Commissioning
Greenstar i System
ErP
- 6 720 806 945 (2015/07)
45
▶ Using the DHW up/down arrow buttons to scroll through to the
Weather Sensor settings menu.
▶ Select menu item 5.W1 - WDM mode enable using the
button.
▶ Toggle this setting to OFF and select with
button.
▶ Press the
button twice to exit to the default appliance screen.
The Greenstar i built-in basic weather compensation needs to be
disabled as the intelligent weather compensation controller adjust the
compensation curve in parallel with the room thermostat to improve
room comfort.
Weather sensor settings (basic weather compensation control)
▶ Press the
and
buttons for approximately 5 seconds to
enter appliance menu function.
▶ Using the DHW up/down arrow buttons to scroll through to the
Weather Sensor settings menu.
▶ Press the
button to select the menu.
▶ Using the DHW up/down arrow buttons to scroll through the menu.
▶ Press the
button to select the menu item.
▶ Using the DHW up/down arrow buttons to scroll through the
adjustment options.
▶ Press the
button to confirm the adjustment.
▶ Press the
button to leave the info menu.
6.5.13 Boiler settings menu
The Boiler settings menu provides additional functionality of the
appliance, table 39 for details.
▶ Press the
and
buttons for approximately 5 seconds to
enter appliance menu function.
▶ Using the DHW up/down arrow buttons to scroll through to the Boiler
settings menu.
▶ Press the
button to select info menu.
▶ Using the DHW up/down arrow buttons to scroll through the menu.
▶ Press the
button to select the menu item.
▶ Using the DHW up/down arrow buttons to scroll through the
adjustment options.
▶ Press the
button to confirm the adjustment.
▶ Press the
button to leave the info menu.
Weather Sensor
settings menu list
Description
5.W1 - WDM mode
enable
▶ Enable the interaction with the
connected WDM (weather dependent
module).
– OFF = Disabled
– On = Enabled
5.W2 - WDM Max.
temperature
Set maximum supply temperature when
outdoor sensor temperature is equal to or
less than -10 °C.
▶ Range from 20 - 90 ( °C)
5.W3 - WDM Min.
temperature
Set minimum supply temperature when
outdoor sensor temperature is equal to or
greater than 20 °C.
▶ Range from 2 - 90 ( °C)
5.W5 - Frost prot.
enable
▶ Enable system frost protection function.
– OFF = Disabled
– On = Enabled
Table 38 Weather sensor settings menu
Boiler settings Menu list Description
2.1b - Max. DHW power
Only available when optional integral
diverter valve kit is fitted.
Maximum domestic hot water output (kW).
2. 1C - Pump head select ▶ Selectable values for pump head.
– 0 = Variable speed
– 1 = Constant pressure low
– 2 = Constant pressure low/middle
– 3 = Constant pressure middle/high
– 4 = Constant pressure high
2.1E - Pump switch mode
setting
▶ Selectable values for pump head.
– 4 = Pump energy save on
– 5 = Depends on heat request
2.1H - Min. pump speed
Minimum pump speed at minimum burner
load.
▶ Range from min - 100%
2.1J - Max. pump speed
Maximum pump speed at maximum burner
load.
▶ Range from min - 100%
2.2C - Air purge mode
Only available when optional integral
diverter valve kit is fitted.
▶ Selectable values air purge mode.
– OFF = Air purge mode off
– AUt = Air purge mode automatic
– On = Air purge mode on
2.3b - Anti fast cycle time Anti cycle function (starts from burner
ignition).
▶ Range from 0 - 60 (mins)
2.3C - Anti fast cycle flow
temperature
Anti cycle temperature hysteresis
(temperature differential).
▶ Range from -30 - 0 (k)
2.5F - Service reminder
time
Set the reminder for service reminder.
Refer to section 6.5.10, page 44.
▶ Range from 0 - 72 (months)
– 0 = Service reminder switched off
– 1 - 72 = Number of months till
reminder
2.7A - System LED select ▶ Operational and fault indicator (blue).
– OFF = LED only active for errors
– ON = LED active for flame activity
and errors (default)
2.9L - Thermal
disinfection enable
Enables thermal disinfection protection for
solar cylinder (available when optional
integral diverter valve kit is fitted).
– OFF = The program is not running
– ON = The program is running
Table 39 Boiler settings menu