SETTINGS

6 720 802 172 (2012/06)

13

Fig. 27

▶ Turn the menu dial to change the value.

Fig. 28

▶ Press the dial to save or use 

 to return without saving.

▶ Use 

 to leave the curve setting window and return to the menu.

>> 

Compressor x operating time on/off

▶ Select how long the compressor should be on or off in heating mode.

Higher set values result in fewer compressor starts and stops, which 
achieves higher economy. However, more pronounced temperature 
fluctuations in the heating system may result than with lower values.

>> 

Room temperature program

▶ Choose if the circuit should be controlled with a program or not.

HP optimized

This means that the control unit is only controlled by the flow set point 
value (

 Chapter 13.2.1), without programmed changes during the 

day. Optimised operation provides the best comfort and energy savings 
in the vast majority of cases.

Program 1 and 2

These selections provide an opportunity to define user programs for 
time control by adjusting the start and stop times, as well as a normal and 
an programmed temperature.

To set the desired time of day:
▶ Select 

Program 1

 or 

Program 2

.

▶ Go to menu 

View/edit active program

.

▶ Select day by turning the menu dial.

Fig. 29

▶ Press the menu dial to mark the value to be changed.

Fig. 30

▶ Turn the menu dial until the desired setting has been selected.
▶ Then press the menu dial.
▶ Turn the menu dial to be able to set additional values in the same way 

as above.

▶ Go back one step with 

.

▶ Select 

Saving alternative

:

Return without saving

Program 1

Program 2

The set changes are saved as a selected program or not at all.

▶ To adjust the normal temperature, proceed to menu 

Room 

temperature normal

.

▶ To adjust the exceptional temperature, proceed to menu 

Room 

temperature exception

.

Room temperature program when there is a room controller:

>> 

Room temperature program

>>> 

Active program

If a program is selected, the following (if the menu button is turned) is 
displayed:

>>> 

View/edit active program

>>> 

Room temperature normal

▶ Set the desired set point for the room temperature.

Recommendations:
▶ Increase the value of the right point if it feels too cold 

at low outdoor temperatures.

▶ Increase the value of curve at 0 °C if it feels a little cold 

at outdoor temperatures around 0.

▶ Increase or decrease the value of the curve equally at 

the right and left points to fine adjust the heat (the 
curve is offset parallel).

Factory setting

20.0

Lowest value

10.0 (Comfort)

Highest value

30.0 (Economy)

Table 10 Compressor operating time on/off

Factory setting

HP optimized

Alternative

• HP optimized
• Program 1
• Program 2

Table 11 Program selection, circuit 1

6 720 614 789-21.3I

6 720 614 789-22.3I

Program

Day

Start

Stop

Program 1, 2

Mon - Sun

5:30

22:00

Table 12 Program 1 and 2

Factory setting

20.0 °C

Lowest value

10.0 °C

Highest value

35.0 °C

Table 13 Room temperature, normal

6 720 643 415-13.1I

6 720 643 415-14.1I

Summary of Contents for 11 KW

Page 1: ...UK IE USER MANUAL USER INSTRUCTIONS WORCESTER GREENSTORE LECP GROUND SOURCE HEAT PUMP IN EITHER SYSTEM OR COMBI VARIANTS 6 720 802 172 01 1I 6KW 7KW 9KW AND 11KW 6 720 802 172 2012 06 en...

Page 2: ...water 15 13 4 Holiday 16 13 5 Energy measurements 16 13 6 Timers 16 13 7 External control 16 13 8 General 17 13 9 Alarms 17 13 10 Access level 18 13 11 Return to factory settings 18 14 Alarms 18 14 1...

Page 3: ...keep the building warm Inbivalentoperationasecondheatingappliance e g gasoroilboiler is used to supplement the heat load 3 1 SELECTION AND SIZING OF A HEAT PUMP Itisessentialthatheatpumpsystemsaredes...

Page 4: ...t water cylinders Greenstore6 11Systemareheatpumpsdesignedtobesupplemented with external domestic hot water cylinders Once the heat pump has been installed and started there are a number of points tha...

Page 5: ...the condenser the heat is transferred to the house heating system radiators and underfloor heating and the hot water system The vapour cools and liquefies The pressure in the refrigerant is still hig...

Page 6: ...play 8 2 ON OFF BUTTON Use the On Off button to turn the heat pump on and off 8 3 STATUS LAMP 8 4 MENU DISPLAY Use the menu display in order to View information from the heat pump View available menus...

Page 7: ...x operating time on off Room temperature program Circuit 2 3 option Heat curve Room temperature program General Summer winter operation Hot water Extra hot water period Stop temperature Hot water pea...

Page 8: ...t The marked row shows your position among the functions under Hot water 3 The arrow shows that there is new menu on the next level 4 The points show that the next level is a setting window 5 The func...

Page 9: ...the initial menu Press in a menu display The detailed information is displayed for as long as is pressed Release The menu display is displayed Fig 18 11 3 OPERATING SYMBOLS Symbols for different funct...

Page 10: ...led room controllers Inthedisplaywindow operatingsymbolscanappearatthebottomright handside ThesymbolforExtrahotwaterorHolidayisdisplayedwhen the function has been set in the heat pump The room control...

Page 11: ...splayed only if party mode is active Holiday The same functions are included here as in the Holiday menu Chapter 13 4 Extra hot water duration For a description of setting Extra hot water Chapter 13 3...

Page 12: ...quare is highlighted The value is then highlighted Fig 25 Turn the menu dial to change the value Press the dial to save or use to return without saving Inthewindow thesquareishighlightedagainandanycha...

Page 13: ...the menu dial Turn the menu dial to be able to set additional values in the same way as above Go back one step with Select Saving alternative Return without saving Program 1 Program 2 The set changes...

Page 14: ...room controller Holiday Active program External control SET POINT VALUE CALCULATION The set point value for the heating circuit is the current curve value adjusted with active curve influence if any s...

Page 15: ...the day on which the hot water peak should take place None means that the function is disabled All means that a hot water peak takes place every day If hotwater peakisdeactivated comfortmodemustbesele...

Page 16: ...This displays Generated energy in kWh divided into Heating and Hot water Consumption electric additional heat ThisdisplaysConsumptionelectricadditionalheatinkWhdividedinto Heating and Hot water 13 6...

Page 17: ...played in the top left corner of the display If the alarm is active the alarm symbol Chapter 11 3 is displayed both in the alarm log and the initial menu of the control panel Delete alarm log The alar...

Page 18: ...er on the heat pump sounds for one second peralarmbuzzerintervalset Atcertaintimesofthedaythealarmbuzzer can be blocked or blocked altogether In the event of a warning the alarm buzzer does not sound...

Page 19: ...ice conditions Alarm timer starts Yes Reset condition The hot gas temperature drops to the permitted temperature Category A Alarm lamp buzzer Yes Restart Acknowledgement is required Contact your insta...

Page 20: ...ion The value of the sensor indicates 50 C Category E Alarm lamp buzzer Yes Restart Automatic once the alarm cause has disappeared Contact your installer if the alarm remains active for more than thre...

Page 21: ...en 14 7 19 FAILURE ON SENSOR T2 OUTDOOR Function In the event of a failure on T2 the outdoor temperature is set to 0 C so that the heat pump can continue to produce heat The alarm is activated when th...

Page 22: ...for more than three hours or recurs often 14 7 29 FAILURE ON SENSOR E2X T10 Function Activated when the sensor s resistance value indicates a temperature lower than 20 C Reset condition The value of t...

Page 23: ...tion The pressure goes back to the permitted level 14 9 3 TEMPORARY HEAT PUMP STOP E21 RHP Function Activated when the pressure in the refrigerant circuit becomes too high If the information appears s...

Page 24: ...connected to the heat pump collector circuit the cold side The level in the vessel must not be less than minimum level 1 3 If the fluid level is too low contact your installer 16 3 PARTICLE FILTER Th...

Page 25: ...6 720 802 172 2012 06 25 NOTES...

Page 26: ...6 720 802 172 2012 06 26 NOTES...

Page 27: ...6 720 802 172 2012 06 27 NOTES...

Page 28: ...900 Worcester Bosch Group is a brand name of Bosch Thermotechnology Ltd worcester bosch co uk 6 720 802 172 WORCESTER BOSCH GROUP TECHNICAL SUPPORT 0844 892 4010 APPOINTMENTS 0844 892 3000 SPARES 0190...

Reviews: