Manual 03554
GECO
Stoichiometric
Woodward
1
Chapter 1.
General Information
Welcome!
This manual describes the GECO™
and GECO Vista Stoichiometric controls.
The GECO
Stoichiometric control provides precise air/fuel ratio control for
engines using three way catalytic converters to reduce exhaust emissions. It is a
more sophisticated exhaust oxygen feedback control system because it includes
continuous oxygen sensor diagnostics, catalyst over-temperature & differential
pressure protection, and failsafe operating modes.
Available Woodward Stoichiometric Controls
Woodward Control P/N
Enclosure Type
Touch Display /
Handheld
9907-865 – GECO
Stoichiometric
Hoffman Enclosure
Handheld
9907-867 – GECO
Stoichiometric
Panel Assembly
Handheld
9907-879 – GECO Vista
Hoffman Enclosure
Touch Display
GECO
Stoichiometric System Features
Microprocessor-based
o
9–30 Vdc supply operation voltage for GECO Stoichiometric
o
19.2–28.8 Vdc supply operation voltage for GECO Vista
Pre-catalyst, closed loop, exhaust oxygen feedback control
Post-catalyst, exhaust oxygen feedback, cascade control allowing
adaptation to changing catalyst performance
Post-catalyst exhaust oxygen control set point variable with engine load
Adjustable fuel valve dithering algorithm for better catalyst control
Catalyst temperature monitoring to protect the catalyst from engine fueling
malfunctions (2 K-type thermocouples)
Catalyst differential pressure monitoring to indicate ash build-up and help
meet regulatory requirements
Open loop valve positioning in event of critical oxygen sensor malfunction or
large transient load changes
Self-learning
capability
that “remembers” appropriate fuel valve positions
over engine load range providing near-perfect failsafe operation
Capable of driving up to two fuel metering valves for “V” engine
configurations
Utilizes low-cost L-Series fuel trim valves capable of “Full-flow’ fuel trim
strategy that extends the AFR adjustment range
RS-485/Modbus
®
* communications support for data transmission
Full color HMI screen, enabling monitoring without hand-held terminal
(available on the GECO Vista model)
Comprehensive diagnostics including continuous oxygen sensor health
monitoring
Manual closed loop enable switch
Alarm
relay
Shutdown
relay
LED Driver for Power Indication, Alarm & Shutdown
Summary of Contents for GECO
Page 8: ...GECO Stoichiometric Manual 03554 vi Woodward...
Page 65: ...Manual 03554 GECO Stoichiometric Woodward 57...
Page 66: ...GECO Stoichiometric Manual 03554 58 Woodward Figure 8 2 Wiring for Single Bank...
Page 67: ...Manual 03554 GECO Stoichiometric Woodward 59...
Page 68: ...GECO Stoichiometric Manual 03554 60 Woodward Figure 8 3 Wiring for Dual Bank...
Page 69: ...Manual 03554 GECO Stoichiometric Woodward 61 Figure 8 4 Legend Plate...