Balanced flue system
Provide ventilation for B23, B33, C53
31. Technical information, balanced flue
Connection types
Type
1)
Operating mode
Can be connected to
open flue
balanced
flue
moisture-resistant
chimney
room sealed
balanced
flue
balanced
flue
certified
balanced
flue
moisture-
resistant
flue
B23P, B33P, C13x,
C33x, C43x, C53,
C53x, C83x, C93x
X
X
B33, C53, C83x
C43x
C13x
2)
,
C33x, C53x
C63x
B23, C53x,
C83x, C93x
1)
Marking "x" indicates that all components of the flue gas route are surrounded by combustion air.
2)
In Switzerland, observe the G1 gas guidelines.
Information about multiple connections:
Point
Safe differential pressure in accordance with DIN EN 15502-2-1
FGB-28
FGB-35
a
The maximum safe differential pressure at the lowest thermal load
(Δpmax, saf(max))
25
b
The maximum safe differential pressure at the highest thermal load
(Δpmax, saf(min))
77
75
c
The maximum safe differential pressure at start
(Δpmax, saf(start))
25
d
The maximum functional differential pressure at the highest thermal load
(Δpmax, func(max))
25
e
The minimum safe differential pressure
(Δpmin, saf)
-200