8
3064058_201610
AHU TE
AHUW TE
Final location
Always install AHU TE air-handling units in rooms where frost cannot occur.
If the occurrence of frost at the final location cannot be ruled out, adopt suitable measures
to prevent water-containing components from freezing. If an outside thermostat is
installed ensure it is adequately insulated to prevent the air-handling unit from shutting
down inadvertently (see frost protection measures, page 25).
AHUW TE air conditioning units are designed to be installed outdoors.
Note
Space requirements
Make sure a clear space equal to at least the width of the equipment units is available
on the operator side; this is the minimum space necessary for installation, operation
and maintenance (see the table below).
Footprint of space required for installation, operation and maintenance:
Fan section
0.8 x appliance width
Cooling coil, heating coil, KVS
1 x appliance width + 250 mm
Filter section up to AHU TE 96
1 x appliance width
from AHU TE 130 0.5 x appliance width
In back-to-back configurations with side-by-side units, leave clearances as stated above
on both sides for installation, operation and maintenance.
Install units that require a siphon (scrubber, humidifier, cooling coil, plate-type heat
exchanger, mist eliminator) in such a way as to ensure correct installation and operation
of the siphon (make adequate provision for the foundation height).
It is advisable to install a waterproof foundation for units with humidifiers and/ or cooling
coils installed above rooms containing moisture-sensitive equipment (e.g. IT rooms, etc.).