background image

Technical Data WSC 304 01

 

____________________________________________________________________________ 

Smoke control unit - WSC 304 01 

 

Connection values: 

4A version 

 

1)

 

Input 

230V / 50...60Hz -  

100VA 

2)  Output 

24V DC -  

 

 when 4A output current 

      Output 

36V DC 

 

 when no output current 

 

Fuses: 

3) Mains 

 

 

 

630mA 

slow 

blow 

4) Motor 

 

 

 

4A 

slow 

blow 

5) Accumulator 

 

 

630mA 

medium 

slow 

blow 

 

Connection possibilities: 

1)  Motors up to 4A. 
2)  Smoke detectors, up to 10 pieces. 
3)  Break glass units (main), up to 2 per PCB (max. current load of the trigger signal = 120mA). 
4)  Break glass units (secondary), up to 15 per PCB. 
5)  Ventilation buttons with ‘open’ indicator, up to 15, any number without ‘open’ indicator  
 

(max. current load = 120mA). 

6)  Wind/rain detectors with potential free close contact (max. current load of the detector = 250mA). 
7)  ASV CLOSE function at the smoke detector input (insert ASV module). 

 

Setting possibilities via slide switch SW2: 

 

SW 2/1 = ON 

The smoke control system trips by a malfunction signal from the motor, smoke detector or 
break glass unit. 

SW 2/1 = OFF 

The smoke control system does not trip by a malfunction signal. The malfunction signal is 
only displayed by LED‘s. 

 

 

SW 2/2 = ON 

The actuators 

only

 open for as long as the ventilation button is pressed (dead man 

control). 

SW 2/2 = OFF 

The actuators open as long as the ventilation button is pressed (self-hold). 

 

 
MALFUNCTION REMEDY: 

 

Diagnosis / monitoring in the control unit: 

 

LED auf den Platinen 

Funktionen 
in Ordnung 

Störung Diagnose 

Mains (green) 

Lit 

Off 

Check mains voltage and mains fuse 

Operation (green) 

Lit 

Off 

Check all functions 

 

Smoke detector (yellow) 

Off 

Flashes when 

interrupted, is lit after a 

short circuit 

Check wiring and the active end 

module. 

Break glass unit (yellow) 

Off 

Flashes when 

interrupted, is lit after a 

short circuit 

Check wiring and the active end 

module 

Motor circuit (yellow) 

Off 

Flashes when 

interrupted, after approx. 

8 s 

Check motor end module and the motor 

fuse 

Battery/load control 
(yellow) 

Off 

See battery diagnosis 

See battery diagnosis 

Summary of Contents for WSC 304 01

Page 1: ...Commisioning Maintenance www WindowMaster com WindowMaster A S Skelstedet 13 2950 Vedb k Danmark Tel 45 4567 0300 Fax 45 4567 0390 WindowMaster GmbH Zum Bache 4 32549 Bad Oeynhausen Deutschland Tel 49...

Page 2: ...onnection Leave the insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of sm...

Page 3: ...review WSC 304 01 ____________________________________________________________________________ Smoke control unit WSC 304 01 3 Operating Accu Motor Alarm Mains Motor Smoke det SHE switch SHE display...

Page 4: ...reak glass unit are lit The yellow malfunction LED in the break glass unit flashes Resetting a trip caused by high temperature The smoke extraction system can be closed again by pressing the Reset but...

Page 5: ...ter ventilation OPEN or ventilation STOP This function is not operative if the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped...

Page 6: ...must be specially made in the production by using a special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break...

Page 7: ...SW2 SW 2 1 ON The smoke control system trips by a malfunction signal from the motor smoke detector or break glass unit SW 2 1 OFF The smoke control system does not trip by a malfunction signal The ma...

Page 8: ...over contact max load 60V 1A with 3 pole connection terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in c...

Page 9: ...r the installation position Open central control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 3...

Page 10: ...ble network for smoke ventilation systems Cable system ends at the interface junction box for the actuator The flexible heat resistant connection cable of the smoke ventilation system actuator is part...

Page 11: ...Cable plan ____________________________________________________________________________ Smoke control unit WSC 304 01 11...

Page 12: ...Standard wiring diagram __________________________________________________________________________ Smoke control unit WSC 304 01 12 WLA 330 WLA331 WSA 300 WSA 310...

Page 13: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 13...

Page 14: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 14...

Page 15: ...e the protection film from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the w...

Page 16: ...relevant regulations b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c T...

Page 17: ...ystem Check fastening and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install o...

Reviews: