Parameter protection
Function
Unit
IT ITE ITER Default
settings
Actual
settings
2
parameter
sets
X
X
X
Set
1/Set
2
Set
1
Set
2
I
B,A
Base current of the thermal over-
load protection (low set element)
x I
N
X X X
0.40
k
A
Constant
X
X
X
0.50
I
B,A
Energizing delay (time )for the
thermal overload
s X X X 0.04
I
B,T
Base current of the thermal over-
load protection (high set element)
x I
N
X X X
0.40
k
T
Constant
X
X
X
0.50
I
B,T
Energizing delay (time )for the
thermal overload
s X X X 0.04
C
Time constant (cooling down)
min
X
X
X
0.5
W
Time constant (warming up)
min
X
X
X
0.5
I>
Pickup value for phase overcur-
rent
x I
N
X X X
0.20
CHAR I>
Tripping characteristic for phase
overcurrent element
X
X X DEFT
tI>
Trip delay for phase overcurrent
element
(s) X X X 0.06
I>+CHARI> Reset
Modus
X X
X
I>>
Pickup value for overcurrent high
set element
x I
N
X X X
1.00
tI>>
Trip delay for overcurrent high
set element
s X X X 0.06
1:1/3pha/e-n Residual voltage measuring
X
3pha
U
E
Pickup value for residual voltage
V
X
1/2/5
I
E>
Pickup value for earth fault low
set element
x I
N
X X 0.01
WARN/TRIP Warning/tripping
setting
X
X
TRIP
CHAR I
E
Tripping characteristic for earth
fault overcurrent element
X DEFT
tIE>
Trip delay for earth fault overcur-
rent elemnt
(s) X X 0.06
IE>+CHAR
I>
Reset Mode
s
X
0
IE>>
Pickup value for earth fault high
set element
x I
N
X X 0.01
tIE>>
Trip delay for earth fault high set
element
s X X 0.06
SIN/COS
SIN/COS - setting
X
SIN
Block/Trip
Block/trip - time
s
X
X
EXIT
t
CBFP
Trip time circuit breaker failure
protection
X X X X EXIT
RS*
Baud-Rate of serial interface
X
X
X 9600
RS*
Parity check of serial interface
X
X
X even
RS
Slave Address of serial interface
X
X
X 1
*only Modbus Protocol