background image

15

60706-160/I

MAINTENANCE

CAUTION: EQUIPMENT DAMAGE

Most electrical equipment in North America operates 

satisfactorily at frequencies between 59 and 61 

Hz (cycles per second).Operating the generator at 

frequencies outside that range may cause damage to 

the generator and/or to electrical equipment driven by 

the generator.

GENERAL

Routine preventative maintenance minimizes costly 

repairs and generator downtime. Before each use, 

inspect the generator: gear case oil level should be 

correct, cooling vents and screens should be clear, 

and generator mounting hardware should be tight. 

Clean and inspect the generator after storing it for long 

periods, and after using it in extremely dusty conditions 

or in severe weather, such as rain or blowing snow.

LUBRICATION

The generator bearings are factory lubricated and sealed, 

and require no further lubrication.

The splined generator input shaft should be cleaned and 

lubricated with thin film of grease before and after each 

use of the generator. 

The drive shaft (tumbling bar) requires greasing. Keep 

the universal joints in the coupling shaft free from grease 

and dirt buildup.

NOTE: Do not over lubricate the universal joints.

See illustration below for recommended lubrication 

schedule for the coupling shaft.

Check the generator gear case oil level before each use 

of the generator. Maintain the oil level at oil level plug 

height. The generator is shipped with lubricant in the 

gearcase. Specifications for the gearcase lubricant are:

API Service:  

GL-5

Grade: 

  SAE 

85W-90-140

Amount:    

2.75 Pint

CAUTION: EQUIPMENT DAMAGE

Do not overfill generator gearcase. Overfilling causes 

overheating and oil seal failure.

Change the oil at least once every six months. Change 

it more often if you use the generator in bad weather. 

Use the following procedure to change the generator 

gearcase oil. 

Page 7

60706-160 REV 3

3117-30

5. Shut off the engine.

4. Disconnect drive shaft (tumbling bar) power take-off end
first, then generator end.

MAINTENANCE

The following chart lists various symptoms of poor generator
operation with possible causes for them and the appropriate
corrective action. You will need a volt-ohm meter or test light to
check some of the causes. For some of the other causes you
will need to check generator speed. To check the generator
speed you can use the frequency meter on the generator
control panel.

CAUTION: Equipment Damage

Most electrical equipment in North America operates satisfac-
torily at frequencies between 59 and 61 Hz (cycles per
second.) Operating the generator at frequencies outside that
range may cause damage to the generator and/or to electrical
equipment driven by the generator.

GENERAL

Routine preventive maintenance minimizes costly repairs and
generator downtime. Before each use, inspect the generator:
gear case oil level should be correct, cooling vents and
screens should be clear, and generator mounting hardware
should be tight. Clean and inspect the generator after storing it
for long periods, and after using it in extremely dusty condi-
tions or in severe weather, such as rain or blowing snow.

LUBRICATION

The generator bearings are factory lubricated and sealed, and
require no further lubrication.

The splined generator input shaft should be cleaned and
lubricated with a thin film of grease before and after each use
of the generator.

The drive shaft (tumbling bar) requires greasing. Keep the
universal joints in the coupling shaft free from grease and dirt
buildup.

NOTE:

Do not over lubricate the universal joints.

See Figure 8 for recommended lubrication schedule for the
coupling shaft.

Check the generator gear case oil level before each use of the
generator. Maintain the oil level at oil level plug height. (Figure
6 illustrates oil level plug location.) The generator is shipped
with lubricant in the gear case. Specifications for gear case
lubricant are:

API Service: GL-5
Grade: SAE 85W-9O-140
Amount: 1 pint

The following kinds of oil are recommended for use in the
generator gear case: Mobil SAE 85W90-140 API Service GL-5,
Sunoco/DX XL80W90-140 Kendal Three Star 85W-140,
Amoco 85W140 or equivalent.

CAUTION: Equipment Damage

Do not overfill generator gear case. Overfilling causes over-
heating and oil seal failure.

Change the oil at least once every six months. Change it more
often if you use the generator in bad weather. Use the follow-
ing procedure to change generator gear case oil (see Figure
6):

1. Remove gear case breather. Soak breather in cleaning
solvent, then allow it to dry.

2. Remove oil level check plug.

3. Remove the oil drain plug, drain the oil into a clean oil
resistant container, 1 quart or larger. Check the oil for metal.
Fine metal dust in the oil does not indicate trouble, but metal
chips do. Dismantle the gear case and look for damaged
gears if you find metal chips in the oil.

4. Replace the oil drain plug. Refill the gear case through the
breather port with new oil of the recommended type. Fill the
case up to oil level check plug height. (It will take about 1 pint.)

Figure 8

1. Remove gearcase breather. Soak breather in cleaning 

  solvent, then allow to dry.

2. Remove oil level plug. See illustration below.

3. Remove the oil drain plug, drain the oil into a clean oil 

  resistant container, 1 quart or larger. Check the oil for 

  metal. Fine metal dust in the oil does not indicate 

  trouble, but metal chips do. Dismantle the gearcase 

  and look for damaged gears if you find metal chips in 

  the oil.

4. Replace the oil drain plug. Refill the gearcase through 

  the breather port with new oil of the recommended 

  type. Fill the case up to the oil level check plug height. 

  About 1 pint.

5. Replace the oil level check plug.

6. Replace the breather.

CLEANING & INSPECTING THE 
GENERATOR

Use a vacuum cleaner or dry low pressure compressed 

air (regulated at 25-35PSI) to clean the generator 

periodically.

WARNING: EQUIPMENT DAMAGE

Do NOT clean the generator while it is running.

Proceed as follows:

1. Remove ventilated control box cover. Vacuum or blow 

  vents and screen clear of dust or debris. Wash them 

  down with cleaning solvent if necessary.

2. Remove cooling fan shroud. Vacuum or blow dust 

  from screen and fan blades. Wipe them off with 

  cleaning solvent if necessary. 

3. Vacuum or blow dust and other debris from inside 

  generator and control box.

4. With the panel cover removed, inspect the wiring for 

  correct routing, fraying insulation, and secure 

 connections.

5. Replace panel cover and cooling fan shroud.

Page 6

60706-160 REV 3

3117-30

6. Make sure that the electrical loads to be powered by the
generator will not exceed the current ratings of the generator,
receptacle, or cord set which will supply the current.

7. Check all electrical connections in the system to be
energized by the generator. Make sure the connections are
correct and tight and the load disconnect plug (if provided) is
fully seated in the receptacle.

8. Make sure all loads are turned off. Do not start the generator
under  load.

GENERATOR STARTING PROCEDURE

1.  With the power take-off drive disengaged, start the engine
which will drive the generator. Run the engine long enough to
warm it up before proceeding, so that it will run smoothly and
achieve full power under generator load.

2. With engine idling, engage the power take-off drive.

3. Watch the frequency meter on the generator and slowly
increase  engine  speed  until  the  frequency  reaches  approxi-
mately 60 Hz.  The voltage output of the generator is controlled
by an Automatic Voltage Regulator (AVR).  Before turning on
any load check your voltage output from the generator using a
volt/ohm meter.  If the voltage is either high or low adjust the
voltage level by turning the voltage adjustment screw on the
AVR.  The AVR is located inside the generator control cabinet.
Once the proper voltage level is set the AVR should bring the
voltage back to the same level each time the unit is started up.
But as a precaution it should be checked each time you use
the generator. As quick check you can plug in a troublelight
and  check  for  normal  brightness.

4. With engine and generator running smoothly, switch on the
electrical load while watching the frequency meter.

NOTE: Equipment Damage

If the load includes motors turn them on one at a time, highest
starting current motor first, next highest second, etc.

Adjust engine throttle to keep generator output under load at
60 Hz. If the engine is equipped a with governor, it may
automatically adjust the throttle as the load changes and keep
the generator output at the proper level. However, some
governors are not sensitive enough to maintain proper output
under  changing  loads,  and  in  such  cases  the  frequency  will
have to be monitored closely and manually adjusted .

GENERATOR SHUTDOWN PROCEDURE

1. Switch off electrical load.

2. Reduce speed of engine driving generator to idle.

3. Disengage power take-off drive, and allow generator to
coast to a stop.

WARNING: Personal Injury

Never try to manually stop the generator.  Always let it coast
until it stops.

3. Make sure the drive shaft (tumbling bar) is assembled with
its  universal  joint  knuckles  “synchronized,”  as  illustrated  in
Figure 7. If knuckles are not synchronized, the bar will chatter
when rotating, which will cause the generator output voltage to
flicker.

DANGER: Personal Injury

POWER TAKE-OFF MUST BE DISENGAGED AT THIS TIME.

4. Couple the tractor to the generator with the drive shaft
(tumbling bar). Couple the tumbling bar to the generator input
shaft first, then to the power take-off shaft. Check alignment of
tractor, power take-off shaft (tumbling bar), and generator input
shaft should form a straight (or nearly straight) line, with less
than  15°  misalignment  between  the  shafts.  Misalignment  will,
stress the drive line and  cause generator output voltage to
flicker.

CAUTION:

Make sure that all tumbling bar lock pins are engaged and
that all safety shields are in place before operating the PTO
generator.

5. Make sure no binding exists in generator or gear box. If
binding is found, locate the cause and correct it before
proceeding.

Figure 7

Figure 6

Summary of Contents for W100PTOS-3

Page 1: ...should ever need to contact us concerning this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER ____________________________...

Page 2: ...105PTOS 4 W105PTOS 17 W120PTOS 18 W1065PTOS 18 W145PTOS 4 W145PTOS 17 W150PTOS 3 36 MONTH LIMITED WARRANTY 24 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followe...

Page 3: ...IONS This engine generator set has been designed and manufactured to allow safe reliable performance Poor maintenance improper or careless use can result in potentially deadly hazards from electrical...

Page 4: ...600 Power Factor 1 0 Amps 141 Input Speed 1000 RPM Generator Speed 1800 RPM Input Shaft 1 3 4 20 Spline Required Tractor PTO HP 170 W100PTOS 3 Watts 100 000 Phase Single Voltage 120 240 Power Factor 1...

Page 5: ...ctor PTO HP 290 W150PTOS 3 Watts 150 000 Phase Single Voltage 120 240 Power Factor 1 0 Amps 625 Input Speed 1000 RPM Generator Speed 1800 RPM Input Shaft 1 3 4 20 spline Required Tractor PTO HP 300 W1...

Page 6: ...output power receptacles and overload protection circuit breakers and most models are equipped with a full load disconnect plug not applicable on the 145 and 150 kW models To reduce maintenance probl...

Page 7: ...e is noted it is always easiest to refuse the shipment and let WINCO take care of the freight claim If you sign for the unit the transfer of the ownership requires that you file the freight claim 2 Be...

Page 8: ...as a portable power source When selecting or building a trailer to mount the generator consider the following points Page 3 60706 160REV3 3117 30 WARNING Personal Injury Equipment Damage TRAILER MAY...

Page 9: ...lified electricians should install electric wiring Wringing must conform to all applicable national state and local codes Reference National Fire Protection Association Manual No 70 National Electrica...

Page 10: ...ULD NOT BE PLUGGED INTO ITS RECEPTACLE ALSO MAKE SURE THAT THE EQUIPMENT TO WHICH THE PLUG LEADS CABLES ARE BEING CONNECTED IS NOT ENERGIZED LIVE Strip the insulation off of the free end of each of th...

Page 11: ...trical wiring Manual No 70 National Electrical Code DANGER PERSONALINJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A SPECIAL DISCONNECT SWITCH MUST BE INSTALLED TO SEPARATE THE GENERAT...

Page 12: ...ect your power output leads directly to the mainline circuit breaker To aid in determining how much load can be applied to the generator and how it should be distributed among the generator output rec...

Page 13: ...will cause the generator output volt age to flicker Drive shafts shipped new from Winco are al ways synchronized and tethered so they can not be taken apart DANGER Personal Injury POWER TAKE OFF MUST...

Page 14: ...hould be checked each time you use the generator As a quick check you can plug in a troublelight and check for normal brightness 4 With engine and generator running smoothly switch on the electrical l...

Page 15: ...ure Change the oil at least once every six months Change it more often if you use the generator in bad weather Use the follow ing procedure to change generator gear case oil see Figure 6 1 Remove gear...

Page 16: ...160 I GENERATOR STORAGE Before storing the generator apply a heavy coat of grease to the splined input shaft Store the generator in a sheltered area where it is protected against snow rain and excess...

Page 17: ...than the rated capacity of the generator see generator nameplate 3 Generator requires 2 HP 1000 watt output Obtain larger engine if necessary 4 Repair adjust or replace as required Output voltage fli...

Page 18: ...ONS 120 240 VOLT SINGLEPHASE GENERATOR CONNECTIONS 120 240 VOLT THREEPHASE GENERATOR CONNECTIONS 120 240V SINGLE PHASE 120 240V THREE PHASE GENERATOR CONNECTIONS 120 240 VOLT SINGLEPHASE GENERATOR CON...

Page 19: ...HREE PHASE Page 11 60706 160REV3 GENERATOR CONNECTIONS 120 208 VOLT THREEPHASE GENERATOR CONNECTIONS 277 480 VOLT THREEPHASE Page 11 60706 160REV3 3117 30 GENERATOR CONNECTIONS 120 208 VOLT THREEPHASE...

Page 20: ...20 60706 160 I W75PTOS 4 W75PTOS 17 BACK VIEW GENERATOR RECEPTACLE PANELS W85PTOS 18 BACK VIEW...

Page 21: ...21 60706 160 I W85PTOS 3 W100PTOS 3 BACK VIEW W85PTOS 21 BACK VIEW...

Page 22: ...22 60706 160 I W105PTOS 4 W105PTOS 17 BACK VIEW W120PTOS 18 W1065PTOS 18 BACK VIEW...

Page 23: ...23 60706 160 I W145PTOS 4 W145PTOS 17 W150PTOS 3 BACK VIEW...

Page 24: ...s you may have other rights which vary from state to state Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of inci...

Reviews: