Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
54
01 AO #1 - mA:
[MONITOR] This menu item displays the Analog Output #1 in mA.
02 ACTUATOR - mA:
[MONITOR] This menu item displays the Actuator Output (Gate) in mA.
30A MON AN OUT LINKNET
This menu allows all analog output mA current signals to be monitored from the LINKnet HT module.
01 AO #1 - mA:
[MONITOR] This menu item displays the Analog Output #1 in mA.
02 AO #2 - mA:
[MONITOR] This menu item displays the Analog Output #2 in mA.
31 MON ANALOG INPUT
This menu allows all analog input mA current signals to be monitored.
01 AI #1 - mA:
[MONITOR] This menu item displays the Analog Input #1 in mA.
02 AI #2 - mA:
[MONITOR] This menu item displays the Analog Input #2 in mA.
31A MON AN IN LINKNET
This menu allows all analog input mA current signals to be monitored from the LINKnet HT module.
01 AI #1 - mA:
[MONITOR] This menu item displays the Analog Input #1 in mA.
02 AI #2 - mA:
[MONITOR] This menu item displays the Analog Input #2 in mA
03 AI #1 - mA:
[MONITOR] This menu item displays the Analog Input #3 in mA.
04 AI #2 - mA:
[MONITOR] This menu item displays the Analog Input #4 in mA
05 AI #1 - mA:
[MONITOR] This menu item displays the Analog Input #5 in mA.
06 AI #2 - mA:
[MONITOR] This menu item displays the Analog Input #6 in mA
07 AI #1 - mA:
[MONITOR] This menu item displays the Analog Input #7 in mA.
08 AI #2 - mA:
[MONITOR] This menu item displays the Analog Input #8 in mA
32 BSLD CTRL (STPTS & RATES)
This menu is used to configure the Baseload parameters.
01 GEN UNLOAD TRIP LEVEL:
[*100 (0,30000)] This menu item defines the Generator Unload Trip
Level Load, in kW. This value is used as the load level at which a generator circuit breaker open
command is given when an unload command is given.
02 GENERATOR MAXIMUM LOAD:
[*5000 (10,30000)] This menu item defines the Generator Maximum
Load, in kW, i.e., the generator rated load.
03 GEN MAX BASELOAD VALUE:
[*4000 (10,30000)] This menu item defines the Generator Maximum
Baseload value, in kW.
04 GEN MIN BASELOAD VALUE:
[*200 (10,30000)] This menu item defines the Generator Minimum
Baseload value, in kW.
05 GEN MAX REM BSLD VALUE:
[*5000 (10,30000)] This menu item defines the Generator Maximum
Remote Baseload value, in kW.
06 GEN MIN REM BSLD VALUE:
[*500 (0,30000)] This menu item defines the Generator Minimum
Remote Baseload value, in kW.
07 GEN INITIAL BSLD VALUE:
[*1000 (0,30000)] This menu item defines the Generator Initial Baseload
value, in kW. This value is used as the Baseload setpoint every time the Baseload mode is enabled,
unless the Remote Baseload mode is enabled (in this case the initial value will be the remote baseload
value) or the Modbus baseload setpoint is used (in this case the initial value will be the remote Modbus
baseload setpoint value)
08 BASELOAD RAISE TIME (SEC):
[*60 (1,600)] This menu item defines the necessary time to the
baseload reference to go from the minimum baseload value to the maximum baseload value.
09 BASELOAD LOWER TIME (SEC):
[*60 (1,600)] This menu item defines the necessary time to the
baseload reference to go from the maximum baseload value to the minimum baseload value.
10 RMT BSLOAD INC TIME (SEC):
[*60 (1,600)] This menu item defines the necessary time to the
remote baseload reference to go from the minimum remote baseload value to the maximum remote
baseload value.
11 RMT BSLOAD DEC TIME (SEC):
[*60 (1,600)] This menu item defines the necessary time to the
remote baseload reference to go from the maximum remote baseload value to the minimum remote
baseload value.
Released