3.3 Operation Modes
The easYgen offers three operation modes:
n
AUTO
n
MANUAL (MAN)
n
STOP
n
... and an internal (non) operating phase during starting the
device itself
The operation mode can be initiated - if current settings allow this
function:
n
directly by pressing the according button at the front panel
n
directly by click on the according button at the ToolKit-SC
remote screen
n
via discrete inputs
n
via interface
3.3.1 Operation Mode AUTO
In operation mode AUTO breakers and genset are under easYgen
control. Start and stop of the engine is managed automatically
together with open, close, and breaker transition.
Depending on settings and application status, AUTO control can:
n
supply load by mains
n
supply load by generator
n
transition load supply from mains to generator or from gener‐
ator to mains
n
start the engine
n
stop the engine
Situation
n
Mains becomes abnormal because one or more of the parame‐
ters below misses its well defined working range:
–
“Overvoltage”
–
“Undervoltage”
–
“Overfrequency”
–
“Underfrequency”
–
“Mains voltage asymmetry”
–
“Mains phase rotation fail”
Start procedure will include breaker handling, engine start, and sig‐
naling/warning.
All of the above listed parameters are (back) in normal range.
Stop procedure will include breaker handling, engine stand-by, and
signaling/warning.
3.3.2 Operation Mode MANual
In operation mode MANual both breakers and genset are inde‐
pendently from each other under easYgen control.
General notes
General notes
Load supply transition from mains
to genset
Load supply transition from genset
(back) to mains
General notes
Operation
Operation Modes > Operation Mode MANual
37690A
easYgen-1800 | Genset Control
18