Technical function description WSC 304 01 

____________________________________________________________________________ 

Smoke control unit - WSC 304 01 

Ventilation functions: 

 

Ventilation OPEN: 

With the dead man's circuit activated (SW2/2 = ON), the actuators only move open for as long as the OPEN 
button of the ventilation button is kept pressed. 
If no dead man's function is activated (SW2/2 = OFF), the actuators open after pressing the OPEN button 
(self hold). 

Display:

 The ventilation open LED in the ventilation button is lit (only with LED integrated in the button). 

 

Ventilation stop: 

The actuators stop when both buttons are pressed. 

Display:

 The ventilation open LED in the ventilation button remains lit (only with LED integrated in the button). 

 

Ventilation closed: 

The actuators close after pressing the CLOSED button. 

Display: 

The ventilation open LED in the ventilation button has extinguished (only with LED integrated in the 

button). 
 

Option: Ventilation time module 

Time setting between 1 and 30 min. Once this time has elapsed, the actuators close after ventilation „OPEN“ 
or ventilation „STOP“. This function is not operative if the setting potentiometer is on the right-hand stop. 
 

Wind/rain CLOSE: 

The actuators close when the wind/rain sensor has tripped (potential free contact in the sensor switches). The 
ventilation functions are out of operation as long as a tripped situation is pending. 

 
Option: Transmission of the wind/rain signal 

The trip signal of the wind/rain sensor can be transmitted potential free to the next smoke control unit 
by plugging in the wind/rain relaying module. 
 
 

Note: All ventilation functions are locked in the event of a power failure or when an alarm is triggered! 

 

 
 
General information: 

 

CLOSE after a power failure: 

Opened actuators will automatically close via the ventilation system 5 minutes after a power failure. 
In the event of alarm, this function will be out of operation. 
 

EMC protection: 

All inputs and outputs are protected from coupled in interferences. 
 

Short-circuit protection: 

All outputs are protected against short-circuit and overload. 
 

Maintenance: 

Smoke control systems must be maintained by the builder at least once per year. 
The maintenance and check of the system must be documented in a test placard in the smoke control unit as 
well as in a logbook. 

 

 
 

Summary of Contents for WSC 304 01

Page 1: ...Commisioning Maintenance www WindowMaster com WindowMaster A S Skelstedet 13 2950 Vedb k Danmark Tel 45 4567 0300 Fax 45 4567 0390 WindowMaster GmbH Zum Bache 4 32549 Bad Oeynhausen Deutschland Tel 49...

Page 2: ...onnection Leave the insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of sm...

Page 3: ...review WSC 304 01 ____________________________________________________________________________ Smoke control unit WSC 304 01 3 Operating Accu Motor Alarm Mains Motor Smoke det SHE switch SHE display...

Page 4: ...reak glass unit are lit The yellow malfunction LED in the break glass unit flashes Resetting a trip caused by high temperature The smoke extraction system can be closed again by pressing the Reset but...

Page 5: ...ter ventilation OPEN or ventilation STOP This function is not operative if the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped...

Page 6: ...must be specially made in the production by using a special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break...

Page 7: ...SW2 SW 2 1 ON The smoke control system trips by a malfunction signal from the motor smoke detector or break glass unit SW 2 1 OFF The smoke control system does not trip by a malfunction signal The ma...

Page 8: ...over contact max load 60V 1A with 3 pole connection terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in c...

Page 9: ...r the installation position Open central control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 3...

Page 10: ...ble network for smoke ventilation systems Cable system ends at the interface junction box for the actuator The flexible heat resistant connection cable of the smoke ventilation system actuator is part...

Page 11: ...Cable plan ____________________________________________________________________________ Smoke control unit WSC 304 01 11...

Page 12: ...Standard wiring diagram __________________________________________________________________________ Smoke control unit WSC 304 01 12 WLA 330 WLA331 WSA 300 WSA 310...

Page 13: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 13...

Page 14: ...Various wiring diagrams ____________________________________________________________________________ Smoke control unit WSC 304 01 14...

Page 15: ...e the protection film from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the w...

Page 16: ...relevant regulations b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c T...

Page 17: ...ystem Check fastening and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install o...

Reviews: