INSTALLATION & SERVICING INSTRUCTIONS
CONDENSATE, GAS & WATER
CONNECTIONS
29
CONDENSATE, GAS & WATER CONNECTIONS
8 716 115 219b (09.2008)
H
J
K
Max. 4500mm
H
Min. 200mm
G
E
D
C
B
A
F
M
F
H
L
CONDENSATE CONNECTION:
The condensate pump (G) fills up and
periodically discharges through the flexible
condensate pipe (H) between 200mm to
4500mm from floor level. After this point the
condensate flows, due to gravity, down the
21.5mm plastic pipe to the outlet.
Fit the bayonet connector on the end of
the condensate waste pipe to the
condensate pump. Push down and rotate
clockwise until the connector is locked.
Route and secure condensate waste pipe
(H) with clips supplied to prevent kinking
or restriction.
Cut off any excess pipe (H).
Fit the condensate waste pipe (H) to
adaptor (K) and secure with clip (J).
Connect adaptor (K) to 21.5mm plastic
pipe and terminate into an internal waste
trap.
(See Pre-Installation section for condensate
pipework running from the adaptor (K) to
the discharge outlet).
Never terminate or discharge into any
open source, including; sink, bath, shower,
bidet, toilet etc.
Note: Any external condensate pipework
should be protected with weather resistant
insulation to help prevent freezing.
The flexible pipe supplied can only be
used inside the property.
CAUTION: ISOLATE THE MAINS GAS AND
WATER SUPPLY BEFORE STARTING ANY
WORK AND OBSERVE ALL RELEVANT
SAFETY PRECAUTIONS.
GAS AND WATER CONNECTIONS:
Remove the transit bung (L) from the gas
& water connections (A, B, C, D & E) on
the boiler and mounting frame.
Note: that surplus water may be present due
to factory testing.
Ensure the area is clear of debris and
manoeuvre the boiler rear wheels onto the
outer rails of the mounting frame (F).
Take care when moving the boiler to
position the front wheels onto the rails
and align the gas/water connections and
the flue.
Secure boiler to mounting frame (F) with
screw (M)
Place the 5 larger valve sealing washers
(shown shaded) onto valves A, B, C, D &
E.
Ensure all pipework is clean.
Tighten the compression fittings to
secure:
A - CH flow (22mm).
B - DHW flow (22mm).
C - Gas inlet (22mm).
D - Mains water inlet (22mm).
E - CH return (22mm).