Manual MRI3 GB
Woodward
DOK-TD-MRI3 Rev.A
29
5. Operation and settings
5.1 Display
Function
Display shows
Pressed push button
Corresponding
LED
Normal operation
WW
Measured operating values
Actual measured val-
ues (related to I
N
; U
E
1
))
(XR-type related to %
I
N
)
<SELECT/RESET> one time
for each
L1, L2, L3, E, U
E>
, I
E>
(I
P
/I
Q
in reference to
directional feature)
Measuring range overflow
max.
<SELECT/RESET>
L1, L2, L3, E
Setting values:
phase (I>; CHAR I>; t
I>
; I>>; t
I>>
)
earth (I
E>
; CHAR I
E
; t
IE>
; I
E>>
; t
IE>>
; U
E>
)
Current settings
Trip delay
characteristics
<SELECT/RESET> one time
for each parameter
I>; CHAR I>; t
I>
; I>>;
t
I>>
; LED
→←
I
E>
;
CHAR I
E
; t
IE>
; I
E>>
;
t
IE>>
; U
E>
Current display as second rated repeti-
tion current I
prim
(phase)/I
prim
(earth)
SEK (0.001-
50.0kA=prim)
<SELECT/RESET><+><->
L1, L2, L3, E
Parameter switch/external triggering of
the fault recorder
SET1, SET2, B_S2,
R_S2, B_FR, R_FR,
S2_FR
<SELECT/RESET><+><-> P2
LED blinking after activation
FLSH, NOFL
<SELECT/RESET><+><->
Characteristics
DEFT, NINV, VINV,
EINV, LINV, RINV
<SELECT/RESET><+><-> CHAR
I>
Characteristics
DEFT, NINV, VINV,
EINV, LINV, RINV,
RXIDG
<SELECT/RESET><+><-> CHAR
IE>
Reset setting (only available at inverse
time characteristics
0s/60s
<SELECT/RESET><+><->
I > + CHAR I> + t
I>
I
E
+ CHAR I
E
+ t
IE>
Relay characteristic angle for phase
current directional feature
RCA in Grad (°)
<SELECT/RESET><+><->
LED
→←
(green)
Warning or trip at earth fault
measuring (E- and ER/XR-types)
TRIP WARN
<SELECT/RESET><+><->
I
E>
Measured method of the residual
voltage U
E
1)
3 PHA; E-N; 1:1
<SELECT/RESET><+><->
U
E>
Residual voltage setting
Voltage in Volt
<SELECT/RESET><+><->
U
E>
Changeover of isolated (sin
φ
) or
compensated (cos
φ
) networks (for
ER/XR-type)
SIN <SELECT/RESET><+><->
Changeover of solidly/resistance
earthed networks (SR-type)
SOLI RESI
<SELECT/RESET><+><->
Switch failure protection
tCBFP
<SELECT/RESET> <+>->
Tripping protection switch failure pro-
tection
CBFP
After fault tripping
Nominal frequency
f = 50/f = 60
<+> <-><SELECT/RESET>
Blocking of function
EXIT
<+> until max. setting value
LED of blocked para-
meter
Slave address of serial interface 1-32
<+>
<-><SELECT/RESET>
RS
Baud-Rate 2)
1200-9600
<SELECT/RESET> <+><->
RS
Parity-Check 2)
even odd no
<SELECT/RESET> <+><->
RS
Recorded fault data
Tripping currents and
other fault data
<SELECT/RESET> one time
for each phase
L1, L2, L3, E I>, I>>,
I
E>
, I
E>>
, U
E>
Save parameter?
SAV?
<ENTER>
Delete failure memory
Wait <->
<SELECT/RESET>
Enquiry failure memory
FLT1; FLT2.....
<-><+>
L1, L2, L3, E I>, I>>,
I
E>
, I
E>>
,
Trigger signal for the fault recorder
TEST, P_UP, A_PI,
TRIP
<SELECT/RESET> <+><->
FR
Number of fault occurrences
S = 2, S = 4, S = 8
<SELECT/RESET> <+><->
FR
Display of date and time
Y = 99, M = 10, D = 1,
h = 12, m = 2, s = 12
<SELECT/RESET> <+><->
Change over the blocking function
PR_B, TR_B
<ENTER> and <TRIP>;
<+><->
I>, I>>, I
E>
, I
E>>
or t
I>
,
t
I>>
, t
IE>
, t
IE>>
Blocking oft he protection function
BLOC, NO_B
<+> <-><SELECT/RESET>
I>, I>>, I
E>
, I
E>>