Troubleshooting
Faults in electrical equipment and mechanical or hydraulic components may only be
rectified by qualified contractors specially trained in these fields.
If a fault occurs that cannot be remedied by means of the measures described below,
inform the manufacturer or a service partner authorised by the manufacturer.
LED constantly green:
pump running
LED flashing green:
pump on standby; no DHW draw-off
LED constantly off:
fault; see below
Mixer/servomotor – for operating condition, see chapter Commissioning
Possible cause
Fault remedy
Temperature in buffer
cylinder too low
Raise temperature in buffer cylinder; check position of
temperature sensors.
Charging pump is not deli-
vering any heating water
• Vent primary circuit with charging pump; see chapter
Commissioning
• Check hydraulic pressure drop between buffer cylin-
der and freshwater module and reduce if required
• Check whether all ball valves in the primary and
secondary circuit are open
• Check whether the freshwater module is correctly
connected to the drinking water and heating network
• Check the module is working correctly – for tempe-
rature and flow sensors, see chapter Commissioning
• Check signal lead (PWM) on the charging pump
• Check the power supply to the charging pump
• Check the charging pump is correctly connected to
the controller
• Replace faulty charging pump
Temperature sensor S1
(primary) faulty
Check function via service key; see chapter Commis-
sioning
Sensor VFS faulty
Check function via service key; see chapter Commis-
sioning
Set temperature set too
low
Correct set value on the controller; see chapter Com-
missioning
Mixer/servomotor faulty
Check function; see chapter Commissioning
Freshwater module faulty
Check mains connection
Replace freshwater module
Plate heat exchanger
scaled up
Descale or replace plate heat exchanger
Possible cause
Fault remedy
DHW and cold water con-
nection interchanged on
the freshwater module
Contact installer/contractor
Sensors faulty
Check function via service key; see chapter Commis-
sioning
Charging pump operating display:
Fault: DHW temperature is below the
selected set value
Fault: freshwater module does not
deliver any DHW when draw-off rate
is low (flow rate)
Summary of Contents for FWS-2-80
Page 5: ...5 3065014_201612 Joogiveekeskus Ühenduskomplekt Paigalduskomplekt Tarnepakend ...
Page 15: ...15 3065014_201612 Primaarpumba PWM signaal 3 Hooldus ...
Page 16: ...16 3065014_201612 Segisti mootori vahetamine Hooldus ...
Page 19: ...19 3065014_201612 Hooldus ...
Page 31: ...31 3065014_201612 Freshwater module Connection set Installation set Standard delivery ...
Page 41: ...41 3065014_201612 PWM signal primary pump 3 Maintenance ...
Page 42: ...42 3065014_201612 Replacing the mixer motor Maintenance ...
Page 45: ...45 3065014_201612 Maintenance ...
Page 67: ...67 3065014_201612 Pirminio siurblio PWM signalas 3 Techninė priežiūra ...
Page 68: ...68 3065014_201612 Maišymo variklio keitimas Techninė priežiūra ...
Page 71: ...71 3065014_201612 Techninė priežiūra ...
Page 93: ...93 3065014_201612 PWM signāls primārajam sūknim 3 Tehniskā apkope ...
Page 94: ...94 3065014_201612 Jaucēja motora nomaiņa Tehniskā apkope ...