7.3.4 Earth fault protection
Setting
range
Step
Tolerance
I
E>
0.01...2.0 x I
N
(EXIT) (E)
0.01...0.45 x I
N
(EXIT)
(ER)
0.001
(0.01...0.05)
0.002
(0.05...0.1)
0.005
(0.1...0.2)
0.01
(0.2...0.5)
0.02
(0.5...1.0)
0.05
(1.0...2.0)
3% from set value
or
0.3% I
N
t
IE>
0.04 - 260 s (EXIT) (E)
0.06...260 s (EXIT) (ER)
(definite time)
0.05 - 20 (EXIT)
(inverse time)
0.02
(0.04...1.0)
0.05
(1.0...2.0)
0.1
(2.0...5.0)
0.2
(5.0...8.5)
0.5
(8.5...10.0)
1.0
(10...20)
2.0
(20...50)
5.0
(50...100)
10.0
(100...260)
0.01
(0.05...0.5)
0.02
(0.5...1.0)
0.05
(1.0...2.0)
0.1
(2.0...5.0)
0.2
(5.0...10.0)
0.5
(10.0...20.0)
3% or
20 ms
5% for NINV
and VINV
7.5% for NINV
and EINV
I
E>>
0.01...2.0 x I
N
(EXIT) (E)
0.01...0.45 x I
N
(EXIT)
(ER)
0.001
(0.01...0.05)
0.002
(0.05...0.1)
0.005
(0.1...0.2)
0.01
(0.2...0.5)
0.02
(0.5...1.0)
0.05
(1.0...2.0)
3% from set value
t
IE>>
0.04...10 s (EXIT)
0.02
(0.04...0.5)
0.05.
(0.5...2.0)
0.1
(2.0...5.0)
0.2
(5.0...10)
3% or
20 ms
RS
1...32
Table 7.4: Setting ranges and steps
Setting ranges for k:
Cable protection:
k = 1...5
Transformer- and generator stator:
k = 0.5...1.5
7.3.5 Earth fault protection (ER-Type)
Setting
range
Step
Tolerance
U
E>
U
N
= 100 V:
3 PHA/e-n: 1 - 70 V
1:1: 1- 120 V
U
N
= 230 V:
3 PHA/e-n: 2 - 160 V
1:1: 2 - 300 V
U
N
= 400 V:
3 PHA/e-n: 5 - 300 V
1:1: 5 - 500 V
1 V
1 V
2 V
2 V
5 V
5 V
5% from set value or <0.5% U
N