7.3 Setting ranges and steps
System parameter
Setting
range Step
Tolerance
I
prim
I
Eprim
(SEK)
0.001...50.0KA
0.001; 0.002; 0.005; 0.01; 0.02;
0.05; 0.1; 0.2
U
E>
(U
prim
/
U
SEK
)
(SEK) 1.01...6500
0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1;
2; 5; 10; 20; 50
7.3.1 Time
overcurrent protection (I-Type)
Setting
range Step
Tolerance
I>
t
I>
0.2...4.0 x I
N
(EXIT)
0.03 - 260 s (EXIT)
(definite time)
0.05 - 10 (EXIT)
(inverse time)
0.01; 0.02; 0.05; 0.1 x I
N
0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1.0;
2.0; 5.0; 10 s; 20 s
0.01; 0.02; 0.05; 0.1; 0.2
3% from set value or
min..
2 % In
3% or
10 ms
3% of the measuring value of
the current or
20 ms (see
EN60255-3)
I>>
t
I>>
0.5...40 x I
N
(EXIT)
0.03...10 s (EXIT)
0.02; 0.05; 0.1; 0.2; 0.5; 1.0 x I
N
0.01 s; 0.02 s; 0.05 s; 0.1 s; 0.2 s
3% from set value or
min.
2% In
3% or
10 ms
7.3.2 Earth fault protection (SR/YR-Type)
Setting
range
Step
Tolerance
I
E>
t
IE>
0.01...2.0 x I
N
(EXIT) (SR)
0.1...20 % I
N
(EXIT)(YR)
0.03...260 s (EXIT)
(definite time)
0.05...10 (EXIT)
(inverse time)
0.001; 0.002; 0.005; 0.01; 0.02;
0.05 x I
N
0.01%; 0.02%; 0.05% I
N
0.01; 0.02; 0.05; 0.1; 0.2; 0.5;
1.0; 2.0; 5.0; 10; 20 s
0.01; 0.02; 0.05; 0.1; 0.2
5% from set value
or
0.3% I
N
0.3% I
N
(SR);
0.03% I
N
(YR)
3% or
15 ms
3% of the measuring value of
the current or
20 ms (see EN60255-3)
I
E>>
t
IE>>
0.01...15 x I
N
(EXIT) (SR)
0.1...150 % I
N
(EXIT)(YR)
0.03...10 s (EXIT)
0.001; 0.002; 0.005, 0.01; 0.02;
0.05; 0.1; 0.2; 0.5 x I
N
0.01%; 0.02%; 0.05% I
N
0.01 s; 0.02 s; 0.05 s; 0.1 s; 0.2s
5% from set value
0.3% I
N
(SR);
0.03% I
N
(YR)
3% or
15 ms
7.3.3 Earth fault protection (E/X-Type)
Setting
range Step
Tolerance
I
E>
t
IE>
0.01...2.0 x I
N
(EXIT)(E)
0.1...20 % I
N
(EXIT)(X)
0.03...260 s (EXIT)
(definite time)
0.05...10 (EXIT)
(inverse time)
0.001; 0.002; 0.005; 0.01; 0.02; 0.05 x
I
N
0.01%; 0.02%; 0.05% I
N
0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1.0; 2.0;
5.0; 10; 20 s
0.01; 0.02; 0.05; 0.1; 0.2
5% from set value or
0.3% I
N
(E);
0.03% I
N
(X)
3% or ±15 ms
3% of the measuring value
of the current or
20 ms (see
EN60255-3)
I
E>>
t
IE>>
0.01...15.0 x I
N
(EXIT)(E)
0,1...150 % I
N
(EXIT)(X)
0.03...10 s (EXIT)
0.001; 0.002; 0.005, 0.01; 0.02; 0.05;
0.1; 0.2; 0.5 x I
N
0.01%; 0.02%; 0.05% I
N
0.01; 0.02; 0.05 s; 0.1 s; 0.2 s
5% from set value or
0.3% I
N
(E);
0.03% I
N
(X)
3% or
15 ms