GAS SPECIFICATIONS
GAS INLET PRESSURE
For Tandoors running on natural gas, an inlet pressure of 13�6 mbar (5�5" W�C�) is recommended to ensure optimum Tandoor
performance� Incoming gas pressure below this pressure will affect Tandoor performance, the lower the pressure the greater the
negative impact� If the gas supply pressure is greater than 34 mbar (14" W�C� or 1/2 psi), an external regulator, supplied by others,
is REQUIRED to lower the gas pressure to the acceptable range� Issues caused by low or high gas pressure are installation issues,
and will not be covered under the Warranty�
For Tandoors running on LP, the recommended inlet pressure to ensure optimum Tandoor performance is 25 mbar (11" W�C�)
Incoming gas pressure below this range will affect Tandoor performance, the lower the pressure the greater the negative impact� If
the gas supply pressure is greater than 34 mbar (14" W�C� or 1/2 psi), adjustment to the supplied external regulator is REQUIRED to
lower the gas pressure to the acceptable range� Issues caused by low or high gas pressure are installation issues, and will not be
covered under the Warranty�
For all installations, follow best practices for proper gas line pipe sizing for the line serving the Tandoor� To insure proper operation,
all gas piping and fittings leading up to the Tandoor should have an inside diameter equal to or greater than that of the Tandoor
gas connection� Also make sure that a readily accessible shut off valve (supplied by others) is installed near the Tandoor, and in
accordance with all applicable codes� Shut off valves must be of the full-flow type, and not introduce any restriction into the gas line�
Use a properly sized flexible pipe and quick disconnect device approved for this application� When using a flexible connector make
sure that its design does not present any reduction in pipe diameter or other restriction� Tandoor issues caused by improper pipe
sizing, improper shut off valves, restrictive connectors, or any other deficiency in the gas supply design or installation will not be
covered under the Tandoor warranty�
THIS APPLIANCE IS NOT FOR USE WITH SOLID FUEL
GAS CONNECTION
The gas connection is made at the lower rear of the appliance� Have a licensed gas installer provide the hookup and test all
fittings and pipe connections for leaks� Use approved gas leak detectors (soap solutions or equivalent) over and around the fittings
and pipe connections to check for leaks�
DO NOT USE FLAME TO TEST FOR LEAKS!
This appliance is equipped with casters; it must be installed using the casters supplied with an approved gas connector/quick
disconnect device in accordance with all pertinent national and local regulations� It must also be installed with restraining means
to guard against transmission of strain to the connector�
IMPORTANT:
The gas supply to this appliance should be equipped with an individual appliance shutoff valve that is capable
of completely isolating the appliance from the main gas supply� This valve should be installed in such a manner as to be readily
accessible to the operator of the appliance�
The Wood Stone gas-fired Tandoor is equipped with a 12�7mm (1/2") FBSPT female gas connection, located on the underside
of the rear of the unit� Anchor points for the restraining means are provided on the underside of the Tandoor; these are holes
punched in the rear portion of the drip/debris pan rails�
Natural Gas (NG): Maximum inlet gas pressure must not exceed 34 mbar (14" W.C. or 1/2 psi)
Propane (LP): Maximum inlet gas pressure to the Tandoor, after the external regulator (if used),
must not exceed 34 mbar (14" W.C. or 1/2 psi)
NG: Minimum inlet gas pressure: 13.6 mbar (below will affect oven performance)
LP: Minimum inlet gas pressure: 25 mbar (below will affect oven performance)