Worcester 11 KW User Manual Download Page 23

ALARMS

6 720 802 172 (2012/06)

23

Category:

 L.

Alarm lamp/buzzer:

 No.

Restart: 

The warning does not close anything but is registered in the 

alarm log.

▶ Check and clean the particle filter, if required.
▶ Contact your installer if the warning remains after acknowledgement.

14.8.3 HIGH TEMPERATURE DIFFERENCE COLLECTOR CIRCUIT 

E2X

Function:

 The warning is activated when the temperature difference 

between collector circuit out and collector circuit in becomes too big.

Reset condition:

 The warning is deactivated on acknowledgement of 

the warning display.

Category:

 L.

Alarm lamp/buzzer:

 No.

Restart: 

The warning does not close anything but is registered in the 

alarm log.

▶ Check and clean the particle filter, if required.
▶ Contact your installer if the warning remains after acknowledgement.

14.8.4 THE HEAT PUMP IS NOW WORKING IN ANTI-FREEZE MODE

Function:

 Activated when the temperature in one of the circuits 

becomes too low.

Reset condition:

 The temperature in the circuit is increased. 

Category:

 L.

Alarm lamp/buzzer:

 No.

Restart:

 Automatic once the alarm cause has disappeared.

▶ Contact your installer.

14.8.5 CHECK CONNECTION TO I/O BOARD X

Function:

 Depends on the board.

Reset condition:

 Communication with the board is re-established. 

Category:

 M.

Alarm lamp/buzzer:

 No.

Restart:

 Acknowledgement is required.

▶ Contact your installer.

14.8.6 CHECK CANBUS CABLE CONNECTION

Function:

 Communication with the controller has been interrupted. The 

controller executes a new start if the alarm is still active after two hours. 
If more than three new starts have been carried out within one hour, the 
alarm 

Too high boot count I/O board BAS x

 (category A), 

 

Chapter 14.7.7.

Category:

 M.

Alarm lamp/buzzer:

 No.

Restart:

 Acknowledgement is required.

▶ Contact your installer if the warning recurs often.

14.9 INFORMATION LOG

The information log shows information from the heat pump.

14.9.1 HIGH FLOW TEMPERATURE E2X.T8

Function:

 The information is given if the temperature of the heating 

medium is too high. The information can appear temporarily when high 
room and hot water temperatures are set.

Reset condition:

 The information is deactivated when the temperature 

falls to the permitted level. 

14.9.2 TEMPORARY HEAT PUMP STOP E21.RLP

Function:

 Activated when the pressure in the refrigerant circuit of the 

heat pump becomes too low. If the information appears several times 
during a certain time period, the information transforms into a category 
A alarm (

 Chapter 14.7.2).

Reset condition:

 The pressure goes back to the permitted level. 

14.9.3 TEMPORARY HEAT PUMP STOP E21.RHP

Function:

 Activated when the pressure in the refrigerant circuit 

becomes too high. If the information appears several times during a 
certain time period, the information transforms into a category A alarm 
(

 Chapter 14.7.3).

Reset condition:

 The pressure goes back to the permitted level. 

14.9.4 LOW TEMPERATURE COLLECTOR CIRCUIT IN E2X.T10

Function:

 The information is given if the temperature of the refrigerant 

to the heat pump is too low. If the information appears several times 
during a certain time period, the information transforms into a category 
A alarm (

 Chapter 14.7.5).

Reset condition:

 The temperature of the collector circuit exceeds the 

lowest permitted temperature. 

14.9.5 LOW TEMPERATURE COLLECTOR CIRCUIT OUT E2X.T11

Function:

 The information is given if the temperature of the refrigerant 

from the heat pump is too low. If the information appears several times 
during a certain time period, the information transforms into a category 
A alarm (

 Chapter 14.7.6).

Reset condition:

 The temperature of the collector circuit exceeds the 

lowest permitted temperature. 

14.9.6 HOT WATER PEAK FAILURE, NEW TRY WITHIN 24 HOURS

Function:

 The hot water has not come up at the right temperature. The 

hot water peak is repeated at the same time on the next day.

Reset condition:

 The correct hot water peak temperature is reached. 

14.9.7 TEMPORARY HEAT PUMP STOP DUE TO WORKING AREA 

LIMITS

Function:

 The compressor stops until the hot gas temperature falls 

below the set limit. The warning can occur when the heat pump works 
close to the lowest permitted outdoor temperature.

Reset condition:

 The hot gas temperature is within the range of the 

compressor. 

14.9.8 TEMPORARY HOT WATER STOP DUE TO WORKING AREA 

LIMITS

Function:

 Ongoing hot water operation is aborted and replaced with 

heating operation. The warning can occur when the heat pump works 
close to the lowest permitted outdoor temperature.

Reset condition:

 The hot gas temperature is within the range of the 

compressor. 

14.9.9 ADDITIONAL HEAT IS NOW WORKING AT ITS HIGHEST 

TEMPERATURE

Function:

 The additional heat begins to be stepped down. The 

information is activated in additional heat mode if the outgoing 
temperature (T1 or T8) approaches the set maximum value. The 
information is blocked during hot water peaks or extra hot water.

Reset condition:

 The information is deactivated when the temperature 

falls.

14.9.10 TEMPORARY HOT WATER STOP E2X

Function:

 Ongoing DHW mode is temporarily interrupted; the system 

changes over to heating mode.

Reset condition:

 DHW temperature drops a few degrees.

Summary of Contents for 11 KW

Page 1: ...UK IE USER MANUAL USER INSTRUCTIONS WORCESTER GREENSTORE LECP GROUND SOURCE HEAT PUMP IN EITHER SYSTEM OR COMBI VARIANTS 6 720 802 172 01 1I 6KW 7KW 9KW AND 11KW 6 720 802 172 2012 06 en...

Page 2: ...water 15 13 4 Holiday 16 13 5 Energy measurements 16 13 6 Timers 16 13 7 External control 16 13 8 General 17 13 9 Alarms 17 13 10 Access level 18 13 11 Return to factory settings 18 14 Alarms 18 14 1...

Page 3: ...keep the building warm Inbivalentoperationasecondheatingappliance e g gasoroilboiler is used to supplement the heat load 3 1 SELECTION AND SIZING OF A HEAT PUMP Itisessentialthatheatpumpsystemsaredes...

Page 4: ...t water cylinders Greenstore6 11Systemareheatpumpsdesignedtobesupplemented with external domestic hot water cylinders Once the heat pump has been installed and started there are a number of points tha...

Page 5: ...the condenser the heat is transferred to the house heating system radiators and underfloor heating and the hot water system The vapour cools and liquefies The pressure in the refrigerant is still hig...

Page 6: ...play 8 2 ON OFF BUTTON Use the On Off button to turn the heat pump on and off 8 3 STATUS LAMP 8 4 MENU DISPLAY Use the menu display in order to View information from the heat pump View available menus...

Page 7: ...x operating time on off Room temperature program Circuit 2 3 option Heat curve Room temperature program General Summer winter operation Hot water Extra hot water period Stop temperature Hot water pea...

Page 8: ...t The marked row shows your position among the functions under Hot water 3 The arrow shows that there is new menu on the next level 4 The points show that the next level is a setting window 5 The func...

Page 9: ...the initial menu Press in a menu display The detailed information is displayed for as long as is pressed Release The menu display is displayed Fig 18 11 3 OPERATING SYMBOLS Symbols for different funct...

Page 10: ...led room controllers Inthedisplaywindow operatingsymbolscanappearatthebottomright handside ThesymbolforExtrahotwaterorHolidayisdisplayedwhen the function has been set in the heat pump The room control...

Page 11: ...splayed only if party mode is active Holiday The same functions are included here as in the Holiday menu Chapter 13 4 Extra hot water duration For a description of setting Extra hot water Chapter 13 3...

Page 12: ...quare is highlighted The value is then highlighted Fig 25 Turn the menu dial to change the value Press the dial to save or use to return without saving Inthewindow thesquareishighlightedagainandanycha...

Page 13: ...the menu dial Turn the menu dial to be able to set additional values in the same way as above Go back one step with Select Saving alternative Return without saving Program 1 Program 2 The set changes...

Page 14: ...room controller Holiday Active program External control SET POINT VALUE CALCULATION The set point value for the heating circuit is the current curve value adjusted with active curve influence if any s...

Page 15: ...the day on which the hot water peak should take place None means that the function is disabled All means that a hot water peak takes place every day If hotwater peakisdeactivated comfortmodemustbesele...

Page 16: ...This displays Generated energy in kWh divided into Heating and Hot water Consumption electric additional heat ThisdisplaysConsumptionelectricadditionalheatinkWhdividedinto Heating and Hot water 13 6...

Page 17: ...played in the top left corner of the display If the alarm is active the alarm symbol Chapter 11 3 is displayed both in the alarm log and the initial menu of the control panel Delete alarm log The alar...

Page 18: ...er on the heat pump sounds for one second peralarmbuzzerintervalset Atcertaintimesofthedaythealarmbuzzer can be blocked or blocked altogether In the event of a warning the alarm buzzer does not sound...

Page 19: ...ice conditions Alarm timer starts Yes Reset condition The hot gas temperature drops to the permitted temperature Category A Alarm lamp buzzer Yes Restart Acknowledgement is required Contact your insta...

Page 20: ...ion The value of the sensor indicates 50 C Category E Alarm lamp buzzer Yes Restart Automatic once the alarm cause has disappeared Contact your installer if the alarm remains active for more than thre...

Page 21: ...en 14 7 19 FAILURE ON SENSOR T2 OUTDOOR Function In the event of a failure on T2 the outdoor temperature is set to 0 C so that the heat pump can continue to produce heat The alarm is activated when th...

Page 22: ...for more than three hours or recurs often 14 7 29 FAILURE ON SENSOR E2X T10 Function Activated when the sensor s resistance value indicates a temperature lower than 20 C Reset condition The value of t...

Page 23: ...tion The pressure goes back to the permitted level 14 9 3 TEMPORARY HEAT PUMP STOP E21 RHP Function Activated when the pressure in the refrigerant circuit becomes too high If the information appears s...

Page 24: ...connected to the heat pump collector circuit the cold side The level in the vessel must not be less than minimum level 1 3 If the fluid level is too low contact your installer 16 3 PARTICLE FILTER Th...

Page 25: ...6 720 802 172 2012 06 25 NOTES...

Page 26: ...6 720 802 172 2012 06 26 NOTES...

Page 27: ...6 720 802 172 2012 06 27 NOTES...

Page 28: ...900 Worcester Bosch Group is a brand name of Bosch Thermotechnology Ltd worcester bosch co uk 6 720 802 172 WORCESTER BOSCH GROUP TECHNICAL SUPPORT 0844 892 4010 APPOINTMENTS 0844 892 3000 SPARES 0190...

Reviews: