Installation
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
For installation into a door panel, proceed as follows:
1.
Panel cut-out
Cut out the panel according to the dimensions in Figure 4-1.
2.
Remove terminals
Loosen the wire connection terminal screws on the back of the unit and
remove the wire connection terminal strips if required (1).
1
3.
Loosen clamping screws
Loosen the four clamping screws (1) until they are almost flush with the
clamp inserts and tilt the clamp inserts down by 45° (2) to remove them
from the housing. Do not completely remove the screws from the clamp
inserts.
1
2
4.
Insert unit into cut-out
Insert the unit into the panel cut-out. Verify that the unit fits correctly in
the cut-out. If the panel cut-out is not big enough, enlarge it accordingly.
Ensure that the gasket is placed properly if used. Ensure that the paper
strip is not pinched between gasket and panel to maintain isolation.
5.
Attach clamp inserts
Re-install the clamp inserts by tilting the insert to a 45° angle (1). Insert
the nose of the insert into the slot on the side of the housing. Raise the
clamp insert so that it is parallel to the control panel (2).
1
2
6.
Tighten clamping screws
Tighten the clamping screws (1) until the control unit is secured to the
control panel (2). Over tightening of these screws may result in the clamp
inserts or the housing breaking. Do not exceed the recommended tighten-
ing torque of 0.1 Nm.
1
2
7.
Reattach terminals
Reattach the wire connection terminal strips (1) and secure them with the
side screws.
1
Note:
If the gasket is damaged, it needs to be replaced. Use only the original gasket kit (P/N 3050-1057) for re-
placement.