9 Commissioning
FWL-PushPull-30 (TwinUnit)
7100904 | 202202
WOLF GmbH | 43
9.2 FWL-PushPull RLS service menu
Bol
d
Factory settings
LED flashes quickly
LED flashes slowly
LEDs
Parameters
Set value /
ventilation
level
Setting / description
Device type on
FWL-PushPull
(Fan1/Fan2)
1
2
FWL-PushPull-45
The type family, which is connec-
ted to the Fan1/Fan2 interface, is
selected here.
Notice: Only single-type FWL-
PushPull-45 or FWL-PushPull-30
unit combinations are permitted at
the fan interface!
Number of device pairs/
devices on
FWL-PushPull
(Fan1/Fan2)
1
2
3
4
5
1 FWL-PushPull-45 unit pair or
1 FWL-PushPull-30
2 FWL-PushPull-45 unit pairs or
2 FWL-PushPull-30
3 FWL-PushPull-45 unit pairs or
3 FWL-PushPull-30
Odd number 3 FWL-PushPull-45
units
Odd number 5 FWL-PushPull-45
units
The number of units connected to
the fan interface (Fan1/Fan2) is
selected here.
Ventilation levels
1
2
Ventilation level “0” possible
Ventilation level “0” blocked
If ventilation level “0” is set to
blocked, the ventilation units can-
not be switched off at this control.
The units then run with at least
ventilation level 1.