Fault finding and diagnosis
Greenstar Heatslave II External
ErP -
6 720 813 345 (2014/09)
43
8.4.3
Cause and fault codes
Cause
code
Fault
code
Description
Reset
type
Blocking Locking
Possible cause
210
E9
Max temperature thermostat activated
Reset
X
Flue gas or tank thermostat overheat. Reset the overheat
thermostat before resetting the appliance.
212
No
code
Safety or flow temperature rises too high
X
Air lock or reduced water content.
218
E5
Flow temperature too high
Reset
X
Primary sensor overheated.
219
E9
Safety temperature too high
Reset
X
The main heat exchanger has overheated.
Maximum temperature 105°C.
220
E9
Safety sensor short circuit
Reset
X
Maximum temperature sensor on the main heat exchanger has
failed.
221
E9
Safety sensor open circuit
Reset
X
Maximum temperature sensor on the main heat exchanger has
not been recognised.
222
E2
Flow sensor short circuit
Reset
X
Flow sensor shorted or damaged.
223
E2
Flow sensor open circuit
Reset
X
Flow sensor disconnected or damaged.
233
E2
HCM (Heat Control Module)
Reset
X
HCM Code plug missing or defective.
237
F0
Reset
X
Resistors between plug X4 pins 3 & 5 disconnected/>150k
or water in the burner control box
238
F0
Reset
X
Resistors between plug X4 pins 3 & 5 disconnected/>150k
or water in the burner control box
239
F0
Watchdog error
Reset
X
259
FO
AD reference error
Reset
X
263
F0
Appliance powered off with locking fault
present
Reset
X
Locking fault present when powered off.
271
D4
Temperature difference between flow
and safety sensors exceeds limit
X
The temperature of the primary flow and the safety sensor on
the main heat exchanger should be within 15°C of each other.
276
E9
Flow temperature exceeds 95°C
X
Primary overheat - boiler waits for temperature to reduce,
approximately 30 minutes.
277
E9
Safety temperature exceeds 95°C
X
Main heat exchanger safety sensor overheat - boiler waits for
temperature to reduce, approximately 30 minutes.
278
F0
Sensor test error
Reset
X
On power up, all safety sensors are checked. Check has failed.
279
F0
AD converter error
Reset
X
290
F0
AD converter reference error
Reset
X
332
E5
Primary flow has exceeded 105°C
Reset
X
Primary sensor overheated.
359
No
Code
DHW outlet or storage tank exceeds 90°C
X
Pump & burner are blocked until temperature drops to <89°C.
360
9A
Incorrect HCM for boiler variant
X
380
No
code
Inlet DCW temperature higher than DHW
outlet temperature
X
The output is blocked until the inlet temperature drops below
the output temperature.
808
A7
DHW sensor defective
Reset
X
809
A0
Thermal store sensor defective
Reset
X
855
9F
Burner lock out
Reset
X
Check the burner and fuel supply. Ensure the oil supply is free
of contaminants.
856
9F
5 burner lockouts repeated resets
Turn
boiler
off/on
X
After Five 855 burner lock outs in one demand period, cause
code 856 is displayed.
After boiler off/on cause code 263 will be displayed, press the
reset button to clear this fault. another 5 burner lock resets can
be attempted.
Table 15 Cause and fault codes
H code Displayed symbols
Cause
H03
Warning triangle and House symbol displayed on controller
Weather compensation activated but no weather sensor detected,
refer to section 5.11 on page 24 for more information.
H11
Warning triangle symbol displayed on controller
DCW in sensor defect, (appliance operation not affected)
Table 16 H fault codes