background image

19

Turn on the gas and electricity supplies.

Turn on a hot water tap to create a demand for hot water.

A continuous ignition spark will occur until the burner is alight

and sensed by the control circuit. The burner pressure should

be 15,5 mbar for natural gas and 35 mbar for Propane.

If the burner pressure cannot be achieved then check that the

inlet pressure at the appliance is 20mbar for natural gas and

37mbar for propane.

If the appliance does not light, check that it is not in the ‘lockout’

state by pressing the lockout reset LED button. See Fig. 26.

Check that fully heated water is available from the tap.

Gradually close the hot tap and check that the burner pressure

drops. Fully open the tap and check that the burner pressure

rises. Fully close the tap and check that the burner goes off.

The fan may continue running until the appliance has cooled to

a preset temperature.

Central Heating

The appliance is dispatched with the controls set to provide a

maximum output for Central Heating of 14 kW.

Check that all the radiator valves are open.

Set the CH temperature control knob to MAXIMUM and check

that the boiler is switched on.

A continuous ignition spark will occur until the burner is alight

and sensed by the control circuit. The burner pressure should

be 5,7 mbar for natural gas and 14,2 mbar for propane.

Set the room thermostat and the Central Heating Temperature

Control to maximum.

On sealed systems check that the system is pressurised and

set  to  the  required  pressure  as  indicated  on  the  gauge.

Check the system to ensure that all the radiators are heating up

evenly.

Balance the system so that the required temperature difference

across the central heating flow and return pipes is obtained.

Set the room thermostat, if fitted, to minimum and check that

the burner goes out. Reset the room thermostat to maximum

and  the  burner  will  re-light  and  follow  the  normal  operating

procedure.

Check for proper ignition of the burner after a break in the gas

supply. Turn off the gas service cock and wait for 60 seconds.

The  burner  will  go  out  but  sparking  from  the  electrode  will

continue for 10 seconds when the appliance will enter a ‘lockout’

state. Carefully open the gas service cock, press the lockout

reset  button  and  observe  the  burner  re-light  and  follow  the

normal sequence of operation.

Set the Operating Switch to OFF.

Turn off the gas service cock and the electrical supply to the

appliance.

Drain the system while the appliance is still hot.

Refill, vent and, with a sealed system, re-pressurise as described

in Section 11.2.

Domestic Hot Water and Central Heating

Turn on the electricity supply to the appliance and open the gas

supply cock at the appliance.

Set  the  Operating  Switch  (and  Programmer)  to  HEATING  &

WATER. If a programmer is fitted set the domestic hot water to

Continuous or 24 Hrs and the central heating to ON. Open a

tap, the burner will light and heat will pass into the system hot

water is discharged. Close the tap and the burner will go off.

The appliance will then return to the central heating mode and

automatically balance with the system requirements.

Set the Operating Switch to OFF and the burner will go out.

11.5 COMPLETION OF COMMISSIONING

Disconnect the pressure gauge and tighten the test point screw.

Restart the appliance and check for gas soundness around the

test point screw.

Refit the cabinet casing.

11

Commissioning The Appliance

11.1 SUMMARY

Domestic Hot Water System. Check that the mains water supply

has been fully flushed out at installation.

Central Heating System. Check that the central heating system

has been fully flushed out at installation.

Gas Service. The complete system, including the meter, must

be inspected and tested for soundness and purged as indicated

in BS 6891.

11.2 APPLIANCE AND  CENTRAL  HEATING  SYSTEM  -

PREPARATION

Remove  the  cabinet  casing  and  lower  the  control  assembly

chassis, if necessary.

Check  that  the  electrical  supply  and  the  gas  supplies  to  the

appliance are off.

Check that all the water connections throughout the system are

tight.

Open the system valves at the appliance. Open all the radiator

valves, fill the system and vent each radiator in turn.

The automatic air vent positioned on the expansion tank at the

top rear of the appliance will vent the appliance. Check that the

air vent cap has been loosened. See Fig. 1.

Check that the pressure relief valve, located at the lower RH

corner  of  the  appliance,  operates  by  turning  the  knob  anti-

clockwise until it releases. Water should be expelled from the

discharge pipe.

Set the Expansion Vessel Pressure

The charge pressure of the expansion vessel as dispatched is

0.5 bar, which is equivalent to a static head of 5 metres (17 ft).

The charge pressure must not be less than the static head at

the point of connection. See Fig. 7. A Schraeder type tyre valve

is fitted to the expansion vessel to allow the charge pressure to

be increased if necessary.

Set the system pressure

Fill the system until the pressure gauge shows  2.5 bar (37 lb/

in

2

) and check for water soundness. Release water from the

system using the relief valve test knob until the system design

pressure is obtained, up to a maximum of 1.5 bar.

Initial system design pressure (bar) = Expansion vessel charge

pr 0.3 bar.

NOTE: 1 bar is equivalent to 10.2 metres (33.5ft) of water.

If the pressure indicated on the pressure gauge is greater than

2.6  bar  when  operating  at  the  maximum  central  heating

temperature, then an extra expansion vessel must be fitted to

the system as close as possible to the appliance central heating

return connection. Refer to BS 7074 Part 1.

Any extra vessel fitted must be pressurised to the same figure

as  the  integral  vessel.  If  the  expansion  vessel  fails  then  the

specified replacement must be fitted.

11.3 PROGRAMMER

Any programmer fitted on the appliance should be set up at this

stage following the instructions sent with the programmer.

If a facia mounted programmer is to be fitted follow instructions

with  the  programmer.  Remove  the  facia  bottom  panel  as

described in section 14.3 (c)

11.4 APPLIANCE OPERATION

Turn off the gas and electricity supplies to the appliance.

Loosen  the  burner  pressure  test  point  screw,  located  on  the

gas supply pipe to the burner manifold (pos. 1) and connect a

pressure gauge.

Domestic Hot Water.

Set the CH temperature control knob to the MINIMUM position.

Set the water flow selector clockwise.

Set any programmer to HEATING & WATER

Summary of Contents for 47 311 43

Page 1: ...6 BOILER OUTPUT To Domestic Hot Water Modulating control Minimum 7 0 kW Maximum 23 0 kW To Central Heating Minimum 10 0 kW Maximum 20 0 kW IMPORTANT THESE INSTRUCTIONS APPLY IN GREAT BRITAIN AND IRELAND ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE GAS METER This appliance must be installed by a competent person in accordance with the CURRENT Gas Safety Installation and Use Regula...

Page 2: ...pes must be capable of supplying this quantity of gas in addition to the demands of any other appliances being served The meter governor should deliver a dynamic pressure of 20mbar 8in wg for natural gas or 37mbar 14 4 in wg for propane at the inlet to the appliance 1 Installation Regulations 1 1 Gas Safety Installation and Use Regulations 1998 It is the law that all gas appliances are installed b...

Page 3: ...ired temperature the burner will extinguish The appliance will remain off for a fixed period of three minutes before re lighting to automatically meet the system requirements Domestic Hot Water and Central Heating The appliance will supply heat to the central heating system as required Ademand for domestic hot water at a tap or shower will override the central heating requirement for the period of...

Page 4: ...er pressure test point 7 Gas inlet test point 8 Thermometer 8 1 Pressure gauge 12 Bypass tube 15 Relief valve 18 Circulation pump with air separator 20 Closed expansion vessel 26 Expansion vessel valve 27 Automatic air vent 29 Burner injectors 30 Burner 32 Flame sensor 33 Ignition electrode 36 Primary temperature sensor NTC 43 Central heating flow 44 Domestic hot water outlet 45 Gas feed pipe 46 C...

Page 5: ... RATE kW Btu h kW Btu h mbar in wg l min kg h CH max 20 68 240 22 2 75 750 11 6 4 6 40 3 CH min 10 34 120 11 8 40 260 2 9 1 2 20 1 DHW max 23 78 480 25 6 87 350 15 5 6 1 46 3 DHW min 7 23 880 7 8 26 610 1 4 0 55 14 1 CH max 20 68 240 22 2 75 750 26 5 10 6 14 0 1 8 CH min 10 34 120 11 1 37 870 6 8 2 7 7 0 0 9 DHW max 23 78 480 25 6 87 350 35 14 0 16 0 2 1 DHW min 7 23 880 7 8 26 610 3 2 1 3 4 1 0 6...

Page 6: ... WATER Modulating 7 to 23 kW OUTPUT TO CENTRAL HEATING 10 to 20 kW MAXIMUM COLD SUPPLY PRESSURE 12 bar 180 psi CENTRAL HEATING CIRCUIT NOMINAL FLOW T 30 C 10 l m PRESSURE HEAD CORRESPONDING TO NOMINAL FLOW 0 2 bar CENTRAL HEATING FLOW TEMPERATURE 45 C 90 C MAXIMUM ADMISSIBLE PRIMARY WATER PRESSURE 2 65 bar DOMESTIC HOT WATER PRODUCTION WATER FLOW SELECTOR TURNED COMPLETELY TO THE RIGHT TEMPERATURE...

Page 7: ...ns given in BS 5440 2 this appliance may be fitted in a compartment with no vents as long as the minimum clearances stated in Section 6 Air Supply are maintained 4 7 The airing space must be separated from the boiler space by a perforated non combustible partition Expanded metal or rigid wire mesh is acceptable provided that the major dimension is less than 13mm See BS 6798 1987 4 8 No combustible...

Page 8: ...nifold 43 Central heating flow 45 Gas Inlet 47 Central heating return 101 Boiler cabinet 102 Flame viewing hole 103 Facia 114 Sanitary Hot and Cold 320 Appliance mounting bracket 341 Nut and olive 22mm compression 342 Nut and olive 15mm compression 343 Gas cock 401 Fibre Washer 402 Adapter 403 Nut ...

Page 9: ...r balcony level 300 mm 12 in From a surface facing a terminal 600 mm 24 in A B C D E F G H TERMINAL POSITION MIN DISTANCE I From a terminal facing a terminal 1200 mm 47 in J From an opening in a car port e g door window into dwelling 1200 mm 47 in K Vertically from a terminal on the same wall 150 mm 6 in L Horizontally from a terminal on the same wall 300 mm 12 in M From door window or air vent ac...

Page 10: ... circulation an extra expansion vessel is required 7 Sealed Primary Systems See Figs 5 and 6 7 1 The system must comply with the requirements of BS 6798 and BS 5449 7 2 The appliance must not be operated without the system being full of water properly vented and pressurised 7 3 The sealed system must only be filled by a competent person using one of the approved methods shown in figure 6 The syste...

Page 11: ...11 Fig 7 System filling and make up ...

Page 12: ...equirements and if necessary reference should be made to the local Water Company before fitting the appliance 8 2 MAINS COLD WATER INLET Devices capable of preventing the flow of expansion water must not be fitted unless separate arrangements have been made 8 3 The final 600mm of the mains cold water connection to the appliance should be made in copper tube only 8 4 The appliance is suitable for a...

Page 13: ...int for the casing Earth connection point for the electrical mains connection ionization current testing point Fig 10 2 Flue temperature limiter 18 Circulation pump 32 Flame sensor 36 Primary temperature sensor NTC 61 Reset button Indicator Light 84 3 way diverter valve 96 Water flow sensor micro switch 135 Master switch 136 Central heating temperature adjustment 151 Fuse T2 5A 250V 153 Transforme...

Page 14: ...ition to the flue turret The flue turret can be replaced by a flue bend with no reduction in flue length Flue components 1 Adapter boiler to turret 2 Adapter item 1 to vertical flue 3 Flue Turret 4 Standard air duct 5 Standard flue duct 6 Restrictor rings 4 off Fan inlet 7 Flue terminal 8 Extension air duct 9 Extension flue duct 10 In line flue elbows 45 and 90 IMPORTANT To ensure the correct oper...

Page 15: ...treated in accordance with the recommendations of BS 7593 1992 A gas cock is supplied but not located on the manifold therefore the final gas connection can only be made after the appliance has been mounted on the wall see fig 3 Brush off any dust or dirt from the valves Lift the appliance onto the top mounting plate and the lower pre plumbing manifold Make up the water connections ensuring that t...

Page 16: ...ot be necessary to cut the extension ducts 0 88m to 1 10m 1 63m to 1 85m or 2 38m to 2 5m Each extension duct must be connected to the first section of flue or the previous extension duct by firstly fitting the inner flue ducts together and pilot drilling and fixing see fig 19 Then the outer air ducts can be similarly fixed using the pair of screws provided The flue terminal section can then be te...

Page 17: ...er with the socket on the appliance slide or twist the turret into the boiler flue connection as described in section 10 4 preceding together with the appropriate restrictor ring 1 Adapter boiler to turret 2 Adapter item 1 to vertical flue Rubber sealing gasket Flue terminal Clamping ring 1 Flue centering ring 2 Air duct 3 Flue duct 1 3 2 4 5 4 Rubber sealing gasket 5 Flue terminal 10 6 FLUE BENDS...

Page 18: ...s must pass through the appropriate space in the control panel and be fixed with the cable clamps provided Refit the control panel cover Test the gas supply pipework up to the appliance for soundness as indicated in BS 6891 Refer to Section 11 for a full description of the filling venting and the pressurising of the system If the appliance is not to be commissioned immediately replace the cabinet ...

Page 19: ...ts Set the Operating Switch to OFF and the burner will go out 11 5 COMPLETION OF COMMISSIONING Disconnect the pressure gauge and tighten the test point screw Restart the appliance and check for gas soundness around the test point screw Refit the cabinet casing 11 Commissioning The Appliance 11 1 SUMMARY Domestic Hot Water System Check that the mains water supply has been fully flushed out at insta...

Page 20: ...cover from the gas setting screw 2 Unscrew the throttle screw no 1 fig 25 and connect the pressure gauge 3 Open the gas tap and switch on the appliance 4 Set the temperature selector to position 7 no 3 fig 25 5 Gauge the burner pressure for the required power taking into consideration the model type see Table 4 Adjust burner pressure using the gas setting screw no 2 fig 25 Turning clockwise lowers...

Page 21: ...on 7 outflow temperature of heating system up to 90 C Turn the main switch to to the left The timer will only work for 70 hours in the case of electricity failure read timer s operating instructions Turning the water flow selector anti clockwise will increase the flow and reduce the water temperature Turning the water flow selector clockwise will reduce the flow and increase temperature G766_152 I...

Page 22: ...g screws and slide off the top cover plate Cover the gas supply to burner orifice Inspect the finned copper heat exchanger and clean as necessary using a soft brush Re assemble the appliance in the reverse order 13 5 TEST THE APPLIANCE On completion of the service and reassembly of the appliance check for gas soundness and the correct operation of the appliance as described in Section 11 Commissio...

Page 23: ...connections on the flow and return pipe tails to the heat exchanger Slacken and lower the two locking nuts retaining the heat exchanger to the inner casing base Remove the two screws from the heat exchanger top retaining plate and remove the plate Lift up the heat exchanger and remove forwards Remove the limit stat electrical connections located at the top RH side of the heat exchanger Undo the sc...

Page 24: ...ated approximately midway up on the vertical gas inlet pipe and remove the gas valve and inlet pipe as a unit Unplug the electrical connection from the valve solenoid Fit the replacement valve in the reverse order ensuring that the face to face joint are located correctly Following the replacement of all the associated parts open the valves and fill and re pressurise the system as described in Sec...

Page 25: ...Disconnect the mains input cable from the screw terminals and pull off the earth lead from the spade terminal and pull away the cable locking clamp from the base Any other external control wiring should be removed in a similar manner Pull off the two edge connectors for the fan and pump supplies also the earth leads from the spade terminals and release the cable clamp Pull off the ignition leads f...

Page 26: ...Exchanger 8 705 406 203 10 Automatic Air Vent 8 718 505 028 11 System Pressure Gauge 8 717 208 047 12 Thermometer 8 717 208 027 13 Pressure Relief Valve 8 717 401 022 14 Circulating Pump 8 717 204 192 15 Expansion Vessel 8 705 407 001 16 Diverter Valve 8 708 505 014 17 DHW Flow Regulator Valve 8 707 002 628 18 Micro switch assembly 8 707 200 007 19 Domestic Water Filter 8 700 507 001 20 Fan 8 707 ...

Page 27: ...27 Fig 27 ...

Page 28: ...owing table 9 Turn on the gas service cock and electrical supply 10 Confirm for gas soundness turn on a hot water tap for maximum hot water output check all the gas connection points 11 Readjust the burner gas pressure for the new gas type according to the values in table 4 When this is done seal the adjusting screw with the wire and lead seal 12 Fix the sticker next to the data plate 13 Remount s...

Page 29: ...y 4 seconds Pressure sensing tube not connected to air pressure switch Re connect Air pressure sensing tube kinked Re align tube Damaged pressure sensing tube Replace as required Wiring to air pressure switch damaged or incorrectly connected check connections or if damaged replace wiring Flue ducts are to long Check design of flue system and revise layout of system as required Incorrect restrictor...

Page 30: ...30 19 Functional Flow Diagrams ...

Page 31: ...31 ...

Page 32: ...booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and or appearances are changed in the interests of continued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 6 720 605 553 PT 2000 11 ...

Reviews: