquistato questo prodotto punti di raccolta locali centri di raccolta rifiuti centri locali di r...

Page 22: ... ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ _______...

Page 23: ... ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ _______...

Page 24: ...ELETTROMEK Via C Colombo 186 98066 Patti ME ITALY Tel 39 0 941 361336 Fax 39 0 941 372806 www xpowerwaterpumps com info xpowerwaterpumps com e mail ...

Reviews: