background image

18

OPM-125/D

GENERATOR CARE

Proper care and maintenance of the generator is necessary 

to ensure a long trouble free life.

EXERCISING THE GENERATOR

The generator should be operated every three to four 

weeks. It should be operated for a period of time sufficient 

to warm the unit up and to dry out any moisture that has 

accumulated in the windings. If left, this moisture can cause 

corrosion in the winding. Frequent operation of the engine-

generator set will also ensure that the set is operating 

properly should it be needed in an emergency.

GENERATOR MAINTENANCE

Any major generator service, including the installation 

or replacement of parts, should be performed only by a 

qualified electrical service technician. 

USE ONLY FACTORY 

APPROVED REPAIR PARTS.

  A. Bearing - The bearing used in these generators is a 

    heavy duty, double sealed ball bearing. They require 

    no maintenance or lubrication.

  B. Receptacles - Quality receptacles have been utilized. If a 

    receptacle should become cracked or otherwise 

    damaged, replace it. Using damaged or cracked 

    receptacles can be both dangerous to the operator 

    and destructive to the equipment.

CLEANING

Remove dirt and debris with a cloth or brush. DO NOT 

use high pressure spray to clean either the engine or the 

generator. The high pressure spray could contaminate the 

fuel system and the generator components.

1. Keep the air inlet screen on both the engine and 

generator free of any dirt or debris to ensure proper 

cooling. At least yearly, remove the blower housing on 

the engine and clean the chaff and dirt out of the engine 

cooling fins and fly wheel. Clean more often if necessary. 

Failure to keep these areas clean may cause overheating 

and permanent damage to the unit.

2. Periodically clean muffler area to remove all grass, dirt, 

and combustible debris to prevent a fire.

3. On engine mufflers equipped with spark arresters, the 

spark arrester must be removed every 50 hours for cleaning 

and inspection. Replace if damaged.

TROUBLESHOOTING

Problem

Possible Causes

Won’t start

Low oil level
Out of fuel
Start switch in OFF position
Fuel Valve turned off
Plugged fuel filter
Blown fuse in key switch
Battery required to open solenoid

Voltage too low

Engine speed is too low
Generator overloaded
Defective stator
Defective rotor (field)
Defective AVR

Circuit breaker trips

Defective load
Defective receptacle
Excessive load
GFCI type of load i.e. a building with 
  bonded neutral

Voltage too high

Engine speed is too high

Generator overheating

Overloaded
Insufficient ventilation

No output voltage

Short in load (disconnect)
Tripped or defective circuit breaker
Broken or loose wire
Defective receptacle
No residual magnetism (in 
generator)
Defective stator
Defective rotor (field)
Shorted capacitor
Shorted diodes on rotor
GFCI receptacle tripped

Will not shutdown

Fuel solenoid valve lever is in up 
position

Summary of Contents for EC6010DR/T

Page 1: ...ould ever need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _______________________________________...

Page 2: ...CLEANING TROUBLESHOOTING 18 CONTROL PANEL WIRING DIAGRAM 19 CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed...

Page 3: ...sent a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or use open flame near the generator se...

Page 4: ...store the unit outside during inclement weather without adequate protection from the elements Failure to do so will damage the unit DO NOT remove from the cradle assembly Removal of the generator fro...

Page 5: ...ceptacles attached to either A or B output legs This generator is capable of producing 21 5 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage to insure c...

Page 6: ...to refuse the shipment and let WINCO take care of the freight claim If you sign for the unit the transfer of the ownership requires that you file the freight claim 2 Before proceeding with the prepara...

Page 7: ...e hydrogen gas when charging Keep sparks flames and burning cigarettes away from the battery Ventilate the area when charging or using the battery in an enclosed space Lead acid batteries contain sulf...

Page 8: ...battery with water use only distilled water Tap water will shorten the service life of the battery Never fill the battery above the fill line Overfilling above the upper level line may cause the elec...

Page 9: ...reen wire connects to the skid base There may already be a ground wire screwed down add the green wire and re secure the screw The black longer wire will connect to the front of the engine Attach blac...

Page 10: ...Preferred fuel installations use 1 4 hose that run straight to the engine with no drops or twists from an adequately sized fuel tank Connect a 1 4 fuel hose to the hose fitting located on the fuel pum...

Page 11: ...nd dry area 0 INITIAL START UP The throttle control on these generators is preset and locked to operate at 3600 RPM nominal with no load speed set at 3690 RPM Only a trained service technician should...

Page 12: ...system When connecting it to a building a transfer switch specifically designed for GFCI and bonded neutral generators is required CONNECTING THE LOADS The engine generator covered in this manual was...

Page 13: ...set is connected to an existing distribution system a fully isolated manual transfer switch must be installed The transfer switch prevents damage to the generator and the other circuit components if...

Page 14: ...5 25 50 50 75 75 100 YOURGEN The WINCO YourGen meter allows you to see useful information about your generator from the front panel by displaying RPMs Voltage frequency load hours and maintenance remi...

Page 15: ...This generator is capable of producing 21 5 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage to insure compatibility Remember that power taken from C r...

Page 16: ...with the air filter removed A Remove the cover ENGINE CARE MAINTENANCE SCHEDULE Daily or Every 10 hrs Every 250 hrs Every 500 hrs Check Oil Check oil filter Check dry air cleaner Fuel tank cleaning C...

Page 17: ...is excessively dirty replace with a new filter You can use pressurized air not to exceed 30 psi to clean the filter Always blow the compressed air from inside to the outside F Clean the dirt from the...

Page 18: ...generator components 1 Keep the air inlet screen on both the engine and generator free of any dirt or debris to ensure proper cooling At least yearly remove the blower housing on the engine and clean...

Page 19: ...19 OPM 125 D CONTROL PANEL WIRING DIAGRAM G1 G1 G1 G2 G N N G G G2 G2...

Page 20: ...uest THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED OR OTHERWISE CREATED INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILIT...

Reviews: