Winco DR20I4-/1 Series Installation And Operator'S Manual Download Page 8

8

OPM-135/C

E: 120V/20 AMP DUPLEX RECEPTACLE:

This convenience receptacle is used to power both battery 

charger and block heater. This circuit must be fed from a 

GFCI fused circuit in the distribution panel.

F: NEUTRAL TO GROUND LEAD LUG:

This lug is provided on the neutral terminal block to allow 

you to run a neutral to ground lead if you are using the 

generator in a stand alone application. This would be an 

application where there is not a distribution panel and 

no other ground to neutral bond in the wiring system. If 

a grounding wire is attached here, remove the floating 

neutral label in the panel. This will not be used when you 

are wiring a generator and transfer switch into an existing 

power system.

WARNING:

A mainline circuit breaker has been provided inside the 

generator housing. During all wiring installations, make 

sure the breaker is in the OFF position and the generator 

operating switch is in the OFF position.

WARNING: EQUIPMENT DAMAGE:

When installing a three-phase 240 Volt system, be sure you 

know which lead is the high voltage “wild” leg (208 Volt 

line to neutral). The generator normally carries the high 

voltage on the G2 lead.

All wires should be installed in rigid or flexible conduit 

(knockouts are provided in the control box).

GROUNDING

A grounding lug has been provided on the engine 

generator set and the generator set must be properly 

grounded to good earth ground. Generally an 8 foot 

copper rod driven into the earth will provide a proper earth 

ground.

D.C. ELECTRICAL CONNECTIONS

All DC connections are completed on the terminal strip 

just below the engine control. All DC connection must be 

separate conduit. You cannot mix AC and DC leads at the 

same conduit.

CONNECTION BOX TERMINALS

To install the wires, reference the following picture. Use a 

small flat head screwdriver to push the release spring inside 

the square hole (A). While the release is being pushed, 

insert the wire into the larger circular hole (B). Remove the 

screwdriver to secure the wire into place.

A

B

A.C. ELECTRICAL CONNECTIONS

NOTICE: CLASS 1 WIRING METHODS ARE TO BE USED FOR 

ALL FIELD WIRING CONNECTIONS TO TERMINALS OF A 

CLASS 2 CIRCUIT

WARNING:

A mainline circuit breaker has been provided inside the 

generator housing. During all wiring installation, make 

sure the breaker is in the off position and the generator is 

disabled. 

WARNING: 

Make sure the generator is disconnected from the battery to 

prevent accidental starting. 

The connection box shown are typical arrangements. 

A. NEUTRAL LUGS:

These lugs are isolated from ground and provided for you 

to connect your neutral wire from the transfer switch to the 

generator.

The 225 Amp terminal block lugs will handle wire size #4 to 

300 MCM and should be torqued to 250 in. lbs.

B. GENERATOR CIRCUIT BREAKER:

This circuit breaker provides overload protection for the 

generator. Your power feeds from the transfer switch 

will connect the bottom lugs on the circuit breaker. The 

generator power feeds have already been wired into the 

upper lugs.

Please refer to the circuit breaker installed on your unit for 

breaker lug capacities and proper toque specifications.  

To select the proper conductor size between the generator 

and the ATS, first look your model up in Table 1 of Appendix 

“A” for your generator amperage, found further in this 

manual. Then refer to Appendix “2” for guidance on wire 

sizing based on both wire type and amperage.

For additional information on wire sizes, refer to table 310-

16 of the National Electrical Code ANSI/NFPA 70.

C. GROUND LUG:

These ground lugs are bonded to ground and are provided 

for you to connect your ground wire from the transfer 

switch to. The lugs will accommodate #10 AWG to 2/0 

AWG and should be torqued to 200 in. lbs.

D: 120V GFCI CIRCUIT TERMINAL BLOCK:

These terminals are rated for 85 Amps and will handle wire 

sizes #4 AWG to 18AWG. They should be torqued to 16 

in. lbs. This circuit must be fed from a fused circuit in the 

distribution panel and provides power for the block heater 

and the battery charger.

Summary of Contents for DR20I4-/1 Series

Page 1: ...AL 1 DEG ANGULAR 9 15 2016 ZJF COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours If you should ever need to contact us on this unit it will help us to...

Page 2: ...FILTER CLEANING RADIATOR CHANGING THE FUEL FILTER STORAGE MAINTENANCE SCHEDULE TROUBLESHOOTING TABLE 16 ENGINE HARNESS SCHEMATIC 17 WIRING SIZE TABLE 17 DSE7310 WIRING DIAGRAM 18 WIRING DIAGRAMS 19 LI...

Page 3: ...k exhaust gas asphyxiation or fire Please read all safety instructions carefully before installation or use Keep these instructions handy for future reference Take special note and follow all warnings...

Page 4: ...everal of the major components also have their own individual data plates providing additional information to document build data for warranty and replacements parts Be sure to have the main WINCO uni...

Page 5: ...enerator for operation take a couple of minutes to ensure the unit you have received is the correct model and review the specification pages in this manual to ensure that this unit meets your job requ...

Page 6: ...aller The factory weather enclosures are acoustical housing intended for outdoor installation only Factory weather enclosed units are not intended to be used indoors and no support is available to ass...

Page 7: ...pipe to aid your installation Ensure proper alignment with the generator The flex can be eliminated if it is pushed to one side to make a connection The most direct path possible should be used to ge...

Page 8: ...ert the wire into the larger circular hole B Remove the screwdriver to secure the wire into place A B A C ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNE...

Page 9: ...ries of remote accessories that can help provide useful information to operators These accessories communicate over the DSE Net Terminal blocks are wired to the distribution panel to aid in installati...

Page 10: ...must be clean and tight Depending on your battery type check the electrolyte in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharged condition...

Page 11: ...N PERSONAL INJURY Only check oil when the engine is not running and is at a low temperature in order to avoid the risk of burns 1 Remove the dipstick and ensure the oil level is between the Min and Ma...

Page 12: ...AC On three phase panels the G2 voltage level should also be checked ON 240 VOLT DELTA SYSTEMS BE SURE YOU KNOW WHERE THE HIGH VOLTAGE WILD LEG IS IT MUST BE IN THE SAME LOCATION ON THE LINE SIDE AS I...

Page 13: ...not connected to a battery charger A solar charger kit is the easiest way to always maintain the battery during storage in mobile applications The supplied battery charger can be plugged in to an exte...

Page 14: ...O NOT dispose or allow oil to seep into the ground or sewer systems doing so will cause environmental damage CHANGING OIL FILTER The filter must be replaced when the lubricant oil is changed Only use...

Page 15: ...iquid in accordance to local codes DO NOT dispose or allow liquid to seep into the ground or sewer systems doing so will cause environmental damage CLEANING RADIATOR The surfaces of the radiator come...

Page 16: ...citer stator AC short in the output leads Defective open generator output breaker Wiring error protective liquid ISO 4113 and introduce the liquid by pressurizing the circuit and driving the engine fo...

Page 17: ...418 431 458 480 519 550 572 585 50 68 86 100 118 137 155 177 205 237 264 291 319 346 391 432 473 487 505 532 560 605 642 669 683 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 600 700 750 800 900 100...

Page 18: ...18 OPM 135 C DSE7310 WIRING DIAGRAM...

Page 19: ...WIRING DELTA SINGLE PHASE 120 240 VOLTS SINGLE PHASE AC WIRING 4 LEAD WIRING DIAGRAMS 24 60708 165 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480...

Page 20: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...

Reviews: