Winco HPS12000HE/F Installation And Operator'S Manual Download Page 7

7

3240

60706-236

The fuel line used to connect the supply line to the 

demand regulator must be a locally approved flexible 

fuel line.  Products used will vary in different regions 

depending on availability and local codes.  Consult 

with your local fuel supplier to ensure complete com-

pliance with ALL codes. 

1.   Remove the plastic cover plug from the demand 

regulator.

2.   Connect the flex fuel line to the demand regulator  

or the optional fuel solenoid..

DANGER: PERSONAL INJURY 

    

Do not use galvanized pipe in the fuel line runs. 

The galvanized coating will become eroded and 

flake off, causing possible obstruction or damage 

to the regulator or fuel valve. The obstruction could 

cause  an inoperative engine or an explosive fuel 

leak.

Size of pipe required for generators operating on 

natural gas/LP gas.

 

Length of Fuel Line*    Fuel Line Size

 

  less than 25 feet 

 3/4 inch black pipe

 

  25 to 100 feet 

 1 inch black pipe

 

  over 100 feet 

 not  recommended**

*allow an additional 3 feet for each standard elbow.  

Do not use ‘street ells’ (restrictive)

** Consult factory for fuel runs over 100 feet.

DANGER! - FIRE - PERSONAL INJURY -

    Be careful when sealing gas joints. Excessive 

sealing compound can be drawn into the solenoid, 

regulator or carburetor causing an engine malfunc-

tion or dangerous fuel leak

.

 

FUEL CONSUMPTION (Full Load) 

 

  Gasoline 

1.67 Gal/HR 

  LP Vapor 

2.2 Gal/HR  

200,932 BTU/HR

  Natural Gas 

200 cu ft/hr 

200,000 BTU/HR

 

 

FUEL PRESSURE

Correct fuel pressure cannot be stressed enough.  

The most common cause for inoperative systems is 

an inadequate or incorrect fuel pressure.  Power and 

performance of the engine is in direct relation to the 

correctness of the fuel system.  Shown below is a 

diagram of a typical L.P. or N.G. installation.  

Reference numbers 1 through 3 in the diagrams 

above are system parts supplied by customer.

Reference number 4 is the engine generator set.

Below is a table of the fuel pressure reading at each 

reference in the system.

Fuel Pressure Table

Single Regulator (L.P. Vapor only) 

1

3

4

UNIT OFF

TANKPSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI 

7-11 in

7-11 in

  

4-6 oz

4-6 oz

FULL LOAD

TANK PSI

7-11 in

7-11 in

 

4-6 oz

4-6 oz

Two (2) Regulator System (L.P. Vapor only) 

1

2

3

4

UNIT OFF

TANK PSI 10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz 

STARTING

TANK PSI 10-15 lbs 

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI 10-15 lbs 

7-11 in 

7-11 in

4-6 oz  

4-6 oz

FULL LOAD

TANK PSI   10-15 lbs 

7-11 in 

7-11 in

4-6 oz

4-6 oz

Summary of Contents for HPS12000HE/F

Page 1: ...INSTALLATION AND OPERATORS MANUAL TRI FUEL GENERATOR HPS12000HE F...

Page 2: ...k Sizing for LP 8 Changing Fuel Types 8 Battery Installation 9 INITIAL START UP 10 Electric Starting for Gasoline 10 Electric Starting for LP NG 11 Stopping Storage 11 Operating Speed 11 CONNECTING TH...

Page 3: ...en c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel only...

Page 4: ...OTE There are 3rd party companies making enclosures for generators that have been properly engineered The use of these 3rd party enclosures is acceptable as long as they have been certified and meet c...

Page 5: ...e on a level surface before you check or add oil to the system The necessity of using the correct oil and keeping the crankcase full cannot be overemphasized En gine failures resulting from inadequate...

Page 6: ...the inlet of the fuel demand regulator on the unit using a locally approved flexible fuel line see table for recommended line size The pressure supplied to the demand regulator must be FOUR TO SIX OUN...

Page 7: ...ts Excessive sealing compound can be drawn into the solenoid regulator or carburetor causing an engine malfunc tion or dangerous fuel leak FUEL CONSUMPTION Full Load Gasoline 1 67 Gal HR LP Vapor 2 2...

Page 8: ...S These engine generator sets are designed to run on three different fuels gasoline natural gas or LP vapor They may be easily changed from one fuel to another FROM GASOLINE TO LP NG 1 With the engine...

Page 9: ...ing the battery in an enclosed space Lead acid batteries contain sulfuric acid which causes severe burns If acid contacts eyes skin or clothing flush well with water For con tact with eyes get immedia...

Page 10: ...the engine switch to the START position and hold it there until the engine starts If the engine fails to start within 5 seconds release the engine switch and wait at least 10 seconds before operating...

Page 11: ...o could result in damage to equipment plugged into the unit and possible injury to the individual ENGLISH STOPPING THE ENGINE M MI IN N M MI IN N START ENGINE SWITCH START ENGINE SWITCH THROTTLE LEVER...

Page 12: ...rator and any load connected to it Running the engine at ex cessively high speeds results in high voltage which may significantly shorten the life of appliances being used Output voltage should be che...

Page 13: ...olt portable appliances and tools to be plugged directly into them Please note that the 4 wire 240 volt receptacle on these units are designed to power both 120 or 240 volt loads The plug for this rec...

Page 14: ...nce problems that result from using a fuel with percentages of ethanol or methanol greater than shown above are not covered under the Warranty If your equipment will be used on an infrequent or interm...

Page 15: ...occur if spark plug wire does not fit firmly on spark plug If this happens reform the ter minal to fit firmly on spark plug tip 5 Carbon Canister Designed to collect store and dispose of fuel vapors...

Page 16: ...ken or loose wire Defective receptacle No residual magnetism in generator Defective stator Defective rotor field Shorted capacitor Shorted diodes on rotor GFCI Receptacle tripped GENERATOR SPECIFICATI...

Page 17: ...17 3240 60706 236 CONTROL PANEL WIRING DIAGRAM...

Page 18: ...arest WINCO Authorized Service Center or to WINCO Inc at Le Center Minnesota THERE IS NO OTHER EXPRESS WARRANTY To the extent permitted by law any and all warranties including those of merchantability...

Page 19: ...ER S WARRANTY COVERAGE The evaporative emission control system is warranted for two years If any evaporative emission related parts on your equipment are defective the parts will be repaired or replac...

Page 20: ...2240 00 20 60706 236 WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com...

Reviews: