Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
72
SERVICE
MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MINIMUM
MAXIMUM
02 AO1 Low Lim Val=
0
-30000
30000
03 AO1 Hi Lim Val=
200
-30000
30000
07A CONFIG AN OUT LINKNET
01 - Analog Out #1 Function
Monitor
02 AO1 Low Lim Val=
0
-30000
30000
03 AO1 Hi Lim Val=
200
-30000
30000
04 - Analog Out #2 Function
Monitor
05 AO2 Low Lim Val=
0
-30000
30000
06 AO2 Hi Lim Val=
200
-30000
30000
08 MAIN CONTROL
01 Governor Run
Monitor
02 Unit Online
Monitor
03 Start Gate Rate
1
0.01
100
04 Unit Stop Rate
5
0.01
100
05 Reset Pulse Time
3
0.01
10
06 Fast Offline Stop?
TRUE
FALSE
TRUE
07 Use Load Rej Gate Limit?
TRUE
FALSE
TRUE
08 Load Rej Gate Value
6
0
100
09 Load Rej Max Time
7
0
100
10 Frst Mode When Brk Close
2
1
4
11 Frst Mode When Brk Close
Monitor
12 Local / Remote / Both
Monitor
09 UNIT SPEED
01 Unit Speed (SS1)
Monitor
02 Unit Speed (SS2)
Monitor
03 Maximum Speed
Monitor
04 Reset Max Speed
FALSE
FALSE
TRUE
05 Use Spd Deadband?
1
1
3
06 High Deadband (%)
0.05
0
5
07 Low Deadband (%)
0.05
0
5
08 Start Speed
50
-10
100
09 Time to Start Spd
20
1
600
10 Top-Speed Window
110
98
110
11 Botm-Speed Window
90
90
102
12 Time to Stabl Spd
15
1
120
13 Overspeed Setpnt
120
0
300
14 Overspeed Delay
1
0.01
2
15 Enable OS Block
TRUE
FALSE
TRUE
16 Time to Incomplete Start
100
1
600
17 Speed SS1 Filter
0.01
0
10
18 Speed SS2 Filter
0.01
0
10
10 GATE POSITION
01 Gate Position
Monitor
02 Value @ 4 mA
0
-200
200
03 Value @ 20 mA
100
-200
200
04 Use Sml Mismatch
TRUE
FALSE
TRUE
05 Sml Mismatch Win
3
1
10
06 Sml Mismatch Tim
10
0
60
07 Use Lrg Mismatch
TRUE
FALSE
TRUE
08 Lrg Mismatch Win
5
1
10
09 Lrg Mismatch Tim
10
0
60
Released