Configuring a PWM Duty Cycle for a CAT ADEM Controller
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
If a PWM signal shall be used with a CAT ADEM speed controller, the duty cycle must be limited between 10%
and 85%. For this, the following settings must be made to the respective analog output (the following parameter
IDs and figures refer to analog output 1; however, another analog output may also be used):
ID
Parameter
Value
Comment
5200
Data source
[00.03] Speed bias A speed signal will be output
5201
Selected hardware type
User defined
A user-defined hardware type will be used
5208
User defined min. output value
10.00%
The minimum output value of the user-defined hardware type is 10%
5209
User defined max. output value
85.00%
The minimum output value of the user-defined hardware type is 85%
5202
PWM signal
On
The PWM signal is enabled
5210
PWM output level
10.00V
The PWM output level is configured to 10 V
Table 4-10: Configuring a PWM duty cycle for a CAT ADEM controller
Figure 4-21: Configuring a PWM duty cycle for a CAT ADEM controller