33
Fan AUTO or
ON
Setting 7
Press “Settings” button to advance to
Setting 7.
Press the “Up” or “Down” arrow buttons
to adjust number to the desired set point.
Factory default is zero (0).
Zero (0) = Auto–fan only turns on when
there is a call for cooling or heating
One (1) = Fan On–fan remains on
continuously
Compressor
anti-short
cycling
Setting 8
Press “Settings” button to advance to
Setting 8.
Press the “Up” or “Down” arrow buttons
to adjust to the desired time in one-minute
increments. Maximum is 10 minutes,
minimum is 3 minutes. Factory default is 5
minutes.
Compressor anti-short cycling time is the
amount of allowable time between
compressor stop and restart. Rapid
start/stop of compressors can cause
premature failure.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER
THAN FACTORY DEFAULT.
Defrost sensor
enable/disable
Setting 9
Press “Settings” button to advance to
Setting 9.
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint.
1 will equal enabled and a 0 (zero) will
equal disabled.
Defrost cut-in
temperature
Setting 10
Press "Settings" button to advance to
Setting 10.
Press the “Up” or “Down” arrow buttons
to adjust to the desired setpoint. This
setting is adjustable from 25°F to 40°F.
Factory default is 39°F.
There must be at least a 1°F difference
between defrost cut-in and cut-out set
points.