34
Defrost cut-out
temperature
Setting 11
Press "Settings" button to advance to
Setting 11.
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint. This
setting is adjustable from 35°F to 50°F.
Factory default is 40°F.
Note: This setpoint must be 1°F/°C higher
than setting 10.
Note: If °C is selected and then switched
back to °F the default cut-out will change
to 41°F.
Defrost check
interval
Setting 12
Press "Settings" button to advance to
Setting 12.
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint. This
setting is adjustable from 30 min at 0
(zero), 1 hour at 1, and then in 1 hour
increments up to a maximum of 12 hours
at 12.
Room
temperature
offset
Setting 13
Press “Settings” button to advance to
Setting 13.
Press the “Up” or “Down” buttons to
adjust to the desired set point. Maximum
setting is +5°F, minimum setting is -5°F.
Factory default is zero (0).
Room temperature offset changes the
actual display reading (temperature only)
by the value of this setting.
Example: Sensor reading = 55°F (13°C)
Setting 13 set to +4
Display reading = 59°F (15°C)
RH offset
Setting 14
Press “Settings” button to advance to
Setting 14
Press the “Up” or “Down” buttons to
adjust to the desired setpoint. This setting
allows the adjustment of %RH reading by
+/-10%. Factory default is 0%RH.