Worcester 11 KW User Manual Download Page 20

ALARMS

6 720 802 172 (2012/06)

20

▶ Contact your installer if the alarm remains after acknowledgement.

14.7.5 LOW TEMPERATURE COLLECTOR CIRCUIT IN E2X.T10

Function:

 Alarm is given if the collector circuit temperature is too low 

and if warning of this has been given several times.

Alarm timer starts:

 Yes.

Reset condition:

 The collector circuit temperature exceeds the lowest 

permitted temperature. 

Category:

 A.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Contact your installer if the alarm remains after acknowledgement.

14.7.6 LOW TEMPERATURE COLLECTOR CIRCUIT OUT E2X.T11

Function:

 Alarm is given if the collector circuit temperature is too low 

and if warning of this has been given several times.

Alarm timer starts:

 Yes.

Reset condition:

 The temperature of the refrigerant exceeds the lowest 

permitted temperature. 

Category:

 A.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Contact your installer if the alarm remains after acknowledgement.

14.7.7 TOO HIGH BOOT COUNT I/O BOARD BAS X

Function:

 Compressor stops. Is activated if the controller has executed 

more than three new starts after the alarm 

Check CANbus cable 

connection

(

 Chapter 14.8.6).

Alarm timer starts:

 Yes.

Reset condition:

 The CAN-BUS communication with the controller has 

been restored. 

Category:

 A.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Contact your installer if the alarm remains after acknowledgement.

14.7.8 MOTOR CUT-OUT 1 E2X.F11, COMPRESSOR 

Function:

 Activated when the compressor's motor cut-out has tripped 

because of high current or lost current phase resulting in undue strain on 
the compressor.

Alarms may also be due to faults in the soft start.

Alarm timer starts:

 Yes.

Reset condition:

 Motor cut-out reset. 

Category:

 B.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Check the heating system fuses, and main fuses.
▶ Contact your installer if the alarm remains after acknowledgement.

14.7.9 FAILURE ON SENSOR E2X.T6 HOT GAS

Function:

 The compressor stops because the hot gas cut-out cannot be 

guaranteed. Activated when the sensor's value indicates a temperature 
lower than -50 °C.

Alarm timer starts:

 Yes.

Reset condition:

 The value of the sensor indicates >

-50 °C. 

Category:

 E.

Alarm lamp/buzzer:

 Yes.

Restart:

 Automatic once the alarm cause has disappeared.

▶ Contact your installer if the alarm remains active for more than three 

hours or recurs often.

14.7.10 SHORT CIRCUIT ON SENSOR E2X.T6 HOT GAS

Function:

 The compressor stops because the hot gas cut-out cannot be 

guaranteed. Activated when the sensor's resistance value indicates a 
temperature higher than 150 °C.

Alarm timer starts:

 Yes.

Reset condition:

 The value of the sensor indicates < 150 °C. 

Category:

 E.

Alarm lamp/buzzer:

 Yes.

Restart:

 Automatic once the alarm cause has disappeared.

▶ Contact your installer if the alarm remains active for more than three 

hours or recurs often.

14.7.11 HIGH FLOW TEMPERATURE E1X.T1

Function:

 Compressor stops. Activated when the temperature in the 

heating circuit becomes too high in relation to the settings that are 
made.

Alarm timer starts:

 Yes.

Reset condition:

 The sensor's value falls below the temperature for 

beginning of the heating demand. 

Category:

 E.

Alarm lamp/buzzer:

 Yes.

Restart:

 Automatic once the alarm cause has disappeared.

▶ Lower the heating on the circuit.
▶ Check that the thermostat valves are open.
▶ Contact your installer if the alarm recurs often.

14.7.12 FAULTY ELECTRIC HEATER E21.E2

Function:

 The electric heater is turned off. Activated by tripped 

overheat protection on the electric additional heat, high flow 
temperature or too high temperature in electric additional heat. The 
automatic trip fuse to the electric additional heat may have been tripped 
due to, for example, a short circuit.

Reset condition:

 Overheat protection reset or the temperature has 

fallen. 

Category:

 F.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Reset the overheat protection if this has been triggered.

▶ Reset the automatic fuse if this has been tripped.

▶ Contact your installer if the alarm continues after acknowledgement.

14.7.13 OVERHEAT PROTECTION TRIPPED HOT WATER ELECTRIC 

HEATER

Function:

 The electric heater is turned off. If alarm output from the 

electric heater has been connected to the multi module, the alarm is 
given when an error occurs.

Reset condition:

 The error in the electric heater has been overcome and 

no alarm signal.

Category:

 F.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Contact your installer if the alarm remains after acknowledgement.

Summary of Contents for 11 KW

Page 1: ...UK IE USER MANUAL USER INSTRUCTIONS WORCESTER GREENSTORE LECP GROUND SOURCE HEAT PUMP IN EITHER SYSTEM OR COMBI VARIANTS 6 720 802 172 01 1I 6KW 7KW 9KW AND 11KW 6 720 802 172 2012 06 en...

Page 2: ...water 15 13 4 Holiday 16 13 5 Energy measurements 16 13 6 Timers 16 13 7 External control 16 13 8 General 17 13 9 Alarms 17 13 10 Access level 18 13 11 Return to factory settings 18 14 Alarms 18 14 1...

Page 3: ...keep the building warm Inbivalentoperationasecondheatingappliance e g gasoroilboiler is used to supplement the heat load 3 1 SELECTION AND SIZING OF A HEAT PUMP Itisessentialthatheatpumpsystemsaredes...

Page 4: ...t water cylinders Greenstore6 11Systemareheatpumpsdesignedtobesupplemented with external domestic hot water cylinders Once the heat pump has been installed and started there are a number of points tha...

Page 5: ...the condenser the heat is transferred to the house heating system radiators and underfloor heating and the hot water system The vapour cools and liquefies The pressure in the refrigerant is still hig...

Page 6: ...play 8 2 ON OFF BUTTON Use the On Off button to turn the heat pump on and off 8 3 STATUS LAMP 8 4 MENU DISPLAY Use the menu display in order to View information from the heat pump View available menus...

Page 7: ...x operating time on off Room temperature program Circuit 2 3 option Heat curve Room temperature program General Summer winter operation Hot water Extra hot water period Stop temperature Hot water pea...

Page 8: ...t The marked row shows your position among the functions under Hot water 3 The arrow shows that there is new menu on the next level 4 The points show that the next level is a setting window 5 The func...

Page 9: ...the initial menu Press in a menu display The detailed information is displayed for as long as is pressed Release The menu display is displayed Fig 18 11 3 OPERATING SYMBOLS Symbols for different funct...

Page 10: ...led room controllers Inthedisplaywindow operatingsymbolscanappearatthebottomright handside ThesymbolforExtrahotwaterorHolidayisdisplayedwhen the function has been set in the heat pump The room control...

Page 11: ...splayed only if party mode is active Holiday The same functions are included here as in the Holiday menu Chapter 13 4 Extra hot water duration For a description of setting Extra hot water Chapter 13 3...

Page 12: ...quare is highlighted The value is then highlighted Fig 25 Turn the menu dial to change the value Press the dial to save or use to return without saving Inthewindow thesquareishighlightedagainandanycha...

Page 13: ...the menu dial Turn the menu dial to be able to set additional values in the same way as above Go back one step with Select Saving alternative Return without saving Program 1 Program 2 The set changes...

Page 14: ...room controller Holiday Active program External control SET POINT VALUE CALCULATION The set point value for the heating circuit is the current curve value adjusted with active curve influence if any s...

Page 15: ...the day on which the hot water peak should take place None means that the function is disabled All means that a hot water peak takes place every day If hotwater peakisdeactivated comfortmodemustbesele...

Page 16: ...This displays Generated energy in kWh divided into Heating and Hot water Consumption electric additional heat ThisdisplaysConsumptionelectricadditionalheatinkWhdividedinto Heating and Hot water 13 6...

Page 17: ...played in the top left corner of the display If the alarm is active the alarm symbol Chapter 11 3 is displayed both in the alarm log and the initial menu of the control panel Delete alarm log The alar...

Page 18: ...er on the heat pump sounds for one second peralarmbuzzerintervalset Atcertaintimesofthedaythealarmbuzzer can be blocked or blocked altogether In the event of a warning the alarm buzzer does not sound...

Page 19: ...ice conditions Alarm timer starts Yes Reset condition The hot gas temperature drops to the permitted temperature Category A Alarm lamp buzzer Yes Restart Acknowledgement is required Contact your insta...

Page 20: ...ion The value of the sensor indicates 50 C Category E Alarm lamp buzzer Yes Restart Automatic once the alarm cause has disappeared Contact your installer if the alarm remains active for more than thre...

Page 21: ...en 14 7 19 FAILURE ON SENSOR T2 OUTDOOR Function In the event of a failure on T2 the outdoor temperature is set to 0 C so that the heat pump can continue to produce heat The alarm is activated when th...

Page 22: ...for more than three hours or recurs often 14 7 29 FAILURE ON SENSOR E2X T10 Function Activated when the sensor s resistance value indicates a temperature lower than 20 C Reset condition The value of t...

Page 23: ...tion The pressure goes back to the permitted level 14 9 3 TEMPORARY HEAT PUMP STOP E21 RHP Function Activated when the pressure in the refrigerant circuit becomes too high If the information appears s...

Page 24: ...connected to the heat pump collector circuit the cold side The level in the vessel must not be less than minimum level 1 3 If the fluid level is too low contact your installer 16 3 PARTICLE FILTER Th...

Page 25: ...6 720 802 172 2012 06 25 NOTES...

Page 26: ...6 720 802 172 2012 06 26 NOTES...

Page 27: ...6 720 802 172 2012 06 27 NOTES...

Page 28: ...900 Worcester Bosch Group is a brand name of Bosch Thermotechnology Ltd worcester bosch co uk 6 720 802 172 WORCESTER BOSCH GROUP TECHNICAL SUPPORT 0844 892 4010 APPOINTMENTS 0844 892 3000 SPARES 0190...

Reviews: