background image

 

10 

Connection diagram 

 

Position of the connections 

 

 

Water out  
(softened water);  
G ¾" external thread

 

Water supply (raw water) 
G ¾" external thread; 
min. 2.5 bar; max. 6 bar;  
max. 60 °C;  
max. 45°dH total hardness

 

Regeneration water 
½ " hose; 2000 mm long

 

Safety overflow 
½ " connection

 

Connection diagram 

 
 

 

 

INFO

 

Pos. 1 to 4 and pos. 6 are not included in the scope of supply 

 
A water safety device (pos. 4) must be used in order for the softener to be operated in accordance with DIN requirements. A kit is 
available from Winterhalter for this purpose. 
The kit contains a backflow preventer type HD in accordance with DIN EN 1717. 
National installation and operating regulations must also be complied with. 
 

The system can also be mounted in mirror image.

 

Provide on-site connections next to the device.

 

Waste water funnel with trap 

5 Hose 

to 

warewasher 

4 Water 

safety 

device 

Supply hose; 2 x G 3/4" union nut 

Dirt trap; 1 x G 3/4" union nut; 1 x G 3/4" external thread 

Water stop cock on-site, G 3/4" external thread 

89013537-00

 

Connection diagram

 

DuoMatik 3 softener 

Prepared: 07.02.2017 sch 

 

View from rear

View from front 

If space is limited, the water safety device (pos. 4) can also be 
installed in the water pipe somewhere else. 
Note: 
-  Top edge of the combination connector must be at least 

110 mm above the top edge of the device 

-  Vertical installation position 
-  Install in direction of flow 

Summary of Contents for DuoMatik 3

Page 1: ...DuoMatik 3 Operating instructions Connection diagram Commissioning instructions 7 12 GB...

Page 2: ......

Page 3: ...ce and how it functions The softener may only be operated as described in these operating instructions 2 Product description The softener consists of a mobile plastic container and a removable cover T...

Page 4: ...te the softener 5 Operation The softener works automatically following commissioning Only the regeneration salt must be refilled from time to time Caution Possibility of damage due to incorrect salt O...

Page 5: ...preventer 3 audibly suck in air while water is flowing out of the hose 4 Replace the backflow preventer 3 if it does not pass the test Reinstall the backflow preventer 3 according to the connection di...

Page 6: ...nce with DIN EN 1717 National installation and operating regulations must also be complied with The system can also be mounted in mirror image Provide on site connections next to the device 6 Waste wa...

Page 7: ...setting 5 mm Total hardness 40 dH Change distance a to 17 mm INFO The salt consumption per regeneration increases from 0 3 kg to 0 5 kg Ensure that the valve base 1 is sitting in the recess of the co...

Page 8: ...PORTANT The arrow must not point to the black area INFO Each tooth deviation means 20 litres of softened water more or less up until the next regeneration Switch on the warewasher connected to the sof...

Page 9: ......

Page 10: ...9 0 75 42 4 02 1 87 www winterhalter de info winterhalter de Winterhalter Gastronom GmbH Commercial Dishwashing Systems Winterhalterstrasse 2 12 88074 Meckenbeuren Germany Telephone 49 0 75 42 4 02 0...

Reviews: