14

OPM-117/B

INITIAL START UP

WARNING: EQUIPMENT DAMAGE:

Before attempting  to start this unit, complete your pre-start 

checklist and ensure the generator mainline circuit breaker 

is in the proper position prior to starting. Starting this unit 

without it properly connected can cause serious personal 

injury or equipment damage.

DO NOT jump start these engine-generator sets. Starting 

these units on a low battery or jump starting them will 

cause damage to the engine control module. 

Use the following check list to verify correct installation 

before starting the engine.

 

 Engine oil. Fill as required with proper grade/qty.

 

 Engine coolant. Fill as required with proper mixture.

 

 Unit mounting base properly bolted down.

 

 Clearance for service and maintenance on all sides.

 

 Proper fuel line material and size.

 

 All fuel line connections tight.

 

 Battery connections clean and tight

 

 Battery fully charged.

 

 All AC and DC wiring installed and properly 

   protected.

 

 Compressor oil. Fill as required with proper grade/

   qty.

After completing the previous checklist, the engine-

generator set is ready for initial start-up. 

MANUAL MODE

1. Press and release the MANUAL MODE button. The small 

LED light 

next to it should come on. 

Note: There is no start delay in this mode of operation.

2. Press and release the green START ENGINE button. The 

DSE 7310 MKII will send two signals to the engine. The first 

signal wire #21 will engage the fuel solenoid, the second 

wire, #22, will engage the starter on the engine. At this 

point the DSE7310 will start the cranking cycle (10 seconds 

on and 10 seconds off).

Note: Wire #93 is energized to turn on the glow plugs for 

15 seconds first and then the starter and fuel solenoid are 

engaged.

If the engine fails to start during this cranking period, the 

starter motor is disengaged and goes into a rest mode after 

which a second attempt is made to start the engine. Should 

this sequence continue through 3 cranking cycles the start 

sequence will be stopped and the display will show ‘FAILED 

TO START”. 

3. During manual operation, the load will not normally be 

applied to the generator. But caution must be used, if the 

line power should fail or be turned off the transfer switch 

during manual operation the load may be applied to the 

generator.

With the engine running smoothly check the no load 

voltage and frequency on the digital display. The voltage 

should be 208/240/480 AC depending on which model 

you have and a frequency of 59.5 to 60.5 hertz (Hz). 

If you have the proper voltage at the generator the next 

step is to check the voltage at the generator terminals in 

the Automatic Transfer Switch. The voltage between the 

G1 and the G3 terminals should be the same as it was 

on the generator front panel. The voltage should also be 

checked between the hot terminals (G1 and G3) and the 

G-N to be certain of a balanced voltage output and a solid 

neutral connection. The voltage between G1 and G-N 

should be about 120 volts AC (277 on 480 units). The same 

approximate voltage should be found between terminals 

G3 and G-N (120 volts AC).

On three phase panels the G2 voltage level should also be 

checked. ON 240 VOLT (DELTA) SYSTEMS BE SURE YOU 

KNOW WHERE THE HIGH VOLTAGE “WILD” LEG IS. IT 

MUST BE IN THE SAME LOCATION ON THE LINE SIDE AS IT 

IS ON THE GENERATOR SIDE. 

(i.e. if it’s on L-3 on the line side it must be on G-3 on the 

generator side. Also on three phase systems make sure that 

the rotation is the same on the generator as it is on your 

line power. Failure to insure proper rotation will cause three 

phase motors to spin backwards possibly damaging them.

NOTICE:

If for any reason during the check out procedure the 

voltage and frequency are not correct, depress the STOP/

RESET button and correct the trouble before proceeding.

4. Stopping - There are two ways to stop the unit when it is 

in the manual mode. Pressing the STOP/RESET button will 

stop the unit immediately. Pressing the AUTO mode button 

will stop the unit but only after the cool down timers have 

timed out and there is no remote start signal being sent to 

the unit.

AUTO MODE

To activate the automatic start mode you will just need to 

depress the AUTO button, the LED indicator beside the 

button confirms that the unit is in automatic mode.

To test the Automatic Transfer Switch, follow the instruction 

on the operator’s manual that came with the transfer 

switch. If you get a fault during the initial start up or prior 

to start up, it is most likely a false warning light. Simply reset 

the ATS start over.

Once you have completed testing of the ATS, be sure you 

ALWAYS leave the system in the standby mode,unless 

servicing the unit. For standby operation, press the AUTO 

button on the front of the control. The green light should 

light up next to the AUTO button.

NOTE: For setting the exerciser circuit, for all ATS, see the 

operator’s manual shipped with the ATS. 

Summary of Contents for PSS60-17

Page 1: ...d to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE D...

Page 2: ...FUEL PRESSURE TABLES NG LP FUEL CONVERSION INSTALLING THE BATTERY 9 SERVICING BATTERIES BATTERY CHARGING CONNECTING THE BATTERY CHARGER BLOCK HEATER AC ELECTRICAL CONNECTIONS 11 DC ELECTRICAL INTERCON...

Page 3: ...that you carefully read and follow the operating instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in...

Page 4: ...h 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not s...

Page 5: ...Ohms Per Ph 20 C Exciter Stator L L 20 00 Ohms 20 C Aux Winding 2 6 Ohms 20 C Voltage Regulator L L AS440 PSS90 E LP Gas Wattage 80 000 80 000 80 000 80 000 Volts 120 240 120 208 120 240 277 480 kvA...

Page 6: ...tes at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The generator is a single bearing direct drive rotating field des...

Page 7: ...t recommended for the PSS60 DO NOT use street ells restrictive INSTALLATION WARNING Before proceeding with installation be sure the operation selector switch is in the stop position and the battery di...

Page 8: ...lve and has a drop tube inside the tank that is pulling fuel from the bottom of the supply tank Before starting the unit you must confirm that you have a good liquid supply at the unit Engine generato...

Page 9: ...de of oil as recommended by the engine manufacturer s maintenance instructions The necessity of using the correct oil and keeping the crankcase full cannot be over emphasized Failure to do so will cau...

Page 10: ...e generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharge...

Page 11: ...e maximum load current without excessive voltage drop By code the wire must be heavy enough to handle the full current rating of the mainline circuit breaker or fuse in the entrance or sub panel prote...

Page 12: ...ring of the Automatic Transfer Switch Because of the many different types of service feeder and distribution equipment no specific wiring instructions can be provided It is recommended that only coppe...

Page 13: ...comes to a standstill Should a remote start signal be present while operating in this mode a remote start WILL NOT occur MANUAL MODE This button places the module into its Manual Mode Once in Manual...

Page 14: ...cy on the digital display The voltage should be 208 240 480 AC depending on which model you have and a frequency of 59 5 to 60 5 hertz Hz If you have the proper voltage at the generator the next step...

Page 15: ...NG When performing any type of maintenance on this equipment make sure the selector switch on the engine generator is in the off position If you are working in the Automatic Transfer Switch confirm wi...

Page 16: ...st hold 12 Volts during cranking 2 Blown fuse on generator control panel 3 Loose or dirty battery terminals 4 Defective engine control module 5 Defective starter 6 Defective start solenoid 7 Locked up...

Page 17: ...HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING...

Page 18: ...B ENGINE HARNESS SCHEMATIC 6 1 6 1 1 3 6 237 21 2 22 17 6 1625 3 8 3 8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 5 9 51 3 5 0 0 7 6 5 1 217 16 35235 7 5 1 250 7 21 21 1 72 1 2 81 87 25 86 6 352...

Page 19: ...1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 803 5...

Page 20: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Reviews: