Manual 85586V1
AtlasPC Digital Control, Vol. I
Woodward
41
Discrete Inputs
If a discrete input is not functioning properly, verify the following:
•
Measure the input voltage on the terminal block. It should be in the range of
18–28 Vdc.
•
Check the wiring, look for a loose connection at the terminal blocks and
disconnected or misconnected cables.
•
Check the software configuration to ensure that the input is configured
properly.
After verifying all of the above, the AtlasPC should be returned for service.
Serial I/O
If a serial port is not functioning properly, verify the following:
•
Check the wiring, look for a loose connection at the terminal blocks and
disconnected or misconnected cables.
•
Check to be sure that termination resistors are properly installed where
needed on the network.
•
Check the software configuration to ensure that the input is configured
properly.
•
Check that the cable is shielded and the shield is properly grounded per the
shields and grounding section in Chapter 2.
After verifying all of the above, the AtlasPC should be returned for service.
Summary of Contents for AtlasPC
Page 8: ...AtlasPC Digital Control Vol I Manual 85586V1 vi Woodward...
Page 130: ...AtlasPC Digital Control Vol I Manual 85586V1 122 Woodward...
Page 131: ......
Page 132: ......
Page 133: ......