Troubleshooting
34
CRC fault, BCC
Faulty boiler coding card
Replace parameter plug
35
BBC missing
Boiler coding card was removed
Korrekten Parameterstecker wieder
aufstecken
36
CRC fault, BCC
Faulty boiler coding card
Replace parameter plug
37
Incorrect BCC
The boiler coding card is incompatible with the
control unit PCB
Refit the correct parameter plug
38 BCC no. invalid
Faulty boiler coding card
Replace parameter plug
39
BCC system error
Faulty boiler coding card
Replace parameter plug
41
Flow monitoring
Return temperature > flow + 25 K.
Vent the heating system, check the sy
-
stem pressure.Check the heating circuit
pump.
50
Activation of boiler co
-
ding card
The parameter plug must still be enabled
Press reset 2x
52
Activation of boiler co
-
ding card
The parameter plug must still be enabled
Press reset 2x
60
Ionisation current
fluctuates
The siphon or the flue gas system is blocked
severe storm.
Clean siphon, check the flue gas system,
Check ventilation air, check monitoring
electrode.
61
Ionisation current
drops
Poor gas quality, monitoring electrode faulty,
severe storm.
Check monitoring electrode and lead.
LED constantly red
Ionisation lead shorted out or
Ionisation electrode earthed (housing).
Check the ionisation lead and position of
electrode to burner.
Press the reset button.