Manual 26710V1
ProTechTPS Total Protection System
Woodward
103
Problem or
diagnostic indication
Description
Possible Cause
Suggested Actions
Trip Cycle Time Mon 1
Alarm
Indicates the Trip
Cycle Monitor Time 1
Alarm has been set.
Trip Cycle Monitor Time
1 Alarm is set when the
maximum cycle time has
been exceeded during a
trip cycle time test.
Check the Trip Cycle Time
Monitor Menu and note the
trip cycle time to see if the
cycle time indicator signal
is reaching the
ProTechTPS.
Connect PCT and verify
settings. Verify the trip
indicator input is from the
correct source and the max
cycle time setting is
correct.
Check external system by
following the trip signal
around the loop until it
returns back to the
ProTechTPS input that is
designated as the trip
indicator input.
Trip Cycle Time Mon 2
Alarm
Indicates the Trip
Cycle Monitor Time 2
Alarm has been set.
Trip Cycle Monitor Time
2 Alarm is set when the
maximum cycle time has
been exceeded during a
trip cycle time test.
Check the Trip Cycle Time
Monitor Menu and note the
trip cycle time to see if the
cycle time indicator signal
is reaching the
ProTechTPS.
Connect PCT and verify
settings. Verify the trip
indicator input is from the
correct source and the max
cycle time setting is
correct.
Check external system by
following the trip signal
around the loop until it
returns back to the
ProTechTPS input that is
designated as the trip
indicator input.
Table 5-3. Alarm Indications