Winco HPS12000HE/F Installation And Operator'S Manual Download Page 6

2240-00

6

60706-236

GASOLINE

When using gasoline, always use fresh, clean, 

unleaded fuel.  This engine is certified to operate on 

unleaded gasoline with a minimum octane rating of 

87 or higher.  Gasoline containing no more than 10% 

ethanol is acceptable.  

 

CAUTION:  EQUIPMENT DAMAGE 

 

Do not use unapproved gasolines, such as E15 or 

E85.  

Do not mix oil

 in the gasoline.  Use of unap-

proved fuels will damage the engine components and 

void the engine warranty.

 

 

Use of fuels with content of ethanol greater than 

shown above may cause starting and/or performance 

problems.  Always ensure that the fuel is clean and 

free of all impurities.

WARNING:  FIRE DANGER

    

Gasoline and its fumes are VERY explosive when 

proper precautions are not taken.

Never use gasoline that has been stored for an ex-

tended period of time as the fuel will lose its volatile 

properties and you will be left with varnish residue.  

The varnish like substance will clog the carburetor 

and will not burn properly. 

 

The use of fuel additives, such as STA-BIL, or an 

equivalent will minimize the formation of fuel gum 

deposits.  If a unit has been out of operation for an 

extended period of time, it is best to drain old fuel 

from the engine and replace with fresh fuel before 

attempting to start. 

 

See the engine manual for special instruction for 

operating this unit at over 5000 feet 

 

LP/NG FUEL INSTALLATION

The information in this instruction is offered to assist 

you in providing the proper vapor fuel supply for your 

engine.  This information is only provided to advise 

you of the engine’s requirements and the decisions 

you must make. In no case should this information be 

interpreted to conflict with any local, state or national 

code.  If in doubt, always follow local codes.

DANGER: FIRE - PERSONAL INJURY - 

    All fuel lines must be installed by a qualified fuel  

supplier

.

The fuel source should be as close as possible to 

the outdoor operating location.  This will reduce the 

installation cost of fuel runs.  Connect the fuel supply 

line to the inlet of the fuel demand regulator on the 

unit using a locally approved flexible fuel line (see 

table for recommended line size).  

The pressure 

supplied to the demand regulator must be  FOUR 

TO SIX OUNCES or 7 to 11 INCHES W.C. (water 

column).

 The primary regulator at the fuel supply 

must be capable of delivering the proper volume of 

fuel at this pressure.  

Have your local fuel supplier install a protected fuel 

connection at the outside operating location.  They 

should also install a lockable fuel shut off valve at the 

connection point. An approved flexible fuel line must 

be installed between the engine generator set and 

the supply line.

DANGER: FIRE - PERSONAL INJURY - 

    The LP/NG fuel supply line must always be shut off 

when the engine is not running.  Failure to do so may 

allow fuel to leak at the unit.

 

INSTALLING THE FUEL LINE

DANGER:  PERSONAL INJURY 

    Units that are intended to be run unattended 

MUST

   have an electric fuel solenoid installed. This 

solenoid MUST be wired to AUTOMATICALLY turn off 

the fuel  whenever the engine stops.

 

Unit location will determine the size of fuel line that 

is required to supply the engine with a constant fuel 

pressure.  Refer to the tables below for fuel line size, 

and recommended tank size.  For distances of 100 

feet and over, a two regulator fuel system is recom-

mended. This system consisting of a primary 10-15# 

regulator at the tank and a 6 ounce secondary regula-

tor installed about 10 feet from the generator. You 

need to run a 3/4 inch line or larger from the second-

ary regulator to the engine-generator set.  When a 

two (2) regulator fuel system is used, a fuel line size 

of 3/8 inch is generally adequate for distances up to 

300 feet.  The line size from the table below applies 

to the distance from the second regulator to the 

demand regulator.  

A positive fuel shut-off device 

must be installed in the fuel line close to the 

engine generator set.  

This manual shut-off valve is 

require by code even if the 12 volt fuel solenoid kit is 

installed. This optional 12 volt DC valve is available 

through your local Winco dealer and can be used to 

shut the fuel off during normal periods of operation 

with-out having to shut off the manual valve.

Summary of Contents for HPS12000HE/F

Page 1: ...INSTALLATION AND OPERATORS MANUAL TRI FUEL GENERATOR HPS12000HE F...

Page 2: ...k Sizing for LP 8 Changing Fuel Types 8 Battery Installation 9 INITIAL START UP 10 Electric Starting for Gasoline 10 Electric Starting for LP NG 11 Stopping Storage 11 Operating Speed 11 CONNECTING TH...

Page 3: ...en c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel only...

Page 4: ...OTE There are 3rd party companies making enclosures for generators that have been properly engineered The use of these 3rd party enclosures is acceptable as long as they have been certified and meet c...

Page 5: ...e on a level surface before you check or add oil to the system The necessity of using the correct oil and keeping the crankcase full cannot be overemphasized En gine failures resulting from inadequate...

Page 6: ...the inlet of the fuel demand regulator on the unit using a locally approved flexible fuel line see table for recommended line size The pressure supplied to the demand regulator must be FOUR TO SIX OUN...

Page 7: ...ts Excessive sealing compound can be drawn into the solenoid regulator or carburetor causing an engine malfunc tion or dangerous fuel leak FUEL CONSUMPTION Full Load Gasoline 1 67 Gal HR LP Vapor 2 2...

Page 8: ...S These engine generator sets are designed to run on three different fuels gasoline natural gas or LP vapor They may be easily changed from one fuel to another FROM GASOLINE TO LP NG 1 With the engine...

Page 9: ...ing the battery in an enclosed space Lead acid batteries contain sulfuric acid which causes severe burns If acid contacts eyes skin or clothing flush well with water For con tact with eyes get immedia...

Page 10: ...the engine switch to the START position and hold it there until the engine starts If the engine fails to start within 5 seconds release the engine switch and wait at least 10 seconds before operating...

Page 11: ...o could result in damage to equipment plugged into the unit and possible injury to the individual ENGLISH STOPPING THE ENGINE M MI IN N M MI IN N START ENGINE SWITCH START ENGINE SWITCH THROTTLE LEVER...

Page 12: ...rator and any load connected to it Running the engine at ex cessively high speeds results in high voltage which may significantly shorten the life of appliances being used Output voltage should be che...

Page 13: ...olt portable appliances and tools to be plugged directly into them Please note that the 4 wire 240 volt receptacle on these units are designed to power both 120 or 240 volt loads The plug for this rec...

Page 14: ...nce problems that result from using a fuel with percentages of ethanol or methanol greater than shown above are not covered under the Warranty If your equipment will be used on an infrequent or interm...

Page 15: ...occur if spark plug wire does not fit firmly on spark plug If this happens reform the ter minal to fit firmly on spark plug tip 5 Carbon Canister Designed to collect store and dispose of fuel vapors...

Page 16: ...ken or loose wire Defective receptacle No residual magnetism in generator Defective stator Defective rotor field Shorted capacitor Shorted diodes on rotor GFCI Receptacle tripped GENERATOR SPECIFICATI...

Page 17: ...17 3240 60706 236 CONTROL PANEL WIRING DIAGRAM...

Page 18: ...arest WINCO Authorized Service Center or to WINCO Inc at Le Center Minnesota THERE IS NO OTHER EXPRESS WARRANTY To the extent permitted by law any and all warranties including those of merchantability...

Page 19: ...ER S WARRANTY COVERAGE The evaporative emission control system is warranted for two years If any evaporative emission related parts on your equipment are defective the parts will be repaired or replac...

Page 20: ...2240 00 20 60706 236 WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com...

Reviews: