Profibus DP – CBF-B1/CBFF-B1 Burner Control Box 

 

vor00161

 

 

Tab.4: Status byte EB2 – Signal Referencing ( CBF(F) 

 Master):

 

Byte       

(decimal) 

Display 

static= S   
flashing = B 

Text 

CBF  CBFF 

00 

Ready  

A1 

Waiting time 

A2 

Safety time during start-up 

A3 

Flame stabilizing period 

A4 

Flame mode 

A5 

FLOX mode 

 

P0 

Air purge 

C0 

Cooling 

 

 

Reserve 

 

 

 

 

Reserve 

 

 

10 

00

 

P

roof 

o

C

losure (USA) 

11 

A1 

False flame signal 

12 

A2 

Start up without flame signal 

13 

A3 

Loss of signal during stabilizing period 

14 

A4 

Flame failure 

15 

d0 

Delta-p switch failure 

 

16 

d2 

Start up without air pressure 

 

17 

d3 

No air pressure during stabilizing time 

 

18 

d4 

No air pressure in Flame mode 

 

19 

dP 

No air pressure during purge 

 

20 

10 

Remote reset limit exceeded (5x/15 min)**

 

21 

d5 

No air pressure in FLOX mode 

 

22 

FF 

FLOX-Flame switching fault 

 

51 

51 

Defective fuse f1 or safety interlock 

52 

52 

Permanent remote reset signal 

53 

53 

Cycle time too short 

54 

54 

Manual operation: Flox locked out 

 

**) „10“ will flash in display if more than 5 remote resets were attempted via the bus within 15 minutes.  Further remote 
resets are not possible, burner must be reset manually at the burner control box. ( Limitation is implemented to prevent 
continuous resetting in case of a bus failure)  Local reset will re-enable remote reset. 
 

  

 

 
During operation the 7-segment display will show the current program status.  Flame signal strength and other parameters 
will be displayed by repeatedly pressing the Reset/Info button.  
Should a fault occur, the CBF-/CBFF will terminate operation and display a flashing fault code.  Meaning of fault code can be 
determined from fault schedule attached to front of control box (see Fig. 2)  Fault schedule is available in several languages 
and can be exchanged easily.  CBF-/CBFF DP will display „- -„ signalising stand-by mode if the box is turned off.  The bus 
system will remain functional to enable communication to other devices.  Control outputs of CBF-B1/CBFF-B1 (ignition, sole-
noid valves) are electrically separated from the power supply. 
 

Fig. 2 : Fault Schedule (English): 

Permanent 

Display 

Blinking 

Start position 

00 

 

Waiting time 

A1 

Flame signal at start 

Safety time on start-up 

A2 

Flame failure during start-up 

Flame proving period 

A3 

Flame failure during proving period 

Normal operation flame 

A4 

Flame failure during operation 

Normal operation FLOX 

A5 

 

 

dx 

Failure pressure switch  

 

FF 

Failure FLOX-flame switching control 

Purge 

P0 

 

Cooling 

C0 

 

 

51 

Fuse F1 fault or safety chain interlock 

 

52 

Permanent remote reset 

 

53 

Cycle time too short 

 

54 

Manual operation: FLOX mode locked 

 

Pb 

Bus fault 

Power switch off 

- - 

 

dimensions: 83x44,25mm 

 

Status Information and Parameters:

 

Summary of Contents for CBF-B1

Page 1: ...th integrated flame relay and cus tomizable Software in a cast aluminum housing 200x200x110mm Protection rating IP54 Connection terminal for power supply 230V 50 60 Hz op tional 115V AC Works with grounded or ground free grid Release signal input 230V AC optional 115V AC via proc ess safety interlock load for ignition transformer and con nected solenoid valves are present Ignition transformer opti...

Page 2: ...signal strength In order to reduce electromagnetic interference it is required to use shielded wire e g Lapp Unitronic order 2170 220T or Siemens order 6XV1830 OEH10 Shield must be diligently fastened to ground terminals of connected devices and po tential equalization between multiple devices may be required To further reduce risk of interference keep bus wires separate from other wiring Data wir...

Page 3: ...s with red and green wires it has been established that green wire be connected to A and red wire be connected to B Incoming wires connect to 1A 1B outgoing wires connect to 2A 2B Wire shield must be sufficiently connected to ground terminal refer to applicable guides of the manufacturer of the Profibus con nectors Fig 3 Control box dimensions CBF F B1 Supplier ident 0x05DB ASIC Type SPC3 SYNC FRE...

Page 4: ...ctor switches within the Profibus control box Picture 2 Picture 2 Profibus address selectors Following tables showing data transmission between master and slave CBF B1 CBFF B1 Tab 2 Output byte Master CBF F Bit Output byte AB0 0 Remote reset 1 Start heat demand 2 Cooling 3 Air purge 4 5 6 7 Tab 3 Input bytes CBF F Master Bit EB0 EB1 EB2 EB3 0 Operation burner Manual mode Status byte 1 Fault burner...

Page 5: ... box Limitation is implemented to prevent continuous resetting in case of a bus failure Local reset will re enable remote reset During operation the 7 segment display will show the current program status Flame signal strength and other parameters will be displayed by repeatedly pressing the Reset Info button Should a fault occur the CBF CBFF will terminate operation and display a flashing fault co...

Page 6: ...s valve and after the safety period the switch must have left the shut position proof of closure POC acc NFPA 86 3 Air purge after reset The larger parameter 13 20 is relevant if burner starts with the heat demand signal In normal mode the time for air purge from field 20 is active The burner will start up when command heat is set in mode air purge xx sec and afterwards it will heat for the minimu...

Page 7: ...within 1 sec otherwise a fault signal FF blinking will be caused The supplied connector for Profibus bus cables included has to be installed according to electrical drawing p 3 Profibus version reduces wiring as only power supply and safety interlocks 230V must be run to the box in addition to the bus ca ble Control cables for the burner components are pre installed and only require hook up on sit...

Page 8: ... load current per input approx 3 mA Max switching cycles 1 000 000 Ambient temperature 20 to 60 C dew formation not permitted Protection rating IP 54 according EC 529 Weight approx 5 kg Profibus connection via Variosub Profibus 9 pin connector Sub D female male counter connector avai lable as option Housing made of cast aluminum with removable flange plate max 2 cable grips M20x1 5mm for power sup...

Page 9: ...ted for qualified personnel under continuous monitoring of faulting burner Gas and air adjustment must be according to values provided on test certificates In case of a fault burner control unit will close gas valves and display will flash a fault code After several unsuccessful reset attempts the combustion chamber must be purged with air to remove any combustible mixtures CBF control boxes can o...

Page 10: ...e fluctuations ex haust restricted or closed up distance recuperator to inner tube incorrect dis tance cross in radiant tube missing igni tion and supervision cables run in same conduit with other cables defective gas lance nozzle defective or plugged gas lance defective combustion chamber air flow correct UV probe defective quartz glass broken or covered with soot combustion chamber back pressure...

Page 11: ...Flame control signals short circuit may cause this Check respond time 1 sec check voltage after fault repair system must be reset Attention FLOX Flame control signals are safety relevant be very careful while repairing risk of explosion 51 flashing Faulty fuse F1 short circuit in valve or ignition circuit safety interlock in terrupted Check ignition transformer and solenoid valves exchange fuse 3 ...

Page 12: ... device error send to vendor for evaluation Power switch turned off Control functions not available when box is not turned on press 0 1 button to power box up Pb flashing Profibus data transmission disturbed CBF cannot communicate with bus master Bus wires broken interrupted bus wires switched in connectors A and B termi nals switched insufficient shielding in correct system termination activate t...