background image

17

60706-160/I

SYMPTOM

CAUSE(S)

CORRECTIVE ACTION

No output voltage

1. Circuit breaker open
2. Defective frequency meter

3. Short circuit in the load

4. Defective receptacles

5. Loose (or broken) wires or
  connections  in control box
6. Defective rotating rectifier
7. Defective AVR
8. Shorted or open rotor

9. Shorted or open stator

1. Reset circuit breakers, replace if defective
2. Check output with another meter, replace meter if 
 defective.
3. Disconnect the load. Check voltage at receptacle cord 
  set. Check motors, appliances, and load leads for short 
  circuit. Repair short.
4. Remove panel cover and check for voltage to the 
  receptacles. Replace defective receptacles.
5. Remove panel cover and check all wiring and 
  connections. Tighten and/or repair where necessary.
6. Test rectifier. Replace if defective.
7. Repair or replace as required.
8. Measure rotor resistance. Replace rotor if open or 
 shorted.
9. Measure between leads for open r short. Replaces 
  stator if defective.

High voltage

1. Defective or misadjusted AVR

1. Adjust, repair, or replace as required

Low voltage

1. Engine speed too low
2. Generator overloaded

3. Inadequate engine horsepower.

4. Defective or misadjusted AVR

1. Check engine speed. Increase RPM if necessary.
2. Reduce load if it is higher than the rated capacity of 
  the generator. (see generator nameplate)
3. Generator requires 2 HP/1000 watt output. Obtain 
  larger engine if necessary.
4. Repair, adjust, or replace as required.

Output voltage 
flickering or 
fluctuation

1. Tumbling bar (shaft) misalignment

2. Engine governor may be worn or 
  improperly adjusted. Set or repair 
  defective governor.
3. Loose connection in field circuit
4. Tumbling bar U-Joints not 
 synchronized

1. Reduce tumbling bar misalignment to less than 15 
 degrees
2. Engine governor may be worn or improperly 
  adjusted. Set or repair defective governor.

3. Check and tighten connections.
4. Reassemble tumbling bar.

Excessive vibration

1. Power take-off misalignment 
 excessive
2. Loose mounting nuts and bolts or 
  hold down studs
3. Universal joints in coupling shaft 
  worn or dry.
4. Defective bearings

1. Correct misalignment. It should be less than 15 
 degrees.
2. Tighten mounting buts and bolts; repair hold down 
  stud mountings.
3. Repair or replace defective parts.

4. Check for possible causes. Replace defective bearings.

Generator 
overheating

1. Poor ventilation
2. Generator overloaded
3. Shorted turns in field or stator 
 windings.

1. Clean ventilation and cooling fan screens.
2. Reduce load, then check voltage and current.
3. Replace defective components.

Oil Leak

1. Loose plug in gearcase
2. Defective seal, gasket, or plug in 
 geargase

1. Tighten plug.
2. Replace seal(s), gaskets or plugs. Maintain correct oil 
 level. 

TROUBLE SHOOTING TABLES

Summary of Contents for W100PTOS-3

Page 1: ...should ever need to contact us concerning this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER ____________________________...

Page 2: ...105PTOS 4 W105PTOS 17 W120PTOS 18 W1065PTOS 18 W145PTOS 4 W145PTOS 17 W150PTOS 3 36 MONTH LIMITED WARRANTY 24 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followe...

Page 3: ...IONS This engine generator set has been designed and manufactured to allow safe reliable performance Poor maintenance improper or careless use can result in potentially deadly hazards from electrical...

Page 4: ...600 Power Factor 1 0 Amps 141 Input Speed 1000 RPM Generator Speed 1800 RPM Input Shaft 1 3 4 20 Spline Required Tractor PTO HP 170 W100PTOS 3 Watts 100 000 Phase Single Voltage 120 240 Power Factor 1...

Page 5: ...ctor PTO HP 290 W150PTOS 3 Watts 150 000 Phase Single Voltage 120 240 Power Factor 1 0 Amps 625 Input Speed 1000 RPM Generator Speed 1800 RPM Input Shaft 1 3 4 20 spline Required Tractor PTO HP 300 W1...

Page 6: ...output power receptacles and overload protection circuit breakers and most models are equipped with a full load disconnect plug not applicable on the 145 and 150 kW models To reduce maintenance probl...

Page 7: ...e is noted it is always easiest to refuse the shipment and let WINCO take care of the freight claim If you sign for the unit the transfer of the ownership requires that you file the freight claim 2 Be...

Page 8: ...as a portable power source When selecting or building a trailer to mount the generator consider the following points Page 3 60706 160REV3 3117 30 WARNING Personal Injury Equipment Damage TRAILER MAY...

Page 9: ...lified electricians should install electric wiring Wringing must conform to all applicable national state and local codes Reference National Fire Protection Association Manual No 70 National Electrica...

Page 10: ...ULD NOT BE PLUGGED INTO ITS RECEPTACLE ALSO MAKE SURE THAT THE EQUIPMENT TO WHICH THE PLUG LEADS CABLES ARE BEING CONNECTED IS NOT ENERGIZED LIVE Strip the insulation off of the free end of each of th...

Page 11: ...trical wiring Manual No 70 National Electrical Code DANGER PERSONALINJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A SPECIAL DISCONNECT SWITCH MUST BE INSTALLED TO SEPARATE THE GENERAT...

Page 12: ...ect your power output leads directly to the mainline circuit breaker To aid in determining how much load can be applied to the generator and how it should be distributed among the generator output rec...

Page 13: ...will cause the generator output volt age to flicker Drive shafts shipped new from Winco are al ways synchronized and tethered so they can not be taken apart DANGER Personal Injury POWER TAKE OFF MUST...

Page 14: ...hould be checked each time you use the generator As a quick check you can plug in a troublelight and check for normal brightness 4 With engine and generator running smoothly switch on the electrical l...

Page 15: ...ure Change the oil at least once every six months Change it more often if you use the generator in bad weather Use the follow ing procedure to change generator gear case oil see Figure 6 1 Remove gear...

Page 16: ...160 I GENERATOR STORAGE Before storing the generator apply a heavy coat of grease to the splined input shaft Store the generator in a sheltered area where it is protected against snow rain and excess...

Page 17: ...than the rated capacity of the generator see generator nameplate 3 Generator requires 2 HP 1000 watt output Obtain larger engine if necessary 4 Repair adjust or replace as required Output voltage fli...

Page 18: ...ONS 120 240 VOLT SINGLEPHASE GENERATOR CONNECTIONS 120 240 VOLT THREEPHASE GENERATOR CONNECTIONS 120 240V SINGLE PHASE 120 240V THREE PHASE GENERATOR CONNECTIONS 120 240 VOLT SINGLEPHASE GENERATOR CON...

Page 19: ...HREE PHASE Page 11 60706 160REV3 GENERATOR CONNECTIONS 120 208 VOLT THREEPHASE GENERATOR CONNECTIONS 277 480 VOLT THREEPHASE Page 11 60706 160REV3 3117 30 GENERATOR CONNECTIONS 120 208 VOLT THREEPHASE...

Page 20: ...20 60706 160 I W75PTOS 4 W75PTOS 17 BACK VIEW GENERATOR RECEPTACLE PANELS W85PTOS 18 BACK VIEW...

Page 21: ...21 60706 160 I W85PTOS 3 W100PTOS 3 BACK VIEW W85PTOS 21 BACK VIEW...

Page 22: ...22 60706 160 I W105PTOS 4 W105PTOS 17 BACK VIEW W120PTOS 18 W1065PTOS 18 BACK VIEW...

Page 23: ...23 60706 160 I W145PTOS 4 W145PTOS 17 W150PTOS 3 BACK VIEW...

Page 24: ...s you may have other rights which vary from state to state Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of inci...

Reviews: