16
5C
Compressor defective?
5B
Electrical connection of compressor
wrong? (Very loud operating noise, hot
gas line not heating)
5A
I22 temperature sensor defective?
5
Error 57 – No increase in temperature in the intermediate circuit (I22)
while compressor is active
yes
no
Replace temperature sensor.
yes
Have repair carried out by experi-
enced refrigeration technician.
yes
no
Rectify compressor’s electrical con-
nection.
Consult with Winterhalter technical cus-
tomer care
no