Manual 37441C
DTSC-50 - ATS Controller
Page 16/106
© Woodward
Power supply
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Power supply
2
1 0 Vdc
6.5 to 32.0 Vdc
6.5 to 32.0 Vdc
Figure 6-2: Power supply
Terminal
Description
A
max
1
0 Vdc reference potential
2.5 mm²
2
6.5 to 32.0 Vdc
2.5 mm²
Table 6-1: Power supply - terminal assignment
For a proper operation of the device, a minimum initial voltage of 10.5 Vdc is necessary when switching on the
DTSC. After this, a continuous operating voltage between 6.5 and 32 Vdc is possible to operate the DTSC-50
safely. The control unit is capable of handling voltage drops to 0 V for a maximum of 10 ms.
CAUTION
Ensure that the engine will be shut down by an external device in case the power supply of the
DTSC-50 control unit fails. Failure to do so may result in damages to the equipment.