30
3061490_0709
CGB-35/CGB-50
Output setting (parameter GB04)
The output setting can be modified with Wolf control accessories with eBUS capability.
The heating output will be determined by the gas fan speed. By reducing the gas fan speed in accordance with the
table, the maximum output will be matched at 80/60°C for natural gas E / H/LL and LPG.
Limiting the maximum output
Limiting the maximum output relative to a flow/return temperature of 80/60 °C
Settings for parameter GB04 with Wolf connection accessories with eBUS capability in [%]
Maximum
output
in
[kW]
Table: Output setting
CGB-35
Heating output
(kW)
8
10
12
14
16
17
19
21
23
24
26
28
30
31
32
Display value
(%)
30
35
40
45
50
55
60
65
70
75
80
85
90
95 100
CGB-50
Heating output
(kW)
11
14
17
19
22
24
27
29
32
34
37
39
42
44
46
Display value
(%)
30
35
40
45
50
55
60
65
70
75
80
85
90
95 100
Summary of Contents for CGB-35
Page 58: ...58 3061490_0709 Notes ...