GECO
Stoichiometric Manual
03554
78
Woodward
Appendix.
Modbus Register Addresses
Integer Input/Output Parameters
Intege
r
Ad
d
ress
Parameter
Name
Parameter
Description
In
tern
al
B
y
tes Internal
Units
Multiply
By
Then
Add
To
Obtain
1
RPM
Engine speed
2
[16.0] rpm
1
0
rpm
2
MAP
Intake manifold pressure - bank 1
2
[8.8] psia
0.00390625
0
psia
5
DP
Catalyst Differential Pressure
[8.8] inH2Od
0.00390625
0
inH2Od
12
CJC
Cold junction (control) temperature
2
[13.3] deg F 0.125
0
deg F
16 EGO1
Engine-out stoichiometric oxygen sensor
- bank 1
1
[0.8] 1.2V
0.004684096
0
volts
17 EGO2
Engine-out stoichiometric oxygen sensor
- bank 2
1
[0.8] 1.2V
0.004684096
0
volts
18 EGO3
Catalyst-out stoichiometric oxygen sensor
- bank 1
1
[0.8] 1.2V
0.004684096
0
volts
20 EGO1_TARG
EGO1
desired
voltage
1 [0.8]
1.2V 0.004684096 0 volts
21 EGO2_TARG
EGO2
desired
voltage
1 [0.8]
1.2V 0.004684096 0 volts
22 EGO3_TARG
EGO3
desired
voltage
1 [0.8]
1.2V 0.004684096 0 volts
24
EGO1_BASE
EGO1 base desired voltage
1
[0.8] 1.2V 0.004684096 0 volts
25
EGO2_BASE
EGO2 base desired voltage
1
[0.8] 1.2V 0.004684096 0 volts
26
EGO1_HEALTH
EGO1 health
1
[0.8] fraction 0.390625
0
%
27
EGO2_HEALTH
EGO2 health
1
[0.8] fraction 0.390625
0
%
28
EGO3_HEALTH
EGO3 health
1
[0.8] fraction 0.390625
0
%
30
CL1
Closed loop control value - bank 1
2
[S0.15]
0.003051758
0
%
31
CL2
Closed loop control value - bank 2
2
[S0.15]
0.003051758
0
%
32
ADAPT1
Adaptive control value - bank 1
2
[S0.15]
0.003051758
0
%
33
ADAPT2
Adaptive control value - bank 2
2
[S0.15]
0.003051758
0
%
34
VALVE1
Fuel valve command - bank 1
2
[S0.15]
0.003051758
0
%
35
VALVE2
Fuel valve command - bank 2
2
[S0.15]
0.003051758
0
%
39
VOLTAGE
Control supply voltage
1
[0.8] 32.45V 0.127274156
0
volts
42
GENERATOR_EST
Estimated generator output power
2
[16.0] bhp
0.7457
0
KW
43
POWER_EST
Estimated engine power
2
[16.0] bhp
1
0
bhp
44
TORQUE_EST
Estimated engine torque
2
[16.0] ft-lbs
1
0
ft-lbs
45
TC1
Thermocouple 1 temperature
2
[13.3] deg F 0.125
0
deg F
46
TC2
Thermocouple 2 temperature
2
[13.3] deg F 0.125
0
deg F
49
VALVE1_CUR
Valve driver 1 current
1
[0.8] 6.18A
0.024327349
0
amps
50
VALVE2_CUR
Valve driver 2 current
1
[0.8] 6.18A
0.024327349
0
amps
55 RUN_MODE
0=stopped,
1=cranking, 2=running
1
integer
1
0
0,1,2
Summary of Contents for GECO
Page 8: ...GECO Stoichiometric Manual 03554 vi Woodward...
Page 65: ...Manual 03554 GECO Stoichiometric Woodward 57...
Page 66: ...GECO Stoichiometric Manual 03554 58 Woodward Figure 8 2 Wiring for Single Bank...
Page 67: ...Manual 03554 GECO Stoichiometric Woodward 59...
Page 68: ...GECO Stoichiometric Manual 03554 60 Woodward Figure 8 3 Wiring for Dual Bank...
Page 69: ...Manual 03554 GECO Stoichiometric Woodward 61 Figure 8 4 Legend Plate...