Troubleshooting guide
The LED does not light up
Check for correct connection and specification of the power adapter.
Ensure that the original power adapter is used.
Specifications: 9 V / DC, 1A
Polarity:
No Flame
In case of ignition or flame faliure check if the burner tube is clogged. Verify the input
pressure of the used gas. Ensure that the correct nozzle is installed in the unit.
Nozzle
N/55
: natural gas, input pressure: 18-25 mbar
Nozzle
P/34
: propane / butane gas, input pressure: 47-57 mbar
The optional foot pedal or external IR - motion sensor does not work
Check for correct connection of the cable.
Ensure that the socket and plug is not twisted or broken.
Status - LED flashes Amber (BHC)
Take care that there are no liquids or other substances at the Bypass (area between the
inner and the outer ring at the upper part
of the burner tube
(5)
).
Especially remove substances in the
marked areas at the electrodes. If there
are contaminants in this area, the flame
cannot encircle the electrodes correctly.
Clean this areas with a brush. The
burner tube can be cleaned with
customary commercial disinfectants,
or it can be sterilized in an autoclave or
washed in a dishwasher.
(see paragraph 6.1)
In operating mode “Button“ and Pedal “Standard“ the flame burns 30 seconds, only
BHC time limit is active, Status-LED “ is flashimg amber. The burner tube is clogged and
must be cleaned
(6.1)
.
Flame too small / large / soft
Check the position of the air and gas adjustment.
Check if the correct nozzle is installed.
Nozzle
N/55
: natural gas, 18-25 mbar
Nozzle
P/34
: propane / butane gas, 47-57 mbar
Check if the drilling of the active nozzle is blocked. Unscew the active nozzle.
(see paragraph 2.1)
If the drilling is blocked clean with a brush or compressed air.
The burner shuts-off due to overtemperature frequently
In case of overtemperature increase the air ventilation or change the operation site.
+
-
Bypass